Uploading Siemens MM440 Parameters via Drive Monitor and STARTER
Field engineers commissioning the Siemens MicroMaster 440 (MM440) drive family (catalog series 6SE6440) frequently need to lift a complete parameter set from the drive to a PC for backup, cloning, or migration to a replacement unit. This reference documents three proven upload paths: USS over RS485 using the legacy DriveMonitor tool and the 6SE6400-1PC00-0AA0 PC connection kit, PROFIBUS DP with Drive ES Basic tied to an S7-416, and the recommended modern path: STARTER with the PC Adapter USB A2 (6ES7972-0CB20-0XA0). Each path is mapped to its hardware kit, terminal assignment, parameter set, and verification procedure so the upload completes on the first attempt without dropping the bus.
1. Overview: MM440 Parameter Upload Methods
The MM440 supports three communication paths for parameter upload. Selecting the right one depends on the host controller in service and the diagnostic tools already deployed at the site.
| Method | Bus / Interface | Required Software | Hardware Kit / Adapter | Typical Use Case |
|---|---|---|---|---|
| Drive Monitor (USS) | RS485 on terminals 29 / 30 | DriveMonitor V5.4 (legacy) | 6SE6400-1PC00-0AA0 PC connection kit | Standalone commissioning, parameter dump without a PLC online |
| Drive ES (PROFIBUS) | PROFIBUS DP via the existing S7-416 bus | Drive ES Basic licensed for STEP 7 | MM440 PROFIBUS option module (6SE6400-1PB00-0AA0) | Inline parameter upload from the same DP network that runs the drive |
| STARTER (USB-MPI) | USB to MM440 USS port via MPI | STARTER V5.5 SP1 or later | 6ES7972-0CB20-0XA0 PC Adapter USB A2 | Modern commissioning, parameter archive for TIA Portal handover |
*.dps archive into the project tree.2. Prerequisites and Hardware Identification
Before connecting any adapter to the drive, verify the following items are in place.
-
Drive: MicroMaster 440 (any firmware; the V1.x through V3.x parameter layouts differ from each other). Read the firmware version from the drive nameplate, e.g.
FW V2.1, and record the rated power, voltage, and order number (6SE6440-2Uxxx-xxxx). - Drive documentation: MM440 Operating Instructions (6SE6400-5AW00-0AP0) and MM440 Parameter List (6SE6400-5BP00-0AP0) for the parameter reference.
- PC: RS-232 (DB9) or USB port. For modern laptops without RS-232, use the USB-to-serial adapter bundled in the PC connection kit.
-
Drive address: The MM440 USS address (parameter P2011[0] for COM link 1) must be known. Factory default is
0. If the drive has been commissioned, read the address from the BOP (Basic Operator Panel) before connecting. - Power state: The control electronics of the MM440 are powered from the main DC bus. The drive does not need to be enabled (RUN), but main power must be present, or the drive must be powered from a 24 V auxiliary supply on terminals 31 / 32.
3. Method 1 — USS on RS485 with Drive Monitor and Kit 6SE6400-1PC00-0AA0
This is the most direct method when the drive is on a bench, in a panel, or in a cabinet and the PROFIBUS network is not available.
3.1 Kit contents (6SE6400-1PC00-0AA0)
The MM4 PC connection kit bundles everything required to bring a MicroMaster 4 drive online to a PC running DriveMonitor or STARTER.
- Isolated RS-232 ↔ RS-485 converter with screw terminals on the drive side and a DB9 on the PC side
- 9-pin SUB-D serial cable (PC to converter)
- DriveMonitor V5.4 DVD with the original Siemens PC-Parameter-Loader driver
- Quick-start guide with the terminal diagram and protocol settings
If the kit is no longer available, an equivalent isolated RS-232 ↔ RS-485 converter (e.g. Phoenix Contact PSM-ME-RS232/RS485-P) can be substituted, but the pinout on the drive side must be observed. A non-isolated converter is not acceptable when the PC and the drive cabinet are referenced to different grounds.
3.2 Terminal 29 / 30 wiring
The MM440's COM link is the two-wire RS-485 interface exposed on the upper row of control terminals.
| Terminal | Signal | Function | Wire Color (kit convention) |
|---|---|---|---|
| 29 | P+ | RS-485 non-inverting (A) data line | Red |
| 30 | N- | RS-485 inverting (B) data line | Black |
Connect the two conductors from the converter's screw terminals to 29 and 30, observing polarity. A common-mode ground is not required when the converter is isolated; if it is non-isolated, terminate the cable shield at one end only.
3.3 Drive Monitor V5.4 setup sequence
- Insert the DriveMonitor V5.4 DVD (or run the installer from the kit). Accept the default installation path
C:\DriveMon. - Start DriveMonitor.
- Open Online → Set Online Connection → USS Online Connection.
- Configure the COM port settings to match the drive's P2010 value:
- Port: COM1 (or whichever the USB-serial adapter is mapped to; verify in Windows Device Manager → Ports (COM & LPT))
- Baud: 9600 (default for an out-of-box MM440)
- Data bits: 8
- Parity: Even
- Stop bits: 1
- Handshake: None
- Set the drive address (P2011[0]). Default is 0.
- Click Test. The status line should read "Drive responding on USS address 0". If not, the issue is at the bus or protocol level; refer to Section 11 (Troubleshooting Matrix).
- Click Online. DriveMonitor reads the parameter set from the drive (approximately 6–12 s for a default parameter set, longer if the full index is selected).
- Choose File → Upload Parameter Set from Drive. Save the resulting
*.dnlfile to a known path. The same file format is readable by STARTER via File → Open with the legacy import option.
3.4 Why cycling the baud rate alone will not fix a no-online condition
Baud rate mismatches are only one of five possible failure modes in a DriveMonitor USS bring-up. The full set is:
- Drive address (P2011[0]) ≠ address configured in DriveMonitor
- Baud rate (P2010) ≠ baud rate configured in DriveMonitor
- RS-485 A/B polarity swapped (29 to B, 30 to A)
- Isolation / ground loop: a non-isolated converter connected between a grounded PC and a drive with PE on the bus shield can saturate the bus driver
- P2014 (telegram off time) shorter than the PC's response latency — the drive drops the link before the parameter request completes
Therefore, simply cycling the baud selector is unlikely to bring the link up if any of the first, third, fourth, or fifth items is wrong.
4. Method 2 — PROFIBUS DP with Drive ES and an S7-416
When the MM440 is wired to a SIMATIC S7-416 via PROFIBUS DP, parameter upload is handled inside the SIMATIC environment with Drive ES Basic (the predecessor of the SIMATIC Drive ES package integrated with STARTER). In this configuration the PC connection kit is not required; the PG/PC is already on the same DP network.
4.1 Hardware requirement
Base MM440 units do not have a native PROFIBUS port. The PROFIBUS module slots into the top of the drive and corresponds to GSD file SIEM811F.GSD (MicroMaster 4 DP V1.0). Order number for the basic PROFIBUS option is 6SE6400-1PB00-0AA0.
4.2 STEP 7 configuration sequence
- Open the STEP 7 project containing the S7-416 hardware configuration.
- Open HW Config and add the MM440 from the catalog (path: PROFIBUS DP → Drives → Siemens AG → SIMOVERT / MICROMASTER 4).
- Set the PROFIBUS address to match the rotary switch on the PROFIBUS module (default is 3).
- Insert a DP slave slot for the drive and select a PPO type. For Drive ES parameter access, use PPO 1 (4 PKW + 2 PZD) — the PKW channel is what exposes the parameter list to the engineering tool.
- Open Drive ES Basic from SIMATIC Manager → Options → Drive ES or via the context menu on the drive icon in HW Config.
- When the Drive ES commissioning window opens, click Online → Connect to Drive.
- Choose Drive → Upload to PG. Drive ES reads the parameter set and stores it as a
*.dpsfile tied to the STEP 7 project.
5. Method 3 — STARTER with PC Adapter USB A2 (Recommended Modern Path)
For new projects, especially those that will be migrated to TIA Portal, the cleanest workflow is STARTER with the PC Adapter USB A2 (6ES7972-0CB20-0XA0).
5.1 Why STARTER is preferred over Drive Monitor
- Native support for current MM4 firmware versions and parameter sets
- Integrated trace, control panel, and expert list
- Same
*.dpsarchive is importable into TIA Portal via the "Migrate device" function - Runs on Windows 10 / Windows 11 64-bit
- USB connectivity avoids a serial-port dependency
5.2 Hardware and software
- STARTER V5.5 SP1 or later (DVD, part of Drive ES Basic V5.5 or available standalone) — see STARTER Getting Started.
- PC Adapter USB A2 (6ES7972-0CB20-0XA0) — a USB-to-MPI/PROFIBUS adapter that exposes the MM440's RS-485 as an MPI bus master to STARTER.
- PROFIBUS connector on the drive side if the drive is on a DP network; for a direct PC-to-drive connection, wire the adapter's MPI cable to MM440 terminals 29 and 30.
5.3 Procedure
- Install STARTER and the PC Adapter USB driver. The driver is included in the package; the cable's USB side presents as a virtual COM port to STARTER.
- Launch STARTER. From the project tree, click Insert Single Drive Unit → MICROMASTER 440. Select the firmware version observed on the drive nameplate.
- Select PG/PC Interface from the Options menu and choose PC Adapter (MPI) with the COM port assigned to the USB cable.
- Click Connect to target system. STARTER will scan the bus; the MM440 appears with its current bus address (default 0).
- Right-click the drive → Load to PG/PC → Load hardware configuration to PG. This is the equivalent of Drive Monitor's upload but stores the result in the STARTER project.
- For an offline archive, choose Project → Archive and save the
*.ziparchive. The archive can be unzipped and the*.dpsfile extracted for handoff.
6. Communication Parameters on the MM440
Before any of the three methods is used, the following drive parameters must be in a known state. The values below are the factory defaults. If the drive has been previously commissioned, check the actual values from the BOP (Basic Operator Panel) or via Drive Monitor's online list.
| Parameter | Description | Factory Default | Setting Required for Upload |
|---|---|---|---|
| P0700[0..3] | Command source selection (0 = BOP, 1 = Terminals, 2 = USS on COM link, 5 = COMM MODULE on CB) | 1 | Leave at 1; parameter upload works regardless |
| P1000[0..3] | Setpoint source selection (similar indices to P0700) | 2 | Leave at 2; parameter upload works regardless |
| P2010[0..1] | USS / MODBUS baud rate (0 = 4800, 1 = 9600, 2 = 19 200, 3 = 38 400, 4 = 57 600, 5 = 115 200) | 6 (= 9600) | Match this to the PC's COM port setting in DriveMonitor or STARTER |
| P2011[0..1] | USS address (0..30) | 0 | Set to the address selected in the PC tool |
| P2012[0..1] | USS PZD length (0 = 2 words, 1 = 4 words, 2 = 6 words, 3 = 8 words) | 2 | Leave at 2 for parameter upload |
| P2013[0..1] | USS PKW length (0 = 3 words, 1 = 4 words, 3 = variable) | 1 | Leave at 1 (4 words, the maximum supported) |
| P2014[0..1] | USS telegram off time in ms (0 = no monitoring) | 2000 | Increase to 5000 if the PC is slow to respond |
7. USS Protocol Frame Reference
The MM440's COM link implements the Siemens USS (Universal Serial Interface) protocol. Each request from the master is a 14-byte frame; each response from the drive is either 14 bytes (read/write of a single parameter) or 30 bytes (array read). The frame structure is fixed across the MM4 family.
| Byte | Field | Value / Description |
|---|---|---|
| 0 | STX | 0x02 (start of text) |
| 1 | LGE | 0x0E (frame length, 14 bytes total) |
| 2 | ADR | Bit 5 = mirror; bits 0..4 = address; bit 7 = 0 (broadcast); bit 6 = 0 (point-to-point). Default 0x00. |
| 3..4 | PKE | Parameter signature (AK = bits 12..15, PNU = bits 0..11) |
| 5..8 | IND | Index (sub-parameter number, e.g. 0 for P0700[0]) |
| 9..12 | PWE | Parameter value (16-bit for U16, 32-bit for U32, IEEE 754 for float) |
| 13 | BCC | XOR checksum over bytes 1..12 |
DriveMonitor and STARTER encapsulate this protocol transparently; the engineer only sees the parameter list. However, when troubleshooting a custom tool, the BCC field is the most common source of errors — a single XOR mismatch causes the drive to silently drop the request with no error reply.
8. Wiring Reference: RS-485 Bus Topology
Figure 1 — RS-485 connection from a PC running Drive Monitor or STARTER to MM440 terminals 29 and 30 via the isolated converter supplied in kit 6SE6400-1PC00-0AA0.
9. Step-by-Step Upload Procedure (Recommended Path)
This consolidated procedure uses STARTER with the PC Adapter USB A2 and is the path recommended for any new field deployment.
- Identify the drive: read the order number and firmware from the MM440 nameplate. Verify that STARTER V5.5 SP1 or later is installed on the PG/PC.
- Connect the adapter: plug the PC Adapter USB A2 into the laptop's USB port. Connect the adapter's MPI cable to MM440 terminals 29 and 30, observing A/B polarity.
-
Power the drive: apply main power or auxiliary 24 V. The BOP should boot and display the drive state (e.g.
ready). -
Read address and baud: from the BOP, navigate to
P2011[0]andP2010and note the values. - Open STARTER: insert a new MM440 device in the project tree, matching the firmware version.
- Configure the PG/PC interface: Options → Set PG/PC interface → PC Adapter (MPI) → Properties. Set the COM port to match the USB adapter, set baud to 187.5 kbps (default for PC Adapter MPI), and bus profile to MPI.
- Connect online: click the Connect to target system button. The bus scan resolves the MM440 in 1–3 seconds.
- Upload to PG: right-click the MM440 in the project tree and select Load to PG/PC → Load hardware configuration to PG. STARTER reads all visible parameters and stores them in the project.
- Verify the upload: open the expert list and confirm that P0304 (motor voltage), P0305 (motor current), and P3900 (commissioning status) match the source drive. If any parameter shows a "??" or default value, the upload was truncated — re-try with P2014 raised to 8000 ms.
-
Archive the project: Project → Archive → Save as ZIP. Store the
*.zipin the engineering repository.
10. Verification Checklist
After the upload completes, perform the following checks before considering the operation successful.
- Checksum: in DriveMonitor, the upload dialog shows a checksum at the end of the upload; confirm it matches the source drive if a master file is available.
- Parameter count: a factory-default MM440 has approximately 1100 parameters. If DriveMonitor returns fewer than 700, the upload was truncated; re-try with a longer telegram off time.
- Online re-read: after saving, go offline, then go online again and read back a handful of representative parameters (e.g. P0304, P0305, P0307, P3900, P1082) to confirm the file matches the live drive.
-
File integrity: the saved
*.dnlfile should be > 50 KB for a full parameter set. Files under 10 KB usually indicate only the index was uploaded. - Restoration test: to prove the file is complete, download the saved set to a known-good MM440 of the same firmware, then go online and read back the parameters. They should match the original drive.
- Fault buffer: read r0947 (fault code) and r0949 (fault value). A value of 0 in both confirms no faults were triggered by the upload itself.
11. Troubleshooting Matrix
| Symptom | Most Likely Cause | Remedy |
|---|---|---|
| DriveMonitor "Test connection" returns timeout | A/B polarity swapped at terminals 29/30 | Swap the two wires. Most isolated converters label A = P+ (29) and B = N- (30) |
| Timeout at 9600 baud, succeeds at 4800 | Cable run too long, or stub too long | Keep the bus stub from the converter to the drive under 1 m; use twisted pair |
| Connects intermittently, drops after 2 s | P2014 (telegram off time) too short | Increase P2014 to 5000–8000 ms |
| "Address conflict" reported | Two drives on the bus at the same P2011 value | Disconnect the second drive, or change its address |
| Driver reports "COM port in use" | Another terminal session has the port open, or wrong COM number | Close all terminal apps; verify the COM number in Device Manager |
| Online OK, upload empty / 0 bytes | PKW length mismatch (P2013 = 0 on a drive set to 3 words) | Set P2013 = 1 (4 words) |
| DriveMonitor crashes on Windows 10 | 32-bit app running on a 64-bit OS without admin rights | Install in a path without spaces; run as administrator; consider STARTER instead |
| Uploads correctly but does not open in STARTER | Drive Monitor's *.dnl is a legacy format |
Use STARTER's online upload (Method 3) or convert with Drive ES |
| Uploads but parameters do not match — e.g. P1080 reads 0 in the file, P1082 reads 50 Hz | Drive has been reset to factory default since the file was saved | Re-upload from the source drive and check r0030 / r0201 for uptime |
| STARTER bus scan finds no MM440 | PC Adapter USB A2 MPI baud rate mismatch (default 187.5 kbps, drive's USS port is 9.6 kbps) | Set PC Adapter to "Auto" and let it negotiate; or lower the adapter baud to 19.2 kbps |
| Upload completes but file is locked read-only | DriveMonitor was installed under Program Files on a locked-down OS | Re-install to C:\DriveMon or a non-system path |
12. File Format Migration: .dnl to .dps
DriveMonitor's *.dnl file is a legacy binary format used by Drive ES Classic. STARTER's *.dps is a structured XML archive inside a ZIP container. The migration path depends on the engineering environment.
-
DriveMonitor → STEP 7 with Drive ES Basic: open the
*.dnldirectly in Drive ES via File → Open; Drive ES converts on load and saves as*.dps. -
DriveMonitor → STARTER (no Drive ES): launch STARTER offline, insert a new MM440 of matching firmware, go online, and load from the drive. The
*.dnlcannot be imported directly; the upload must be repeated. -
STARTER → TIA Portal: open the TIA Portal project, add a new SINAMICS G120 or MICROMASTER 4 device in the device tree, and use Device → Migrate device → Import STARTER archive. The
*.zipfrom STARTER is consumed directly.
*.dnl taken from a V1.1 MM440 will not load cleanly onto a V3.0 unit — the parameter indices for several safety and motor-data parameters differ between firmware generations. Always record the source firmware on the parameter file's metadata.13. Safety and Field Practices
- Parameter upload is a read-only operation with respect to the drive's controlling program, but it can briefly hold the bus. Do not perform an upload while a critical process is running through the drive; schedule it for a maintenance window.
- The MM440's COM link uses a single twisted pair. Do not run it in the same conduit as motor power cables; keep at least 200 mm of separation, or use a shielded cable grounded at the drive end only.
- When uploading to a drive that has been replaced under a warranty exchange, confirm the firmware version before writing parameters back. Siemens hardware exchange units sometimes ship with newer firmware than the original, and a parameter download with the wrong firmware metadata can brick the unit's startup sequence.
- If the drive is part of a safety chain (SIL-rated), the upload does not affect safety parameters stored in any safety module, but the resulting file is not a safety record and must not be used as evidence for safety acceptance tests.
- Document the parameter file's source: drive order number, serial number, firmware version, and date. The file name
MM440_6SE6440-2UD21-1BA1_FWV2.1_2024-09-18.dnlis a recommended convention.
FAQ
Why does Drive Monitor show "no response" even though the wiring is correct?
Beyond baud rate, the most common cause is a polarity swap between the converter's A/B outputs and MM440 terminals 29 (P+) and 30 (N-). With the isolated converter from kit 6SE6400-1PC00-0AA0, A must land on 29 and B on 30; swap them and re-test. A second common cause is P2014 (telegram off time) shorter than the PC's response latency — raise it to 5000 ms.
What is the difference between Drive Monitor and STARTER for MM440 parameter upload?
Both can read and write MM440 parameters, but Drive Monitor is a legacy 32-bit tool that ships with the 6SE6400-1PC00-0AA0 PC connection kit and uses its own *.dnl file format. STARTER is the current commissioning tool, runs on 64-bit Windows, uses the *.dps archive format, and is importable into TIA Portal. Use STARTER for any new project; use Drive Monitor only when reproducing a legacy installation.
Can I upload parameters from the MM440 over the existing PROFIBUS to the S7-416 without a PC kit?
Yes. With the optional PROFIBUS module (6SE6400-1PB00-0AA0) installed on the MM440 and a licensed Drive ES Basic add-on, STEP 7 exposes the drive as a DP slave with PPO 1. Open Drive ES from the drive icon in HW Config, connect, and select Drive → Upload to PG. The PG must be online with the S7-416 CPU.
What is the default USS baud rate and address on a factory-fresh MM440?
P2010 = 6 (9600 baud) and P2011[0] = 0 (address 0). If the drive has been commissioned previously, both must be read from the BOP (Basic Operator Panel) or from Drive Monitor's online list before attempting the upload — otherwise the PC will time out looking for a drive that is configured differently.
How long does a full MM440 parameter upload take via Drive Monitor?
For a factory-default parameter set (about 1100 parameters) at 9600 baud, expect 6–12 seconds. A heavily modified drive with a populated expert list can take 25–40 seconds. If the upload is interrupted or the file is smaller than 50 KB, the telegram off time (P2014) is almost certainly too short for the PC's processing latency.
Does the upload affect the drive's runtime behavior, or is it strictly read-only?
The upload itself is read-only — it does not write any parameter. However, holding the bus for 30+ seconds can delay any open-loop USS control requests from the S7-416 during the upload window. If the S7-416 uses PPO 1 with a 50 ms cycle, expect two or three dropped telegram cycles during the upload, which most applications tolerate via P2014 on the S7-416 side.