Symptom and Working Answer
A Perspective Table keeps rendering numbers as 1,234,567.89 when the target is 1.234.567,89. Setting the session locale to es-ES leaves the comma grouping unchanged, and changing the locale from a script has no visible effect.
The workaround that holds has two parts:
- Set the session locale to
it-IT. Italian uses the same convention as Spanish: period for thousands and comma for decimals. In field use,it-ITis the locale that switches Perspective number formatting reliably. - Place a Numeric Entry Field in the same view and hide it. Its presence triggers the locale number format for every number displayed on the page, including numbers in Table cells that otherwise stay in the default format.
This is a known defect. Inductive Automation tracks it internally as IGN-7305, open since 2023. A related defect covers the Numeric Entry Field decimal separator for Swedish, Spanish and Catalan (BUG-3267, IGN-11874). Treat the workaround as permanent until the release notes for your Ignition version list one of these tickets as fixed.
Locale Resolution in Perspective Number Rendering
In this article, locale means the session-level locale property, session.props.locale. The term format string means the pattern in a Table column's numberFormat property, such as 0,0.00.
Perspective uses numeral-style format strings. In that syntax, , and . are pattern tokens. The comma means "group thousands" and the period means "decimal point here." They are not the characters printed on screen. At render time, the client-side formatter replaces those tokens with the delimiters defined for the active locale.
That replacement works only when the formatter has the locale's delimiter data loaded and selected. If it does not, it falls back silently to the default English delimiters. No error is raised. This explains both symptoms:
- The locale property holds the correct value, but the Table output does not change. The property and the formatter's active locale are out of sync.
- Adding a Numeric Entry Field fixes the whole page. That component's initialization causes the formatter to apply the session locale, and every number rendered afterwards picks up the new delimiters.
One wrong practice follows from this. Do not rewrite the format string as 0.0,00 to force period grouping. That swaps the meaning of the tokens and produces misplaced decimals. It breaks as soon as the locale switch starts working.
Diagnostic Decision Path
- Check 1: identify the rendering layer. Confirm the number sits in a Perspective component, here a Table inside a Perspective view. It must not be in a Vision component, a Report, or a Gateway page, because each of those formats numbers through a different path. If it is Perspective, go to Check 2. If it is not, this defect and workaround do not apply.
-
Check 2: read the column configuration. Open
props.columnsand find the entry for the numeric field. Expectrenderset tonumber(orautowith numeric data) and anumberFormatthat uses standard tokens, such as0,0.00.- If the column renders as
string, or the data arrives already formatted as text, locale settings cannot affect it. Fix the data type first. - If the column is numeric, go to Check 3.
- If the column renders as
-
Check 3: read the live session locale. In the running session, read
session.props.locale. You can bind a Label to it for a quick readout.- If it does not show the locale you set, the write is not reaching the session. Set it in the session props, or write it from a session-scoped event.
- If it shows the locale but the Table still groups with commas, you are looking at the formatter defect. Go to Check 4.
-
Check 4: substitute
it-IT. Change the session locale fromes-ES(orsv-SE,ca-ES) toit-IT.- If the Table switches to period grouping, apply the procedure below and stop.
- If some or all numbers still show commas, go to Check 5.
-
Check 5: add the Numeric Entry Field trigger. Drop a Numeric Entry Field into the same view and reload the session.
- If every number now renders
1.234.567,89, keep the field and hide it. - If numbers still render wrong, move to the string-formatting fallback in the pitfalls section.
- If every number now renders
Workaround Procedure: it-IT Locale and Hidden Numeric Entry Field
- Open the session properties in the Designer and set
localetoit-IT. If the locale is chosen per user at login, writeit-ITtosession.props.localein the session startup logic instead. - Leave the Table column
numberFormatin standard token form, for example0,0.00for two decimals or0,0for integers. - Add a Numeric Entry Field to the view that contains the Table. It does not need a binding or a meaningful value.
- Hide the field by setting its display position property to false inside a flex container.
- Keep the component mounted. The trigger depends on the component existing on the page.
- Other ways of hiding it may prevent it from rendering at all. If you hide it another way, repeat Check 5.
- Repeat steps 3-4 in every view that displays formatted numbers and can be the only view on screen. A popup or docked view shown on its own does not inherit the trigger from a view that is not loaded. Putting the field in a docked view that is always open is a workable alternative.
- Add a note in the view documentation that references
IGN-7305, so the field is removed deliberately once the defect is fixed, not by someone cleaning up an "unused" component.
Pitfalls and Fallback
| Pitfall | Effect | Correction |
|---|---|---|
Swapping tokens in numberFormat (0.0,00) |
Wrong decimal placement; breaks once the locale switch works | Keep 0,0.00 and let the locale supply the delimiters |
it-IT affects more than numbers |
Dates and month names render in Italian; translation lookups resolve against the Italian locale | Check date columns, date pickers and translated text after the switch; pin explicit date format strings where needed |
| Hidden trigger field removed during cleanup | Formatting silently reverts to comma grouping | Name the component clearly, for example LocaleFormatTrigger, and document it |
| Grouping differences between locales | Spanish conventions do not group four-digit values; Italian ones do, so 1234 shows as 1.234 under it-IT
|
Confirm the operators accept four-digit grouping |
| Pre-formatting values as strings | Correct appearance, but the column sorts alphabetically, not numerically | Use this only as a last resort, and only on columns that do not need sorting or filtering |
The last-resort fallback bypasses the client formatter. Build the display string in a script transform on the Table data binding, with the period and comma inserted explicitly, and set that column's render to string. Keep the raw numeric value in a hidden column if downstream logic needs it.
Verification Checks
-
Check 1: bind a Label to
session.props.localein the running browser session. Expectit-IT. -
Check 2: put a test row with the value
1234567.891in a column withnumberFormat0,0.00. Expect1.234.567,89. -
Check 3: temporarily delete the hidden Numeric Entry Field and reload. Expect the value to revert to
1,234,567.89, which confirms the view depends on the trigger. Restore the field and confirm Check 2 passes again. -
Check 4: click the numeric column header to sort. Expect numeric order, for example
9,50before100,00. Alphabetical order means a column was converted to a string. -
Check 5: close the browser tab, open a fresh session, and navigate directly to the view without passing through any other page. Expect
1.234.567,89on first render.
FAQ
Can I use es-ES in Ignition Perspective to get a period thousands separator?
Setting the session locale to es-ES has been observed to leave Table numbers comma-grouped. Use it-IT, which applies the same period-thousands and comma-decimal convention, together with a hidden Numeric Entry Field in the view.
Does the Numeric Entry Field workaround need the field to be visible?
No. Hide it by setting its display position property to false in a flex container. It must stay mounted in the same view as the Table, because the trigger depends on the component being present on the page.
Can I change the Perspective locale from a script to fix the separator?
A script can write session.props.locale, but a correct value there does not force the Table formatter to switch delimiters. Pair the it-IT locale with the hidden Numeric Entry Field; the script alone does not change the rendered separator.
Does a newer Ignition version fix the Perspective Table number locale bug?
The Table behavior is tracked as IGN-7305, open since 2023. The related Numeric Entry Field decimal-separator issue is tracked as BUG-3267 / IGN-11874. Check your version's release notes for those identifiers before removing the hidden field.