Troubleshooting WinCC V6.0 SP4 Server/Client Runtime Freezes

David Krause15 min read
SiemensTroubleshootingWinCC
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Troubleshooting WinCC V6.0 SP4 Server/Client Runtime Freezes

Random runtime freezes on a WinCC V6.0 SP4 Server/Client configuration typically present as a single client (or the server) stalling for tens of seconds while counters continue incrementing. Screens fail to load, the Graphics Runtime stops repainting, and the operator must exit Runtime and close WinCC Explorer to recover. The companion server (or the other clients) may continue serving requests, or may itself appear to "freeze" for roughly 60 seconds before returning to normal. The most common root causes documented in V6.0 SP4 deployments are: (1) ActionOverflow on the script engine when a C/B- or VBS-action enters a tight loop, (2) illegal tag addresses being polled continuously by an action, (3) Ethernet physical-layer faults (intermittent cable breaks, marginal RJ-45 crimps, USB-hub keyboard/mouse chatter on a client), and (4) a known runtime behavior internally referred to as slinkysearch that affects picture-cache lookup. This article consolidates the diagnostic workflow, the exact log signatures, and the verified remediation steps.

1. Symptom Matrix: Server vs. Client Behavior

Before chasing the cause, classify the freeze. WinCC V6.0 SP4 freeze behavior is not symmetric between server and client roles because the picture cache, tag subscription, and script execution models differ.

Symptom Server Client (main) Client (other) Most Likely Root Cause
Runtime stops repainting for ~60 s, recovers automatically Yes No (counters continue) No ActionOverflow on server-side script (action > 5000 in queue)
Random hang, must exit Runtime + close WinCC Explorer No Yes No Local USB/peripheral interference, picture cache slinkysearch, or local script loop
All clients freeze simultaneously, server unaffected No Yes Yes Faulty Ethernet run between server and switch (replace cable first)
Tag values update but picture change returns "no picture" Yes Yes Yes Picture cache or ODBC archive writer blocking main thread
ActionOverflow 1007000 in WinCC diagnostics log Logged on server or client Logged Script in tight loop or blocking call; check UnLoadFctAll nCount growth
Field note: If the server freezes for ~60 s and the client stays responsive, the server script engine is the prime suspect. If only one client freezes while the server and other clients are fine, the cause is local to that client (USB hub, video driver, picture cache, or the client's own actions).

2. Required Diagnostic Artifacts

Collect the following from every affected machine before restarting Runtime. They form the evidence trail for a single-ticket resolution.

  1. WinCC Diagnostics folder<ProjectPath>\Diagnostics\*.log from the affected server and client. Includes WinCC_Sys_<date>.log, WinCC_Script_<date>.log, and connection logs.
  2. APDiag / ODBC trace — tag polling history for the suspected illegal address (e.g., C-210_YA_1200A.Value).
  3. Windows Event Viewer — System and Application logs filtered for the freeze timestamp; look for source WinCC, S7DOS, CCAgent, and NDIS / TCPIP warnings.
  4. Network capture — short Wireshark or netsh trace capture on the server NIC during the next freeze (mirror the port or use a hub).
  5. Process dumpprocdump -ma CCExplorer.exe or Task Manager → Create Dump File when Runtime hangs.
  6. Ping and tracert results from the affected client to the server, to each PLC (S7-300/400/1200/1500), and to the switch management IP.

3. Reading the WinCC Diagnostics Log

WinCC V6.0 SP4 writes messages with a fixed numeric prefix. The four signatures below account for the majority of random-freeze tickets.

Message ID Severity Exact String Meaning Action
(none, ERROR) ERROR Illegal tag address "<TagName>.Value"! Action/Dynamization requested a tag that does not exist on the configured AS connection Fix the tag spelling/structure, or recreate the tag and recompile the OS
1007007 ERROR (4) SCRIPT, Deactivation : Action was stopped by script An action explicitly terminated another running action (e.g., via Stop or process kill) Audit the script; remove aggressive Stop() calls or restructure triggers
1007001 WARNING (4) SCRIPT, UnLoadFctAll nCount <n> WinCC tore down all running script functions (typical after ActionOverflow or crash) Cross-reference to the 1007000 line that triggered the unload
1007000 ERROR (4) SCRIPT, ActionOverflow:more than 5000 Actions to work Internal action queue overflowed; runtime is in a degraded state Locate the looping action; reduce trigger frequency; split work into async tasks
Critical: The 1007000 line almost always appears within seconds of the user-visible freeze. Search the diagnostics folder with findstr /S /I "1007000" *.log and inspect the previous 50 lines — the offending action is the one whose trigger fired most recently with no corresponding completion record.

4. ActionOverflow — Root Cause and Resolution

4.1 Why 5000 actions matter

Each WinCC action (C script, VBS, or global action) is dispatched onto a Windows thread pool. WinCC maintains a FIFO queue with a hard cap of 5000 pending actions. When an action is triggered but blocks — for example, by a synchronous MS_HMIRuntime.Tags read on a dead connection, a Wait on a synchronizing object, an external COM call, or a tight For loop with no DoEvents — every subsequent trigger piles up. Once the cap is reached, 1007000 ActionOverflow is logged and UnLoadFctAll tears the whole script set down. The Graphics Runtime then has to reload the picture and reinitialize the script engine, producing a visible 30–90 s "freeze."

4.2 Verifying the queue depth in real time

On the affected server or client, open WinCC Explorer → Tools → Status of Actions (or call the internal API PDLRTGetActionsStatus). The current queue length and longest-waiting action are displayed. Values approaching 1000 sustained, or any single action with > 5 s wait, are a leading indicator of an imminent ActionOverflow.

4.3 Common coding patterns that cause ActionOverflow

Pattern Trigger Frequency Failure Mode Fix
250 ms trigger with synchronous HMIRuntime.Tags(tag).Read against a non-responsive AS 4 Hz Queue fills in 21 minutes if the AS is offline Use direct tag request with a state check, or extend trigger to 1 s minimum
Trigger on a tag that changes 50×/s (raw encoder value) 50 Hz Queue fills in 100 s Debounce via a 1-Hz global action, or use Tag Logging smoothing
Action calls HMIRuntime.Screens.Item(...).ScreenItems(...).Properties(...) in a loop on picture load Per picture open Hangs while picture window is open; counters OK but no repaint Move configuration to picture properties; use SmartTags for the dynamic parameter
Action contains a Do...Loop While True with no Sleep or DoEvents 1 Hz Monopolizes thread; UnLoadFctAll on first watchdog tick Use Application.Sleep (C) or WScript.Sleep (VBS) ≥ 200 ms inside any loop
Action performs a synchronous ADODB.Connection.Execute on a blocked archive 1–10 Hz Backpressure into the script queue Asynchronous recordsets; do not query archive DBs from picture-window triggers

4.4 The "nCount 359" interpretation

When you see UnLoadFctAll nCount 359 in the log, the nCount value is the number of action objects forcibly unloaded. A non-trivial nCount immediately preceding a 1007000 confirms the unload was triggered by the overflow, not by a clean project stop. The exact number can also be cross-referenced to the number of configured actions in the picture to find the one that was missing from the unload set (i.e., the one that didn't return from its last call).

5. Illegal Tag Address Errors

The log line ERROR Illegal tag address "C-210_YA_1200A.Value"! indicates the action framework evaluated a tag reference for which WinCC cannot find a matching internal tag definition. The reference is to a tag in a user-defined structure (UDS) or a connection-prefixed address. The three things to verify:

  1. Structure element exists: Open the tag in WinCC Tag Management and confirm that C-210_YA_1200A is the full tag name and that the structure element is a member, not a sub-structure. The .Value suffix is added by the runtime; you do not type it in the script.
  2. Connection is online: The PLC may be online, but the S7 connection used to read this tag may be a different one. Cross-check Tag Management → [Connection] → Properties → Connection Name against the project's connection list.
  3. Type compatibility: An action trying to assign a string to a numeric tag, or to call .Value on a raw bit, will throw this. Use .Read with type checking, or address the tag directly as a SmartTag.
Important: A single action that polls an illegal tag at high frequency will, in addition to logging the error, still consume script queue slots, leading to a secondary ActionOverflow. Fix the tag before tuning the trigger.

6. Network Integrity Verification

6.1 Ping baseline

Run the following from each WinCC machine:

ping -n 100 -l 1024 <ServerIP>
ping -n 100 -l 1024 <PLC1IP>
ping -n 100 -l 1024 <PLC2IP>
ping -n 100 -l 1024 <SwitchMgmtIP>

Acceptable values for V6.0 SP4 are:

Hop Mean RTT (ms) Max RTT (ms) Packet Loss (%)
Server ↔ Client (same subnet) < 1 < 5 0
Client ↔ S7 PLC < 5 < 30 0
Server ↔ Switch Mgmt < 2 < 10 0

Anything above this, or any non-zero loss, indicates a Layer-1 or Layer-2 issue that masquerades as a WinCC freeze because the Graphics Runtime's tag subscription times out and the picture cannot be repainted.

6.2 tracert usage in a flat plant LAN

If the affected machine is in the same subnet as the destination, tracert will normally return only a single hop (the destination itself), because Windows routers do not decrement TTL on a same-subnet delivery. The diagnostic value of tracert on a WinCC client is therefore limited to confirming routing topology, not detecting cable faults. Use it to verify the path traverses no more than two routers:

tracert -d -h 5 <ServerIP>

More than two hops in a plant LAN usually means a misconfigured gateway or a rogue device acting as a router.

6.3 Physical-layer checks

A broken or marginal Ethernet cable between the WinCC server and the core switch will produce a freeze on all clients simultaneously while the server's local graphics continue to update. This is the most commonly reported cause of "all clients freeze" tickets. The two practical checks are:

  1. Swap the suspected patch cable for a known-good CAT5e or CAT6 cable, observing 100 Mbit/s or 1 Gbit/s link LED on both ends.
  2. Use a cable tester (Fluke MicroScanner or equivalent) to verify all eight conductors pass continuity and the pair-to-pair resistance is < 0.5 Ω on each pair.

USB-hub-attached peripherals on a WinCC client have also been reported to cause local freezes. Eliminate the hub as a variable by moving the keyboard and mouse to direct PS/2 (via an active PS/2-to-USB adapter only if the motherboard has PS/2 ports) or to direct USB ports on the client. The original ticket that prompted this article was resolved by replacing the USB hub with PS/2 extensions.

7. The "SlinkySearch" Behavior

Slinkysearch is the colloquial name used by Siemens development for the picture-cache lookup algorithm in the V6.0 SP4 picture window subsystem. Under specific conditions — typically when a base picture contains hundreds of faceplates or dynamic dialogs and a hot-key navigates through several picture windows in rapid succession — the cache traversal exceeds the watchdog budget and the runtime pauses for several seconds. A pre-SP4 hotfix was eventually distributed to address this; on SP4 deployments, the workaround is to reduce the number of nested picture windows per base picture, to keep faceplate instances < 200 per picture, and to disable the picture cache for navigation-heavy screens.

7.1 Disabling the picture cache per picture

  1. Open the affected picture in Graphics Designer.
  2. Right-click the picture window → Properties.
  3. Clear Cache after leaving the picture.
  4. Set Update to On change rather than On Show if the picture does not need to be repainted on every navigation.

Disabling the cache increases picture-open time but eliminates the slinkysearch pause, which is an acceptable trade-off in operator-HMI applications where correctness beats load time.

8. Step-by-Step Resolution Procedure

Follow this sequence in order. Do not skip steps; each gates the next.

  1. Capture the freeze. When the next freeze occurs, immediately Task Manager → right-click CCExplorer.exeCreate Dump File. Also click Take Stack Trace if you have procdump installed.
  2. Grep the diagnostics folder. findstr /S /I "1007000 Illegal ActionOverflow Deactivation" "C:\<Project>\Diagnostics\*.log"
  3. If 1007000 is present: identify the looping action (Section 4.3) and fix per the table. Re-test.
  4. If only "Illegal tag address" is present: fix the tag reference (Section 5) and re-test.
  5. If neither is present: run the network integrity checks (Section 6). Replace the server-to-switch patch cable first; it is the cheapest fix and the most common cause of multi-client freezes.
  6. If the problem is single-client only: check the local USB hub, replace the keyboard/mouse with PS/2 or direct USB, update the video driver, and disable the picture cache on heavily nested picture windows (Section 7).
  7. Re-test with logging enabled: WinCC Explorer → Computer → Properties → Graphics Runtime → Activate Diagnostics. Reproduce the scenario three times.
  8. If the freeze persists: open a Siemens support ticket referencing the dump, the log, the network capture, and the action names suspected.

9. Verification Checklist

Use this checklist to confirm a permanent fix. Every item must be green for 72 continuous hours of production operation.

Check Pass Criterion Verification Command / Method
No 1007000 events in 72 h 0 occurrences findstr /S /I "1007000" *.log across the diagnostics folder
No illegal tag address events 0 occurrences findstr /S /I "Illegal tag address" *.log
Action queue peak < 100 Continuous, all shifts Status of Actions dialog / PDLRTGetActionsStatus API
Ping RTT server < 5 ms, loss 0% 24 h sample ping -t <ServerIP> | findstr "loss"
All clients repaint < 500 ms All 1-Hz navigation paths Operator walk-through with stopwatch
No 60 s stalls observed 0 occurrences Operator log entries

10. Common Pitfalls

  • Restarting the server is not a fix. The ActionOverflow will re-occur on the next triggering event. Always fix the action, not the symptom.
  • Increasing the 5000-action cap is not supported. WinCC V6.0 SP4 has a fixed internal queue; the only knob is the action's own trigger frequency and execution time.
  • Tracert is not a cable tester. A passing tracert proves only that routing is configured correctly; it does not detect a marginal pair or a broken shield.
  • Ignoring "Deactivation : Action was stopped by script". This is a warning, not an error, but it indicates a script is killing peer actions, which is almost always the signature of a poorly written watchdog.
  • Tuning tag logging/archiving times to a lower value is not a WinCC freeze remedy. It changes the archive load, not the script queue depth. It is useful only when the freeze is correlated with archive writer blocking the main thread.

11. When to Escalate

Escalate to Siemens Technical Support with the dump and logs when any of the following is true:

  • No 1007000, no illegal tag address, network is clean, and the freeze still occurs.
  • The freeze coincides with a specific picture change that includes a slinkysearch pattern.
  • The dump shows the main thread blocked in WaitForSingleObject on a non-script handle (an S7DOS read against an offline CP).
  • Multiple V6.0 SP4 sites report the identical pattern; this is a candidate for a Siemens Hotfix request.

For the authoritative reference, consult the Siemens Industry Online Support entry for WinCC V6.0 SP4 and the WinCC V6.0 SP4 Service Pack Release Notes. For S7 connection diagnostics, the S7DOS / S7 Communication Diagnostics Manual describes the trace log fields that appear in the same diagnostics folder. Tag configuration details for V6.x are in the WinCC Information System under Tag Management → Internal Tags / External Tags.

FAQ

What does the "ActionOverflow: more than 5000 Actions to work" message mean?

It means the WinCC script engine has more than 5000 actions queued and waiting to run, almost always because one action is blocking the dispatch loop. The script framework then calls UnLoadFctAll and tears down the action set, producing a 30–90 s visible freeze. Locate the blocking action (typically a synchronous tag read, a tight loop without Sleep/DoEvents, or a blocking COM call) and either raise its trigger period to ≥ 1 s, add a Sleep, or convert synchronous I/O to asynchronous.

Why does only the server freeze for ~60 s while the client keeps running?

The server hosts the project scripts, the archive writer, and the picture cache for shared screens. A server-side action in a tight loop will fill the server's action queue; the client, which receives only picture changes and tag values, sees a brief stall but recovers when the server's UnLoadFctAll completes. Counters increment on the client because the tag subscription is independent of the script engine. The fix is on the server: find and repair the looping action.

Can a faulty Ethernet cable really cause WinCC to freeze on all clients?

Yes. A marginal cable between the WinCC server and the core switch causes S7 and internal WinCC keep-alive packets to be dropped, which causes the Graphics Runtime to stall while waiting for retransmits. The cheapest diagnostic is to swap the suspect patch cable for a known-good one. A cable tester confirming all eight conductors and < 0.5 Ω pair resistance is the definitive check.

How do I find which specific script is causing the ActionOverflow?

Search the diagnostics folder for "1007000" and inspect the 50 lines immediately before it. The action whose trigger timestamp last advanced without a corresponding completion record is the suspect. You can also enable Status of Actions in WinCC Explorer to see the live queue and the longest-waiting action name. Bisect by disabling half the actions in the affected picture and re-running until the overflow stops.

What is the difference between "Deactivation : Action was stopped by script" and ActionOverflow?

Deactivation (message 1007007) is logged when one action explicitly calls Stop on another — usually an application-level watchdog. ActionOverflow (1007000) is logged when the queue hits 5000 pending actions. They often appear together: a watchdog notices the queue is filling and tries to stop the offending action, but by then the queue is already past the cap and UnLoadFctAll runs anyway. Treat 1007007 as a warning and 1007000 as the actual incident.

Does reducing tag logging archive times fix WinCC freezes?

Not directly. Archive configuration affects the archive writer thread and the ODBC/SQL load; it does not affect the script action queue. Reducing archive times can help if the freeze coincides with archive commits blocking the main thread, but it will not resolve an ActionOverflow caused by a looping script. Tune archive times only when archive-related symptoms (slow trending, archive write errors) are present alongside the freeze.

Back to blog