Use the Renishaw application to run the pairing sequence for the RMP60 and RMI-Q, then verify the Mazak tool definition separately. In this installation, the application-guided process completed pairing in about three minutes. Mazak error 230, shown as “bad MMS signal,” can remain when the machine does not receive the expected probe state or when the control's spindle-tool state does not match the physical setup.
Symptom interpretation
Separate radio pairing, receiver status, tool management, and metrology setup. Treating them as one operation makes error 230 difficult to isolate.
| Observed symptom | Engineering meaning | Next check |
|---|---|---|
| The probe LEDs flash after battery insertion and then turn off | The probe has executed a battery-startup indication. This alone does not prove that the receiver has registered it. | Read the receiver indicators while invoking the probe. |
RMI-Q position P1 remains yellow |
The receiver is reporting a stored-slot or operating state that must be decoded using the indicator table for the installed interface. | Run the application-guided pairing sequence and compare all receiver LEDs afterward. |
| The receiver error LED remains red | The interface is not presenting the valid condition expected by the machine input. | Check pairing, probe wake-up, batteries, and the machine-interface signal. |
| The probe-status LED remains red | The status supplied by the interface is not changing to the machine-ready state. | Activate the probe and observe whether this LED changes. |
Error 230 appears when the probe tool is called |
The control's probe/tool sequence has detected a wrong MMS signal. | Confirm both the radio state and the actual tool recorded in the spindle. |
Probe-to-control signal mechanism
The term “pairing” here means registering the radio probe with a receiver position such as P1. Pairing establishes the radio association; it does not define the probe as a Mazak tool, put the correct tool number in the spindle record, center the stylus, or calibrate measurement offsets.
The complete signal path is the RMP60, the RMI-Q, the receiver's machine-interface outputs, and the Mazak Smooth control logic. A failure at any boundary can produce a probe-related machine alarm. Receiver LEDs therefore provide the dividing point: if the receiver does not recognize the probe correctly, work on batteries, activation, and pairing. If its state changes correctly but the control still reports error 230, inspect the machine-interface signal and tool-management state.
The short LED sequence after inserting batteries is a local probe indication. It must not be used as the sole pairing test. Likewise, entering a probe description in the Mazak tool table does not create the radio association.
Application-guided pairing procedure
- Identify the hardware as a Renishaw
RMP60probe andRMI-Qreceiver. Confirm that the application instructions selected apply to this product pair. - Install serviceable batteries with the correct polarity. Watch the startup LED sequence, but do not interpret the LEDs turning off as proof of a fault.
- Open the Renishaw application and select its probe setup or pairing guidance. Follow the displayed order and timing for battery insertion, stylus deflection, receiver discovery, and confirmation. Those timing prompts replace improvised power-cycle sequences.
- Observe the
RMI-Qduring the procedure. Pairing is complete only when the application finishes successfully and the receiver no longer shows the previous persistent error combination during probe activation. - Cycle the probe through the activation method configured for the machine and confirm that the receiver follows the change. If the receiver remains unchanged, repeat the application sequence after checking the batteries and selected receiver position.
The application resolved this installation quickly after manual attempts failed. That result points to pairing timing or mode selection rather than the stylus, holder, or Mazak tool description as the initial communication fault.
Mazak tool integration and calibration
After radio communication works, configure the control-side tool record. The physical probe and the spindle record must describe the same tool during the call sequence.
- Mount the probe body in its holder and fit the stylus.
- Define the applicable tool record as a probe in the Mazak control.
- Call the probe through the normal magazine sequence and confirm that it is physically loaded into the spindle before beginning a measurement cycle.
- Compare the tool number recorded as being in the spindle with the actual probe tool number. Correct any mismatch through the documented Mazak tool-management function.
- Mechanically center the probe in the holder. Pairing cannot correct stylus runout.
- Run the applicable Mazatrol probe calibration program. Calibration establishes the measurement relationship needed after installation; merely screwing in the stylus does not produce a calibrated probe.
Some procedures used on other Mazak control generations temporarily assign T0, reset error 230, and then restore the correct tool number. That sequence was reported for Fusion and Matrix controls, not Smooth. Do not transfer it to Mazak Smooth without the machine documentation or Mazak service direction.
Numbered verification checks
- Check 1: Probe startup. Remove and reinstall the batteries as directed by the application. Expect the probe LEDs to execute their startup sequence.
-
Check 2: Receiver response. Activate the probe while watching the
RMI-Q. Expect its probe-related indication to change rather than remain fixed in the prior red-error state. - Check 3: Pairing persistence. Restart the normal machine operating sequence and activate the probe again. Expect the registered receiver position to recognize the same probe without repeating pairing.
- Check 4: Tool-state agreement. Call the probe from the magazine and inspect the spindle tool record. Expect the recorded tool number to match the probe physically in the spindle.
-
Check 5: Alarm clearance. Invoke the configured probe tool under normal operating conditions. Expect error
230to remain cleared. - Check 6: Measurement verification. Run the Mazatrol calibration routine and then measure a known reference. Expect a repeatable result within the limits assigned to the machine, probe, stylus, and calibration setup.
Recurring configuration pitfalls
| Wrong practice | Why it fails | Correct practice |
|---|---|---|
| Using the battery LED flash as a connection test | It proves local startup, not receiver registration. | Verify a corresponding RMI-Q state change. |
| Describing the tool as a probe before completing pairing | The Mazak tool type does not configure the radio link. | Pair first, then validate control integration. |
| Repeatedly removing batteries and power-cycling the machine without controlled timing | Pairing depends on entering the required setup states in the correct order. | Follow the Renishaw application prompts. |
Copying reset or T0 sequences from another control generation |
Tool-management behavior can differ between Mazak control families. | Use the Smooth procedure documented for the machine. |
| Skipping centering and calibration after communication succeeds | A connected probe can still report inaccurate positions. | Center the stylus and run the Mazatrol calibration program. |
Frequently asked questions
Why does my RMP60 flash after battery insertion and then turn off?
The flash is the probe's battery-startup indication; it is not a completed-pairing confirmation. Activate the probe while watching the RMI-Q for a corresponding state change.
Why does Mazak Smooth show error 230 with an RMP60?
Error 230 reports a bad MMS signal during the probe-tool sequence. Check the RMI-Q status first, then confirm that the spindle tool record matches the probe physically loaded.
Why are the RMI-Q error and probe-status LEDs red?
The receiver is not presenting the operating state expected by the machine. Recheck probe activation and application-guided pairing; if the receiver responds correctly but the alarm remains, inspect the machine-interface and tool-state path.
Why does pairing not calibrate the RMP60?
Pairing registers the radio probe with the receiver. Centering and the applicable Mazatrol calibration program are separate operations required for accurate measurement.
How do I verify the RMP60 repair is complete?
Call the probe normally, expect the RMI-Q to follow probe activation and error 230 to stay cleared, then measure a known reference and expect repeatable results within the assigned machine and probe limits.