Twin Lobe Blower High Amps: Process Load, Not the Motor

Ryan Tanaka6 min read
Motor ControlOther ManufacturerTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

The panel shows one 50 HP twin lobe blower at 62-63 A while an identical blower and motor run at 51-52 A. Replacing the motor did not change the current, so start with the process and blower load, not another motor. The first checks are local suction pressure, discharge pressure, valve position, and pipe resistance under matched operating conditions.

Read the symptoms before changing parts

The current difference is about 19-24%, based on the reported 62-63 A versus 51-52 A range. That is large enough to investigate, but current alone does not identify the restriction or mechanical fault.

Symptom Most useful interpretation
New 50 HP motor still draws 62-63 A The motor itself is unlikely to be the primary cause. Check the driven load, piping, operating point, and electrical supply.
Current falls to 30 A with the discharge line removed The connected discharge system adds substantial load. The blower is not truly unloaded because it still has magnetic, bearing, seal, windage, and gas-moving losses.
Comparable unit draws 51-52 A The comparison is valid only when speed, gas, inlet condition, discharge pressure, valves, and header conditions match.
High current with high discharge pressure Look for discharge blockage, a restricted valve, check-valve trouble, fouling, or unequal branch resistance.
High current with abnormal suction pressure Inspect the intake filter, inlet valve, silencer, ducting, and upstream blockage.
High current with noise, vibration, or temperature rise Investigate bearings, rotor contact, end-wall rubbing, deposits, and internal damage.

Understand what raises blower current

A twin lobe blower traps and transfers a volume of gas each revolution. The shaft torque rises as the pressure difference between suction and discharge rises. A discharge restriction raises discharge pressure; an inlet restriction lowers suction pressure. Either condition can increase the pressure ratio and change the required power.

Motor current is only a proxy for shaft load. Its relationship to power also depends on supply voltage, phase balance, power factor, efficiency, connection, and speed. Never treat 30 A as a direct percentage of full mechanical load, especially at light load where magnetizing current remains significant.

Parallel blowers need special attention. Two identical machines connected to a common header can operate at different points when their branch lengths, fittings, valves, check valves, or deposits produce unequal resistance. Read pressure close to each blower connection; a common-header reading can hide a restrictive individual branch.

Wear does not automatically explain high current. Excessive internal clearance can increase backflow from discharge to inlet and reduce delivered capacity. Internal rubbing, failing bearings, or deposits add friction directly and are stronger mechanical explanations for elevated current. Use flow, temperature, vibration, sound, and clearance inspection to separate leakage from friction.

Run the diagnostic checks in order

  1. Verify the electrical reading first. Record current on every available motor conductor and measure supply voltage under load. Compare the motor connection and measured current with the nameplate. A large current imbalance directs the investigation toward the supply, connections, or winding circuit; similar currents that rise together point toward shaft load.
  2. Create a valid comparison. Run the suspect and reference blowers at the same speed and with the same service gas, inlet temperature, valve lineup, and header demand. If they operate in parallel, test each machine separately when the process permits. Do not compare one blower during peak header demand with another during a lighter condition.
  3. Measure suction and discharge pressure locally. Take readings near both blower flanges. Calculate the pressure difference using the same pressure basis for both readings. Compare that result with the reference blower and the manufacturer performance curve for the actual speed and inlet condition.
  4. Inspect the inlet path. Check the intake filter, inlet valve, silencer, screens, and ducting for contamination or collapse. A failed filter can also admit debris that fouls the blower.
  5. Trace the discharge branch. Confirm that isolation valves and dampers are in their required positions. Check the nonreturn valve, silencers, flexible connections, branch piping, and common-header connection for blockage or abnormal resistance. Never run the blower against a closed discharge path.
  6. Check mechanical condition. Isolate the equipment using the site energy-control procedure. Inspect bearings, lubricant condition, coupling condition, rotor freedom, deposits, and signs of rotor or end-wall contact. Use the manufacturer procedure and clearance limits rather than judging internal clearance by feel.
  7. Compare condition indicators. Record discharge temperature, bearing temperature, vibration, noise, delivered flow, and current on both units. High temperature with poor flow strengthens the case for recirculation, excess pressure ratio, fouling, or internal damage.

Correct the measured cause

  1. If the suction measurement identifies a restriction, clean or replace the filter and remove inlet deposits. Repair damaged ducting or a valve that does not reach its commanded position.
  2. If discharge pressure is excessive, clean the restricted line and repair the obstructed valve, check valve, silencer, or branch component. For unequal parallel branches, correct the piping resistance or operating arrangement through an engineering review; do not throttle the healthy blower merely to make its current match.
  3. If inspection finds fouling, clean the blower by the approved method and identify how contamination entered. Repair the inlet filtration problem before returning the machine to service.
  4. If bearings or internal rubbing add torque, stop operation and repair the mechanical defect. Restore rotor and end clearances to the manufacturer limits and confirm free rotation before coupling the motor.
  5. If clearances indicate wear and flow is low, compare the measured performance with the blower curve. Repair or rebuild the blower when leakage prevents it from meeting duty without abnormal temperature or load.
  6. Change one condition at a time, then repeat the same current, pressure, temperature, vibration, and flow measurements. This keeps a temporary header change from looking like a successful repair.

Verify the repair under matched conditions

Return the piping and valves to their normal operating lineup. Record suction pressure, discharge pressure, current on each conductor, voltage, discharge temperature, bearing condition, vibration, speed, and delivered flow. Repeat the measurements on the reference blower at the same header demand.

  • The repaired blower should operate within its motor nameplate and blower performance limits.
  • Its current should move toward the 51-52 A reference range only when both machines operate at comparable pressure, speed, inlet condition, and flow.
  • Local pressure readings should no longer show excess resistance in the suspect branch.
  • Temperature and vibration should remain stable rather than rising during the test.
  • The overload protection must retain the setting required by the motor, protection scheme, and applicable design documents. Raising the setting to tolerate 62-63 A does not remove the load.

Avoid the fixes that waste time

  • Do not install another motor before proving an electrical defect. The first replacement left the current unchanged.
  • Do not call the 30 A reading a true no-load test. An open discharge removes piping resistance but not motor excitation or blower losses.
  • Do not clean only the discharge pipe without measuring pressure. The restriction may be at the inlet, a valve, a silencer, a check valve, or the common header.
  • Do not compare amperes without matching operating conditions. Identical model numbers do not create identical pressure drops.
  • Do not blame ordinary clearance wear for high current without checking flow and mechanical condition. Leakage and rubbing produce different diagnostic patterns.
  • Do not keep operating through rubbing noise, increasing vibration, or rising bearing temperature. Continued operation can turn a repairable clearance or bearing problem into rotor and casing damage.

FAQ

Why does one twin lobe blower draw more amps than an identical blower?

It is usually operating against a different suction-to-discharge pressure difference, suffering extra piping resistance, or carrying added mechanical friction. Compare local pressures, speed, valve positions, flow, temperature, and vibration before comparing current.

Why does blower current stay high after replacing the motor?

An unchanged 62-63 A reading after installing another 50 HP motor points back to the driven load or supply conditions. Check phase currents and voltage first, then inspect the inlet, discharge branch, bearings, fouling, and internal rubbing.

When should I stop the blower and escalate to official support?

Stop when current exceeds the applicable motor limit, protection operates, flow collapses, or rubbing, abnormal vibration, or rising temperature appears. Do not continue testing if the discharge path may be closed or the rotor may be contacting the casing. Escalate to the blower manufacturer's official support channel when measured pressure and speed cannot be reconciled with the performance curve or when internal inspection and clearance correction require product-specific limits.

Back to blog