Why Does the ABB YuMi Left Gripper Command the Right?

Erik Lindqvist6 min read
ABBRoboticsTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

The engineer sees signal B trigger one physical gripper, but the right-hand gripper moves when only the left-hand gripper was requested. One requested actuator and one incorrect response identify a command-routing problem before they identify a servo-load problem. Motor current creates the motion, but endpoint selection decides which motor receives that current. The number that matters is the count of physical grippers responding to the command: exactly one, with its identity matching the software reference.

Available correction approaches

There are three practical places to correct a left/right mismatch: the gripper network identities, the software mapping between logical names and physical endpoints, or the task structure that issues the command. Changing gripper IP addresses could change endpoint identity, but that option is excluded because the completed application already depends on the existing addresses.

Approach What it changes Decision criterion Recommendation
Change gripper IP addresses Physical network identity Acceptable only if every dependent reference can be retested Exclude under the stated constraint
Correct the left/right software binding Association between the command and gripper endpoint Use when the wrong physical gripper consistently receives the command Preferred correction
Move the command out of TASK_BG Which task owns gripper motion Use when device access is task-dependent or commands can overlap Preferred architecture if binding is correct

First prove the binding. If TASK_BG resolves the left-hand command to the right-hand endpoint, correct that task's device association without changing either IP address. If the binding is correct but another task can write to the same gripper interface, make one task the sole command owner and pass requests to it through internal state.

Command path and failure mechanism

A gripper instruction passes through several layers: the Boolean request, the task evaluating it, the logical gripper reference used by that task, the configured endpoint behind the reference, and the physical servo gripper. A correct signal B transition proves only that the first condition was satisfied. It does not prove that the instruction selected the left-hand endpoint.

Because the right-hand gripper moves, a valid command is reaching a valid device. That observation moves power loss, total communications failure, and a non-running background task down the diagnostic list. The highest-value checks are the logical-to-physical mapping and command ownership across tasks.

The foreground state matters as well. The left arm is waiting for signal A while TASK_BG reacts to signal B. Waiting does not automatically grant another task exclusive ownership of the left gripper. If both tasks can issue gripper commands, execution order can replace, redirect, or mask the intended action. This is timing and ownership, not a reason to change motor settings.

Quantities and diagnostic observations

Quantity or state Expected result Fault indication Where to read it
signal B One clean activation for the intended request Unexpected transitions or a continuously active request Controller signal monitor or task trace
Command execution in TASK_BG One left-gripper request per intended event Repeated execution while the condition remains true Program monitor, breakpoint, or temporary diagnostic state
Logical gripper selection Reference resolves to the physical left gripper Reference resolves to the right gripper Device configuration and task-visible data
Physical response count Exactly one gripper moves Zero, two, or the wrong one moves Controlled observation
Competing command No other task writes during the test Another task issues an open or close request in the same interval Cross-reference and execution trace

Run the observations with robot motion inhibited or otherwise placed in a controlled test state appropriate to the installation. A servo gripper can move immediately when its endpoint receives a valid instruction. Keep hands and tooling outside the gripper travel and pinch region.

Isolation procedure

  1. Record the current IP-to-physical-gripper association without editing it. Identify which configured endpoint belongs to the left gripper and which belongs to the right gripper.
  2. Cross-reference every gripper command in all tasks. Include open, close, initialization, recovery, and any shared routine that can select a gripper indirectly.
  3. Monitor signal B and prove that TASK_BG enters the intended branch. Add a temporary diagnostic state immediately before the gripper request if the controller monitor cannot show the branch clearly.
  4. Disable execution of other gripper commands for a controlled test while leaving the network configuration unchanged. Trigger signal B once and observe which physical unit responds.
  5. Inspect the left-hand gripper reference visible to TASK_BG. Follow that reference through its configuration to the endpoint recorded in step 1. A name containing “left” is not proof of the endpoint behind it.
  6. Issue separate controlled requests through the left and right logical references. Record a two-row result matrix: requested reference versus responding physical gripper.
  7. If the matrix is reversed, correct the software association or the arguments passed into the shared gripper routine. Retain the existing IP addresses.
  8. If each isolated reference operates the correct gripper, restore one competing command path at a time. The first restored path that recreates the fault identifies the ownership or sequencing conflict.

Recommended task architecture

Assign gripper actuation to one command-owning task when multiple tasks can request movement. The foreground sequence and TASK_BG may both detect conditions, but they should publish requests rather than independently drive the same gripper interface. The owner validates the requested side, issues one command, records completion or failure, and then accepts the next request.

For this sequence, TASK_BG can convert signal B into a left-open request. The command owner then applies that request to the verified left-hand binding. Use an edge or a request/acknowledge handshake when signal B can remain active; otherwise the background scan may issue the open command repeatedly. Reset or acknowledge the request only after the owner has accepted it, not merely because one scan elapsed.

Keep the side selection explicit at the command boundary. Avoid separate task-local objects with identical-looking names unless their endpoint assignments are deliberately identical. A shared routine also needs an explicit side or device argument; relying on task context makes a mapping error harder to see.

Verification and recurring pitfalls

  1. Start with both grippers in a known, safe state and confirm their physical identities against the unchanged IP mapping.
  2. Trigger signal B once while the left arm is waiting for signal A. Confirm that only the left-hand gripper opens.
  3. Hold signal B active long enough to cover multiple background scans. Confirm that the command owner accepts one request rather than continually retriggering it.
  4. Test the right-hand gripper through its normal sequence and verify that the mapping correction did not exchange normal left/right behavior elsewhere.
  5. Repeat with the foreground gripper logic enabled. Trace command order and confirm that no later write reverses or redirects the requested state.

Recurring faults include trusting a logical name without tracing its endpoint, editing IP addresses before checking software bindings, allowing two tasks to command one actuator, and using a maintained Boolean as though it were a one-shot event. Another pitfall is declaring success after seeing any gripper move. Acceptance requires the requested physical side, one response per request, and unchanged behavior in the other arm's normal sequence.

FAQ

What happens if both tasks can command a gripper?

The observed state depends on execution order, and a later command can mask the earlier request. Give one task command ownership and let other tasks submit requests with an acknowledge state.

What happens if the left and right references are reversed?

A valid left-hand command reaches the right-hand endpoint, so the right gripper moves without any fault in its servo. Correct the logical-to-endpoint association while retaining the existing IP addresses.

What happens if signal B stays active?

TASK_BG can evaluate the condition on successive scans and repeatedly issue the open request. Convert the maintained level into a single accepted event or use a request/acknowledge handshake.

When should I stop testing and contact ABB support?

Stop if the verified logical binding points to the left endpoint but controller diagnostics show the command reaching another device, or if controlled tests produce inconsistent physical responses. Preserve the IP map, task trace, request-versus-response matrix, controller configuration, and diagnostic records, then escalate through official ABB support.