Generating WinCC Alarms Without Manual Tag Entry: AS-OS, VBS API, and Bit-Level Methods
1. Overview: The Alarm Engineering Bottleneck
In a typical WinCC HMI/SCADA project, alarm configuration is one of the most labor-intensive engineering activities. A mid-sized plant with 200 motors, 400 valves, and several hundred discrete I/O points can easily produce 2,000 to 5,000 individual messages. When every message requires a manual tag entry in the WinCC Tag Management and a parallel entry in Alarm Logging, the engineering time balloons, the configuration database becomes error-prone, and every PLC-side signal rename cascades into a manual HMI-side update.
Siemens offers several mechanisms that allow the engineer to either push the alarm definition down to the PLC (so the message travels with the program) or to read the alarm state from a packed bit-pattern tag using a single HMI tag per device. The methods covered in this article are:
- AS-OS engineering: configure messages in STEP 7 and have them exported to WinCC automatically.
- The WinCC Configuration Tool: bulk-edit alarm text, message classes, and acknowledgment from an external spreadsheet.
- VBS / C API call against the Alarm Logging runtime to set/reset messages programmatically.
- Bit-level Alarm Logging on a single status tag, so one DWORD drives up to 32 alarms.
All four methods are valid production techniques; the correct choice depends on whether STEP 7 and WinCC are co-located, whether the project uses PCS 7, and whether the HMI platform is classic WinCC or TIA Portal WinCC Professional.
2. Alarm Engineering Approaches Comparison
| Method | Where the alarm is defined | Tags required in WinCC | Manual HMI work per alarm | Best fit |
|---|---|---|---|---|
| AS-OS with Alarm_8 / Alarm_8P | STEP 7 / TIA PLC symbol comments | One raw data tag per CPU (message frame) | 0 (auto-generated) | PCS 7, large plants, S7-300/400 + WinCC V7 |
| WinCC Configuration Tool (Smart Tools) | External Excel / CSV, imported to Alarm Logging | One tag per alarm as usual | Bulk import (no per-tag typing) | Classic WinCC projects, retrofit of legacy data |
| VBS / C API to Alarm Logging | WinCC project, no tag | 0 (no HMI tag at all) | 0 (scripted) | Custom faceplates, dynamically instanced objects |
| Bit-level Alarm Logging on a packed tag | WinCC Alarm Logging, bit reference | 1 tag per device / panel | Medium (one tag, many messages) | Status words from drives, valve manifolds, MCCs |
3. Method 1 - AS-OS Engineering with Alarm_8 / Alarm_8P
The AS-OS engineering concept is the canonical Siemens answer to "do I have to type every alarm in WinCC?". The principle is that the message text, message class, acknowledgment requirement, and trigger tag are all defined in the STEP 7 project on the PLC side, and the STEP 7 / WinCC integrator exports them to WinCC in a single batch operation.
3.1 PLC-Side Configuration
- Open the STEP 7 project containing the S7-300 / S7-400 program (or the TIA Portal project for S7-1500).
- Insert an
FBalarm block. For S7-300/400, the standard block isFB 35 (ALARM_8P)from the standard library; for S7-400H and S7-1500 the corresponding type isALARM_8Pwith up to 8 associated values. For simpler applications the legacyFB 33 (ALARM)orFB 36 (NOTIFY_8P)can be used. - Wire the message trigger bit, the acknowledge variable, and the message number. The message number is the linkage between the PLC program and the WinCC text library; the same number must exist in both.
- Edit the message text directly on the symbol or on the block instance. STEP 7 stores this text in the S7 program container. Up to 10 associated values (
EV_1throughEV_10) can be embedded; each is sent to WinCC as a tag value at runtime.
3.2 Export to WinCC
- In the STEP 7 / WinCC configuration tool (Options > STEP 7 - WinCC Assignment or the PCS 7 plant view), select the S7 program and the target WinCC project.
- Trigger the Compile OS (PCS 7) or Export Messages (classic STEP 7) action. This writes a binary file containing every message text, message class, and tag association.
- WinCC ingests the file and creates a single raw data tag of type
WORDorDWORDper CPU, plus the full message text in Alarm Logging. No per-alarm WinCC tag is generated. - At runtime, the CPU sends the message number and the up-to-10 associated values as a frame; WinCC looks up the text by number and displays it without ever polling an individual tag.
3.3 Limits and Notes
- Message number range is 0 to 65535 in classic AS-OS; PCS 7 reserves 0-9999 for system messages.
- Maximum of 10 associated values per message, each 4 bytes (REAL or DWORD) or 8 bytes (REAL extended).
- The technique is S7-300/400 / S7-1500 native. It is not available for third-party PLCs over OPC, although a similar pattern can be built with the WinCC Alarm Logging
Alarm_DLGHMIand a custom message frame driver.
4. Method 2 - WinCC Configuration Tool (Smart Tools)
The WinCC Configuration Tool is delivered as part of the WinCC Smart Tools package and is the official bulk-editor for Alarm Logging. It exchanges CSV files with the WinCC project database, which means the alarm list can be edited in Excel and then re-imported.
4.1 Typical Workflow
- Install the Configuration Tool from the WinCC DVD under Smart Tools > WinCC Configuration Tool. It is also documented in the WinCC Information System under Smart Tools.
- Open the tool, point it at the active WinCC project, and select Export Alarms. A CSV is produced with one row per message.
- Edit the CSV in Excel. Reasonable column mappings are:
Number,Class,Type,Tag,TriggerBit,MessageText_EN,MessageText_DE,AckModel. - Save the CSV and run Import Alarms. The tool writes directly into the WinCC project database; Alarm Logging is updated without manual entry.
4.2 Spreadsheet-to-Alarm-Logging Mapping
| Excel column | WinCC Alarm Logging field | Typical value |
|---|---|---|
| Number | Message number | 100001 |
| Class | Message class (Error / Warning / Information) | Error |
| Type | Message type (Incoming / Outgoing / Ack) | Incoming, must be acknowledged |
| Tag | Trigger tag name | Motor1_Status |
| TriggerBit | Bit number inside the tag (0-31) | 3 (overload) |
| MessageText_EN | Text library EN | Motor %s overload tripped |
| MessageText_DE | Text library DE | Motor %s Überlast ausgelöst |
5. Method 3 - VBS / C API for Programmatic Alarm Control
WinCC exposes its Alarm Logging runtime through a COM automation interface. The VBScript object HMIRuntime.Alarm (in classic WinCC) and the equivalent C/C# API in WinCC Professional allow the engineer to raise and clear messages from a script, without ever having defined the alarm in Alarm Logging beforehand.
5.1 Raising a Message via VBScript
Sub RaiseMotorAlarm(motorTagName, stateBit)
Dim alarm
Set alarm = HMIRuntime.Alarm
' State machine for the motor faceplate:
' bit 0 = running
' bit 1 = tripped
' bit 2 = overload warning
' bit 3 = communication fault
If (stateBit And 1) <> 0 Then
alarm.CreateSystemState "Motor " & motorTagName & " running", 0
End If
If (stateBit And 2) <> 0 Then
alarm.CreateSystemState "Motor " & motorTagName & " TRIPPED", 1
End If
If (stateBit And 4) <> 0 Then
alarm.CreateSystemState "Motor " & motorTagName & " overload warning", 2
End If
If (stateBit And 8) <> 0 Then
alarm.CreateSystemState "Motor " & motorTagName & " COM fault", 1
End If
End Sub
5.2 Available API Surface
| Method | Effect | Notes |
|---|---|---|
HMIRuntime.Alarm.CreateSystemState |
Raises a system-state message | Does not require a pre-defined alarm row in Alarm Logging |
HMIRuntime.Alarm.ResetSystemState |
Clears a system-state message | Use the same text string as the Create call |
HMIRuntime.Alarm.Acknowledge |
Acknowledge a specific message instance | Requires message instance ID |
SSMSet (C API) |
Set a state-driven message in C | WinCC Professional runtime API |
MSGSet (C API) |
Set a message-driven message | Used in PCS 7 custom DLLs |
5.3 The "Customized Object" Use Case
The original question in this thread was: "I want a custom object whose internal bits should generate alarms. Is this possible?" The answer is yes, with two distinct approaches:
- Bind the custom object's bits to a status
DWORDtag and use Method 4 below (bit-level Alarm Logging). The object is re-usable, the alarm definition is project-wide. - Place a VBScript on the object that calls
HMIRuntime.Alarm.CreateSystemStateon demand. No WinCC tag at all is required; the alarm is generated from the script context. This is the most "config-free" approach but loses the standard Alarm Logging view of state and acknowledgment.
6. Method 4 - Bit-Level Alarm Logging on a Packed Tag
This is the most popular method for reducing tag count. Instead of creating one WinCC tag per alarm trigger, the engineer creates one DWORD (or WORD) per device and defines up to 32 alarms on individual bits of that single tag.
6.1 Setting Up Bit-Level Trigger
- In WinCC Tag Management, create a single tag, e.g.
Motor1_StatusWord, of data typeUNSIGNED32(DWORD). - Open Alarm Logging, create one message row per bit you want to alarm on, and set the trigger to
Motor1_StatusWordwith the bit number field set to 0, 1, 2, ... up to 31. - Define the message class, text, and acknowledgment model per bit. For instance bit 0 = "Motor 1 overload trip", bit 1 = "Motor 1 breaker open", bit 2 = "Motor 1 VFD fault", etc.
6.2 Why This Works at All
Alarm Logging is a polling engine. The polling cycle (default 250 ms, configurable in the WinCC project properties) reads the trigger tag, masks the configured bit, and raises the alarm if the masked value transitions from 0 to 1. Because the mask and the bit interpretation live in Alarm Logging rather than in the tag, you get N alarms for the price of one tag acquisition.
6.3 Limits
- Maximum 32 bits per DWORD, so up to 32 alarms per device. A motor with 20 alarms consumes one tag and produces twenty messages.
- The CPU side must pack the bits; the engineer should document the bit map in a project-wide naming convention (e.g.
Dev_Status.bit0= overload,bit1= breaker, ...). The faceplate can use the same convention for color coding. - One bit per alarm. Multi-bit patterns (e.g. "state = 0x03 means warming up") require either two separate messages or a derived tag with a comparison expression.
7. TIA Portal Unified Alarm Engineering
The TIA Portal (STEP 7 V15 and later, WinCC Professional / WinCC Unified) merges the PLC and HMI configuration under one engineering tool. This naturally aligns with the original question: "Can WinCC read messages from a single raw-data block defined in the PLC?"
7.1 HMI Alarm Configuration Inside TIA Portal
- Open the TIA Portal project and select the HMI device.
- Navigate to HMI alarms > Discrete alarms. The editor lists all PLC tags with their symbol comments.
- For each PLC tag you want to alarm on, click Add. A new alarm row is generated, pre-populated with the PLC tag name and the symbol comment as default message text.
- Edit message class, acknowledgment model, and trigger bit if the tag is a bit-packed structure. The compiler propagates the configuration to the WinCC runtime database on download.
7.2 PLC Program Blocks for TIA Alarm Generation
For S7-1200 / S7-1500, the alarm blocks are Program_Alarm (S7-1500) and the legacy WRMSG / WRMSG_Q instructions. The pattern is:
// SCL example for S7-1500
IF #overloadTrip THEN
"Program_Alarm".OVERLOAD(MSG := 'Motor #name overload tripped',
Severity := 1, // 1 = error
EnableTag := TRUE);
ELSE
"Program_Alarm".OVERLOAD(Enable := FALSE);
END_IF;
Each Program_Alarm instance generates one alarm row visible in the TIA Portal HMI alarm editor. The text and the trigger live in the PLC code; the HMI side only renders the alarm.
7.3 Exporting PLC Messages into a Classic WinCC Project
For projects that use STEP 7 (classic) and WinCC separately, the AS-OS export is the supported route. The relevant setting is in SIMATIC Manager > Options > Configure AS-OS Assignment. See the WinCC message configuration FAQ for the exact menu path and the supported message number ranges.
8. Project Transfer and OS Download Workflow
A second practical concern that often comes up: STEP 7 is installed on the engineering laptop, while WinCC is installed on the customer PC. There are three supported transfer flows.
8.1 Zip and Transfer
The most common flow. The engineer copies the WinCC project folder (typically C:\Program Files\Siemens\Automation\WinCC\WinCCProjects\<ProjectName>), zips it, and copies it to the customer PC. WinCC V7.x stores all configuration, graphics, and the runtime database in this folder, so the transfer is self-contained. Restart the WinCC Explorer on the target PC and the project opens with the same paths as on the engineering station provided the drive mapping is preserved.
8.2 OS Download (PCS 7 / Step 7 Integrated)
- On the engineering station with STEP 7 / PCS 7 and the WinCC Configuration software installed, open SIMATIC Manager.
- Select the OS, right-click and choose Download OS to Target System. STEP 7 transfers the compiled OS runtime to the WinCC station over the configured network.
- The customer PC needs the WinCC runtime license and a network route to the engineering station. No manual file copy is required.
8.3 TIA Portal Download
In TIA Portal the equivalent is Online > Download to Device > Software (only) for the HMI device. The HMI device must be reachable on PROFINET / Ethernet and the HMI runtime on the target station must be in transfer mode.
9. STEP 7 and WinCC Co-Installation Requirements
AS-OS engineering requires the STEP 7 / WinCC integrated toolset on the same PC (either both installed, or STEP 7 installed with the WinCC add-on). The Configuration Tool and the VBS API do not require STEP 7 on the runtime PC; they only need WinCC. Bit-level Alarm Logging needs neither. The table below summarizes the workstation requirements.
| Method | Engineering PC | Customer / Runtime PC |
|---|---|---|
| AS-OS | STEP 7 + WinCC Configuration | WinCC Runtime only |
| Configuration Tool | WinCC Configuration + Smart Tools | WinCC Runtime only |
| VBS API | WinCC Configuration | WinCC Runtime only |
| Bit-level Alarm Logging | WinCC Configuration | WinCC Runtime only |
For WinCC V7.5 and later, the WinCC Information System documents these methods under Working with WinCC > Alarm Logging and Smart Tools > WinCC Configuration Tool. Refer to the WinCC V7.5 System Manual for the message-class taxonomy and the WinCC Information System FAQ for the runtime architecture.
10. Verification and Commissioning
Whichever method is chosen, the verification procedure is the same.
- Tag simulation: In WinCC Explorer, open Tools > WinCC Tag Simulation. Force the trigger tag (or each individual bit for Method 4) to 1 and confirm the corresponding message row appears in the Alarm Control view.
- Acknowledgment path: Click the message in the Alarm Control and confirm the horn / acknowledgment icon toggles correctly. If the message is set to "must be acknowledged", the alarm stays in the active list until acknowledged.
- Bit masking verification: For Method 4, force bit 17 of the status DWORD to 1 and confirm that only the alarm configured on bit 17 fires, not the alarm on bit 18. This catches the common mistake of mis-numbering bits in the Alarm Logging row.
- Project transfer integrity: After the customer PC is updated, open the project, regenerate the runtime database, and confirm that the message text in the Alarm Control matches the engineering project. WinCC stores the text in the runtime database, so a corrupted transfer can leave the engineering database correct but the runtime database stale.
- Archive round-trip: If the project archives alarms, trigger a sample alarm, wait for the configured archive cycle, and read the alarm back from the archive. This confirms that the message number / class is correctly mapped in the database, not just in the editor.
11. Troubleshooting Matrix
| Symptom | Likely cause | Fix |
|---|---|---|
Alarm text in Alarm Control shows @@@@ instead of the configured text |
Runtime database not regenerated after edit | Right-click the project in WinCC Explorer, choose Regenerate Runtime Database, then restart the runtime |
| Bit-level alarm fires on the wrong bit | Bit numbering offset (LSB vs MSB) confusion in Alarm Logging | Verify the bit field is 0-31 with LSB = bit 0, and that the PLC packs the bits in the same order |
| VBS-generated system state message does not appear in the Alarm Control | Alarm Control filter excludes system messages | In the Alarm Control properties, enable the "System messages" filter class |
| AS-OS export produces 0 messages | STEP 7 / WinCC project not yet linked via Configure AS-OS Assignment | Open the STEP 7 OS assignment dialog, set the target WinCC project, then re-export |
| Configuration Tool import reports "tag not found" | The CSV references a tag that does not exist in WinCC Tag Management | Add the tag first, or remove the row from the CSV. The tool does not create tags |
| Alarm clears immediately on PLC stop / connection break | Tag returns a quality bad / substitute value, the bit becomes 0, the alarm clears | Configure the alarm as "latching" in Alarm Logging, or map the bit to a non-zero quality substitution |
| Too many messages flooding the alarm view | Polling cycle too short and alarm classes too broad | Increase the Alarm Logging polling cycle to 500-1000 ms, and group low-priority messages into a single "process warning" class |
12. Field Notes and Best Practices
- Pick one method per project. Mixing AS-OS (which expects a STEP 7 / WinCC integrated engineering flow) and bit-level (which expects a single packed status tag) inside the same project produces confusing message-number collisions and double-firing alarms.
- For S7-1500 with TIA Portal, use the
Program_Alarmblock family; the engineering effort per alarm is the lowest in the Siemens portfolio. - For classic WinCC + S7-300/400 plants with hundreds of identical motors, the Configuration Tool combined with a bit-level status word is the fastest path: one CSV defines the alarm text, one tag per motor carries the bit pattern, and the operator faceplate reuses the same screen for every device.
- For PCS 7 plants, AS-OS is the only sanctioned approach. The PCS 7 course covers the message-number reservation, the standard message classes, and the operator authorization handling that the AS-OS pipeline assumes.
- Always export the alarm list (CSV) and the tag list (CSV) at project handover, and archive them under version control. The WinCC project database is a binary blob; a future engineer who needs to bulk-edit will be grateful for a text export.
13. Frequently Asked Questions
Can WinCC generate alarms without any configured WinCC tag at all?
Yes, via the HMIRuntime.Alarm.CreateSystemState VBS method or the equivalent C API. The alarm text is the parameter, the trigger is the script call. No tag is required. Note that these system-state messages cannot be acknowledged in the same way as configured alarms.
How many alarms can a single WinCC tag drive via bit-level Alarm Logging?
Up to 32 per DWORD tag (16 per WORD, 8 per BYTE). Each bit in the tag can trigger one message row in Alarm Logging. The polling cycle is shared across all bit-triggered alarms on the tag.
Does AS-OS engineering work with S7-1200 / S7-1500 in TIA Portal?
Yes, but the legacy AS-OS export from classic STEP 7 does not. In TIA Portal the equivalent is the HMI alarm editor under the HMI device, populated from the PLC symbol or the Program_Alarm blocks. The message travels as part of the project download, not as a separate export step.
Is a PCS 7 course necessary to learn AS-OS engineering?
For full PCS 7 message-class handling, operator authorization, and standard message numbering, yes. For a one-off STEP 7 / WinCC project using the legacy export, the WinCC message configuration FAQ and the Configuration Tool's online help are sufficient.
Can STEP 7 and WinCC be installed on the same PC and the project still transferred to a different PC?
Yes. The AS-OS compile produces a WinCC project folder that is self-contained. Zip the project folder (typically under WinCCProjects\<ProjectName>), copy it to the customer PC, and continue editing there. If both PCs have STEP 7 + WinCC installed, the Download OS to Target System function avoids the manual file copy.
What happens to bit-level alarms when the PLC connection is lost?
The trigger tag reports a quality-bad code, the runtime substitutes the configured substitute value (default 0), and the alarm clears. To prevent accidental clearing on a connection loss, mark the message as latching in Alarm Logging, or set the substitute value to 0xFFFFFFFF so all bits remain active until the operator clears them.