Problem Overview
Engineers upgrading from SIMATIC WinCC Professional V13 SP1 Update 9 to WinCC Professional V14 (part of the TIA Portal V14 product family, released in 2017) frequently encounter a silent install failure: the TIA Portal setup launches without an explicit error code, but the WinCC Professional product components are greyed out and cannot be selected in the product tree. The setup completes, but only STEP 7 and WinCC Basic features are installed, leaving the HMI/SCADA engineering environment for WinCC Professional absent.
This article consolidates the field-confirmed root causes, diagnostic steps, and remediation procedure for the most common WinCC Professional V14 install failures following a V13 SP1 uninstall. The same procedure applies to subsequent TIA Portal V14.x service packs, V15/V15.1, and to users migrating from TIA Portal V16/V17 to V18 where a downgraded or mixed-version SQL footprint exists.
Symptoms of the Install Failure
Three primary symptoms indicate the failure mode described in this article:
- Greyed product components — the WinCC Professional V14 setup dialog lists WinCC Professional ES, WinCC Professional RT, and related options as present but non-selectable, even when only the WinCC Professional media is being installed.
-
No error code or event log entry — the setup exits with return code 0 and the Siemens Setup log file (
%TEMP%\Siemens\Setup\Logs\) contains no "failed" or "rolled back" entries. - STEP 7 Professional V14 and/or WinCC Basic V14 install successfully — only the WinCC Professional component family is affected, which is the diagnostic fingerprint that the issue is component-specific and not a TIA Portal framework failure.
0x80091007 (hash mismatch) or 0x80072EE2 (DNS resolution), the cause is media corruption or proxy mis-configuration, not the SQL/parallel-install issue described here. Consult the Siemens TIA Portal installation manual for those codes.
Root Cause Analysis
Three interacting conditions cause WinCC Professional V14 to refuse a clean install on a machine that previously hosted WinCC Professional V13 SP1 Update 9:
Cause 1 — Residual SQL Server Instances
WinCC Professional V13 SP1 Update 9 installs two Microsoft SQL Server instances: the WINCC instance (used by the WinCC archive and runtime databases) and, when configured for archiving, a separate WINCCPLUS instance. The TIA Portal uninstaller does not remove these instances; it only removes the WinCC client components that connect to them. When the V14 setup detects that one or both instances already exist, it skips the SQL Server install step but cannot re-bind the V14 binaries to the V13 instance, leaving the product tree disabled.
Cause 2 — WinCC Basic V14 Already Installed
The TIA Portal V14 product line is composed of three distinct WinCC editions: WinCC Basic, WinCC Comfort/Advanced, and WinCC Professional. These editions share a common TIA Portal shell but use mutually exclusive runtime binaries. WinCC Basic V14 and WinCC Professional V14 cannot coexist on the same machine at the same major version. If a user installs STEP 7 Professional V14 with the WinCC Basic option checked (a common default in the V14 product line installer), the subsequent WinCC Professional V14 install will detect the WinCC Basic V14 footprint and disable its own components to prevent file overwrites.
Cause 3 — Microsoft Message Queuing Not Installed
WinCC Professional V14's setup prerequisite scan requires Microsoft Message Queuing (MSMQ) to be present on the target operating system. MSMQ is an optional Windows Server feature that is not enabled by default on Windows 10 1607+ or Windows Server 2016. The TIA Portal V14 setup checks for MSMQ early in the product tree enumeration; when MSMQ is missing, WinCC Professional V14 silently de-registers from the install set on Windows installations where the option cannot be enabled offline.
Prerequisites
Before executing the remediation procedure, confirm the following:
- Local administrator rights on the target machine
- The TIA Portal V14 installation media (DVD or downloaded ISO from the Siemens Industry Online Support portal)
- License keys for WinCC Professional V14 (transferred to the local license server or USB dongle)
- Operating system: Windows 7 SP1 (64-bit), Windows 10 1607+ (64-bit, Pro/Enterprise), or Windows Server 2008 R2 SP1 / 2012 R2 / 2016 — all are supported by TIA Portal V14 per the TIA Portal V14 system requirements.
- A current backup of all V13 SP1 projects and the WinCC archive database (
*.ldf/*.mdffiles in%ProgramFiles%\Siemens\Automation\WinCC OLE DB\or the configured archive path)
Diagnostic Procedure
Run the following checks before attempting any remediation. Each check corresponds to one of the three root causes above.
Check 1 — Installed Siemens Software Inventory
Open Control Panel → Programs and Features and sort by publisher "Siemens AG". Capture a screen of every entry. Look for any combination of the following installed product names:
| Product Name (as listed in Programs and Features) | Indicates |
|---|---|
| SIMATIC STEP 7 Professional V14 | TIA Portal framework installed |
| SIMATIC WinCC Basic V14 | WinCC Basic footprint present — blocks WinCC Professional V14 |
| SIMATIC WinCC Comfort V14 | WinCC Comfort/Advanced footprint present — blocks WinCC Professional V14 |
| SIMATIC WinCC Professional V14 | Partial V14 install exists — complete uninstall required |
| SIMATIC WinCC Professional V13 SP1 | Uninstall did not complete cleanly |
Check 2 — SQL Server Instance Inventory
Open Microsoft SQL Server Configuration Manager → SQL Server Services. Record every instance listed. Expected WinCC-related instance names:
-
WINCC— used by WinCC Professional V13/V14 archive and runtime -
WINCCPLUS— used by WinCC Runtime Professional and WinCC V7 when configured for process historian data -
SQL2014WINCCorSQL2017WINCC— named instances bundled with the Siemens SQL setup
Check 3 — Windows Optional Feature State
Open Control Panel → Programs → Turn Windows features on or off. Scroll to Microsoft Message Queuing (MSMQ) and confirm whether the parent node or any sub-features are checked. Note the current state.
Step-by-Step Remediation
Execute the steps in the exact order below. Skipping a step or reversing the order will result in a partial or failed re-install.
Step 1 — Uninstall WinCC Basic V14 (or WinCC Comfort V14)
- Close all TIA Portal instances, including the TIA Portal Help System and the TIA Administrator Service.
- Stop the
Siemens TIA Administratorservice viaservices.msc. - Open Control Panel → Programs and Features.
- Right-click SIMATIC WinCC Basic V14 (or SIMATIC WinCC Comfort V14) and select Uninstall.
- Confirm the uninstall and allow the TIA Portal setup to remove shared files.
- Restart the machine when prompted.
Step 2 — Remove Residual SQL Server Instances
The TIA Portal uninstaller leaves SQL Server instances intact. Use one of the two removal paths below.
Path A — Standard Programs and Features Removal
- Open Control Panel → Programs and Features.
- For each entry that contains "Microsoft SQL Server" AND matches a version of
SQL Server 2014,SQL Server 2016, orSQL Server 2017(the three versions bundled with TIA Portal V14 through V17):- Right-click and select Uninstall.
- When the SQL Server Installation Center appears, choose Removal.
- Select the named instance (
WINCCorWINCCPLUS) and proceed.
- Reboot the machine.
- Verify in SQL Server Configuration Manager that the WinCC-related instances no longer appear under SQL Server Services.
Path B — Manual Removal of Orphaned Instances
If Path A fails (typically when the SQL Server 2014/2016/2017 instance is missing from Programs and Features because the uninstaller metadata was removed) perform the manual cleanup:
- Open regedit as Administrator.
- Navigate to
HKLM\SOFTWARE\Microsoft\Microsoft SQL Server\Instance Names\SQLand delete the value(s) forWINCCandWINCCPLUS. - Navigate to
HKLM\SOFTWARE\Microsoft\Windows\CurrentVersion\Uninstalland search for subkeys whoseDisplayNamecontains "Microsoft SQL Server" and references a removed WinCC install — delete the corresponding subkey. - Open SQL Server Configuration Manager → SQL Server Services and stop any service whose Binary Path contains the orphaned instance.
- Delete the physical data directories:
-
C:\Program Files\Microsoft SQL Server\MSSQL12.WINCC\(SQL 2014) -
C:\Program Files\Microsoft SQL Server\MSSQL13.WINCC\(SQL 2016) -
C:\Program Files\Microsoft SQL Server\MSSQL14.WINCC\(SQL 2017)
-
- Reboot the machine.
%ProgramFiles%\Microsoft SQL Server\ directory to a safe location before deleting is strongly recommended. If a third-party application is using the same SQL Server instance, do not delete it.
Step 3 — Install Microsoft Message Queuing (MSMQ)
- Open Control Panel → Programs → Turn Windows features on or off.
- Expand Microsoft Message Queuing (MSMQ) Server.
- Check MSMQ Server Core and, for domain-joined controllers, also check Active Directory Domain Services Integration and Routing Support.
- Click OK. Windows will copy the required files and enable the service.
- Verify that the
Message Queuingservice is set to Automatic startup inservices.msc.
Step 4 — Remove Any TIA Portal V14 Footprint
- Open Control Panel → Programs and Features.
- Uninstall in this order:
- SIMATIC WinCC Professional V14 (if listed)
- SIMATIC STEP 7 Professional V14 (if listed)
- SIMATIC TIA Portal V14 components
- Reboot the machine.
- Verify the
%ProgramFiles%\Siemens\Automation\directory contains no V14-era folders (e.g.,Portal V14,TIA Portal V14).
Step 5 — Reinstall WinCC Professional V14
- Insert the TIA Portal V14 DVD or mount the ISO.
- Run
Start.exeas Administrator. - Select WinCC Professional V14 in the product tree. All WinCC Professional components (ES, RT, Recipes, Logging, OPC) must be selectable.
- Choose Complete or Custom install as required by the project scope.
- Click Install. The setup will re-create the SQL Server
WINCCinstance, install MSMQ-aware components, and register the WinCC Professional runtime. - When the setup completes, reboot the machine.
Verification
Confirm the install succeeded by performing the following checks:
- Programs and Features — confirm SIMATIC WinCC Professional V14 is listed with the expected version (e.g., V14.0.0.0 or the applied Update).
-
SQL Server Configuration Manager — confirm the
WINCCinstance is present and theSQL Server (WINCC)service is running. - TIA Portal — open the TIA Portal V14, create a new project, add an HMI device with type "WinCC Runtime Professional", and confirm the device is added without an "incompatible runtime" warning.
- WinCC Explorer — launch WinCC Explorer from the Windows Start menu. The Computer properties dialog must list all activated packages.
-
MSMQ Service — in
services.msc, confirmMessage QueuingandMessage Queuing Triggers(if installed) are set to Automatic and in the Running state.
Parallel Installation Constraints Across TIA Portal Versions
Per the official Siemens Parallel installation of TIA Portal documentation, the parallel-installation matrix for WinCC Professional is intentionally narrow. The following rules apply across all TIA Portal major versions:
- Parallel installation of WinCC Professional V14 (ES or RT) with an earlier version of WinCC Professional (ES or RT) is not permitted on the same machine.
- Parallel installation of WinCC Professional V21 (ES or RT) with an earlier version of WinCC Professional (ES or RT) is not permitted.
- WinCC Basic and WinCC Professional of the same major TIA Portal version cannot coexist — uninstall one before installing the other.
- WinCC Comfort/Advanced and WinCC Professional of the same major TIA Portal version can coexist with STEP 7 Professional, but not with each other.
If parallel operation of two WinCC Professional versions is required (for example, V14 ES to maintain a V13 project and V16 ES to develop a V16 project), use one of the following approaches:
- Run the secondary version in a Windows virtual machine (Hyper-V or VMware Workstation) using USB passthrough for the license dongle.
- Use a second physical machine and synchronize projects via TIA Portal multi-user server or Git-based PLC project versioning.
- Maintain a dual-boot configuration with separate Windows installations for each TIA Portal major version.
Field-Proven Caveats
The following constraints have been observed in production environments and should be considered before, during, and after the remediation:
-
Anti-virus interference — CrowdStrike, SentinelOne, and Windows Defender real-time scanning can intercept the SQL Server installer's file-copy phase and silently roll back the install. Add an exclusion for
%ProgramFiles%\Microsoft SQL Server\and the Siemens install paths before re-running the setup. - UAC elevation — TIA Portal V14 setup must be launched as Administrator. The TIA Portal framework is UAC-aware, but the embedded SQL Server installer is not; partial-elevation failures are reported as a successful setup with missing components.
- Windows 10 1809 / 1903 — TIA Portal V14 is not officially supported on Windows 10 1809 or later per the system requirements. For new deployments, use Windows 10 1607 (LTSB 2016) or upgrade to TIA Portal V15.1 or later.
- Project compatibility — WinCC Professional V14 can open V13 SP1 projects after the install is complete, but the project will be upgraded in place. Back up the project before opening it for the first time in V14.
- License migration — WinCC Professional V13 SP1 licenses must be returned to the license server before the V14 license can be activated on the same seat. Use the Automation License Manager to transfer or float the licenses.
- Domain vs. workgroup — the WinCC Professional V14 setup will run successfully on a workgroup-joined machine, but runtime redundancy features (master/standby) require an Active Directory domain and proper MSMQ routing configuration.
Troubleshooting Matrix
| Observed Symptom | Likely Cause | Remediation |
|---|---|---|
| WinCC Professional V14 greyed out, WinCC Basic V14 selectable | WinCC Basic V14 footprint blocks Professional install | Uninstall WinCC Basic V14 per Step 1 |
| WinCC Professional V14 greyed out, STEP 7 V14 installed | Residual SQL Server instance from V13 SP1 | Uninstall SQL Server instances per Step 2 |
| WinCC Professional V14 greyed out, clean machine | MSMQ not enabled | Install MSMQ per Step 3 |
| Setup terminates with no error, no components installed | Anti-virus or UAC interference | Add AV exclusions, run as Administrator |
| SQL Server (WINCC) service fails to start | Orphaned instance registry entries | Perform Path B manual cleanup in Step 2 |
| "Incompatible runtime" warning when adding HMI device | WinCC Basic V14 and Professional V14 share project file | Remove WinCC Basic V14, reopen project |
Related Upgrade Paths
The same SQL/parallel-install conflict pattern applies to subsequent TIA Portal major versions. The matrix below summarizes the upgrade target for common production scenarios:
| Source Version | Target Version | Clean Uninstall Required? | SQL Cleanup Required? |
|---|---|---|---|
| WinCC Professional V13 SP1 | WinCC Professional V14 | Yes | Yes |
| WinCC Professional V14 | WinCC Professional V15 / V15.1 | Yes | Yes |
| WinCC Professional V15.1 | WinCC Professional V16 | Yes | Yes |
| WinCC Professional V16 | WinCC Professional V17 | Recommended | Recommended |
| WinCC Professional V17 | WinCC Professional V18 / V19 | Recommended | Recommended |
For in-place upgrades, the TIA Portal installer provides an Upgrade option that performs the SQL and product-tree reconciliation automatically. In-place upgrade is preferred over uninstall/reinstall when the project must be preserved without re-import. When the in-place upgrade fails with the same greyed-out component symptom, fall back to the manual procedure documented in this article.
FAQ
Why is WinCC Professional V14 greyed out after I uninstalled V13 SP1 Update 9?
Three conditions block the V14 install: (1) a residual SQL Server WINCC or WINCCPLUS instance from V13, (2) WinCC Basic V14 already installed, and (3) Microsoft Message Queuing not enabled. Remove all three conditions before re-running the V14 setup.
Can I install WinCC Basic V14 and WinCC Professional V14 on the same machine?
No. Per the Siemens parallel installation documentation, WinCC Basic and WinCC Professional of the same major TIA Portal version cannot coexist. Uninstall WinCC Basic V14 before installing WinCC Professional V14.
How do I remove a residual WINCC SQL Server instance manually?
Open SQL Server Configuration Manager and uninstall the named instance via the SQL Server Installation Center. If the instance is not listed, delete the registry keys under HKLM\SOFTWARE\Microsoft\Microsoft SQL Server\Instance Names\SQL and remove the MSSQL*.WINCC data directories under C:\Program Files\Microsoft SQL Server\. Reboot after removal.
Is Microsoft Message Queuing (MSMQ) required for WinCC Professional V14?
Yes. The TIA Portal V14 setup prerequisite scan requires MSMQ to be installed and the service set to Automatic. Enable it via Control Panel → Programs → Turn Windows features on or off → Microsoft Message Queuing Server → MSMQ Server Core.
Can I run WinCC Professional V14 and V13 SP1 on the same machine in parallel?
No. The TIA Portal parallel installation rules prohibit parallel installation of two WinCC Professional major versions on the same machine. Use a virtual machine or a second physical machine to maintain two versions.