Overview
Operating two separate WinCC Runtime stations from a single engineering location is a common requirement in plant modernization. The classic case is two IPCs running independent single-user (single-station) projects with local RT licenses, plus a third IPC dedicated to configuration that must compile, edit graphics, and download to both runtime systems without disrupting production.
Two production-grade architectures solve this:
- SIMATIC Manager multi-project integration with a full RC (WinCC Configuration) license on the Engineering Station (ES).
- Engineering Client approach where the ES opens WinCC projects remotely as a client, using only an RC Client license, while RT stations hold server licenses.
The choice is governed by licensing cost, future scalability (single station vs. distributed multi-user), and which engineering tool is already installed (WinCC V7.x with SIMATIC Manager or TIA Portal / WinCC Professional). The guidance below follows Siemens official documentation: WinCC in SIMATIC Manager - Engineering and Runtime, the PCS 7 multi-project manual Multi-project / multi-user engineering (V9.0), and TIA Portal multiuser engineering.
WinCC Project Types and Licensing Fundamentals
Before choosing a topology, fix the terminology. The WinCC V7.x product line distinguishes the following project modes, each with its own license envelope:
| Project Type | Runtime Role | Required License | Typical Use |
|---|---|---|---|
| Single-User Project | One RT station, no clients | WinCC RT (RC used at design only) | Standalone machine HMI |
| Server Project (Multi-User) | RT Server hosting client connections | WinCC Server RT | Distributed plant visualization |
| Client Project | Operator/client only, no local RT tags | WinCC Client RT (or RC Client for configuration) | Multi-client stations |
| Engineering Station (ES) | Configures and downloads projects | WinCC RC (full) or RC Client (when remote-editing server projects) | Central engineering |
Key licensing points per the SIMATIC HMI WinCC V7.5 SP2 manual and WinCC engineering in SIMATIC Manager (entry 59216666):
- RT license activates runtime on the IPC; it does not enable project editing.
- RC license enables full offline configuration (graphics, scripts, tags, alarms, archives) and is required to compile, download, and modify a WinCC single-station project.
- RC Client license is a reduced-price RC variant that permits editing a WinCC Server (multi-user) project opened remotely as a client. It cannot create a new project; it edits an existing server-side project.
- Server RT license is needed only when the runtime becomes a multi-user server. For two IPCs that will remain single stations, server licenses are not required.
Architecture Comparison
The two architectures have different operational and cost profiles. The table below summarizes trade-offs:
| Aspect | Option 1: SIMATIC Manager Multi-Project + RC | Option 2: Engineering Client + RC Client |
|---|---|---|
| Engineering tool on ES | WinCC Explorer + SIMATIC Manager | WinCC Explorer (remote project open) |
| Project storage | Centralized in a SIMATIC Manager multiproject on ES; distributed to RTs on download | Stored on each RT; ES opens remote folder/share |
| License on ES | Full RC license | RC Client license |
| License on RT #1, #2 | RT license (single-user) | Server RT license (multi-user) |
| Future scalability to additional clients | Limited - requires migration to multi-user | Native - clients connect to existing server project |
| Single source of truth for graphics | Yes - master data library lives in the multiproject | Partial - each RT has its own copy, must be kept in sync |
| Compile/Download path | Download via SIMATIC Manager to selected target | Compile and activate on the remote RT directly |
| Network dependency | Only at download time | Persistent UNC path to RT share required |
Decision Matrix
| If your situation is... | Choose |
|---|---|
| Both RTs will stay single-station for the foreseeable lifetime | Option 1 |
| Future requirement to add operator/thin clients at either RT | Option 2 |
| Need to keep all tag databases, scripts, and graphics in one master library | Option 1 |
| ES is rarely used and RT projects must remain editable locally | Option 2 |
| Plant already standardized on PCS 7 with SIMATIC Manager | Option 1 (see PCS 7 multi-project manual) |
| Plant standardized on TIA Portal / WinCC Professional | TIA multiuser engineering (see Section 8) |
Option 1: SIMATIC Manager Multi-Project with Full RC License
This approach follows the official Siemens procedure documented in entry 59216666 and the PCS 7 multi-project manual at 22258951 (V9.0). The engineering station owns the canonical project, and downloads push compiled WinCC projects to each IPC over the plant network.
Prerequisites
- WinCC V7.x installation media matching the RT version on IPC #1 and IPC #2 (mixing major versions causes tag export failures).
- SIMATIC Manager installed on the ES (bundled with WinCC V7.x or installed separately).
- A full WinCC RC license on the ES.
- RT licenses installed on IPC #1 and IPC #2.
- Network reachability between ES and both RT stations; admin shares (
WinCC_Projectfolder) accessible with the WinCC service account. - Same Windows user account (or mirrored service account) configured as a member of the local
SIMATIC HMIgroup on ES and on both RT IPCs.
Procedure
- On the ES, launch SIMATIC Manager and create a new multiproject via File > New > Multiproject. Name it after the line or area (for example,
LineA_MultiProject). - Inside the multiproject, create two sub-projects:
IPC1_WinCCandIPC2_WinCC. Mark the multiproject as the master for shared master data library. - Right-click each sub-project and assign the target station as WinCC Station. Configure the PC name and the network address of IPC #1 and IPC #2 in Object Properties > Target System.
- Install/configure the WinCC project of each RT once directly on the IPC (graphics, tag connections to the PLC, alarm logging, archives). This is the "as-built" project that will be pulled into the ES.
- On the ES, set the target path for each sub-project to the corresponding RT share:
\\IPC1\WinCC_Projectand\\IPC2\WinCC_Projectusing the WinCC service account. - Use PLC > Compile and Download Objects in SIMATIC Manager to push the WinCC sub-project to the assigned RT. WinCC generates the runtime files and starts activation remotely.
- After the first successful round-trip, all future engineering edits happen on the ES sub-project only. Always end with a compile/download to the affected RT.
- Manage shared objects (master data library, central tag prefixes, common picture modules) at the multiproject level so that changes propagate consistently. See Multi-project / multi-user engineering V8.2 manual for the master data library workflow.
Verification
- On the ES, in SIMATIC Manager select both sub-projects and choose Target System > Check Target Path. Both must report
OK. - Compile a sub-project and verify that the generated
*.RTcompile log lists zero errors and zero warnings. - On the target IPC, open WinCC Explorer > Project Properties and confirm the version header matches the ES compile. Mismatch indicates an incomplete download.
- Activate Runtime on the IPC. Status bar must read
Runtime activewith no red alarm line. - Force a tag change from the PLC and confirm the value updates on the HMI. If it does not, the tag connection (channel/connection name) was not migrated correctly during the first pull.
Option 2: Engineering Client with RC Client License
This approach uses the ES strictly as a remote editing client. Both RT stations are reclassified as multi-user (server) projects; the ES opens the project over the network using WinCC Explorer's "Open remote project" function and edits with an RC Client license.
Prerequisites
- Both RT IPCs must hold WinCC Server RT licenses (one per server, not one per client).
- ES must hold an RC Client license.
- The two RT projects must already exist as single-station projects. Convert them to multi-user by adding the Server option in the project properties and reactivating Runtime once locally.
- Network: ES must resolve and authenticate to
\\IPC1\<ProjectName>and\\IPC2\<ProjectName>. Use a service account with read/write toSIMATIC HMIACL on both servers. - No SIMATIC Manager is required on the ES for this option, which simplifies the install footprint.
Procedure
- On IPC #1, open WinCC Explorer, choose Project Properties > Type, switch from Single-User to Multi-User Server. Repeat on IPC #2. Re-activate Runtime locally to validate the project still runs.
- From the ES, open WinCC Explorer and select Open > Open Remote Project. Enter
\\IPC1\WinCC_Project\<ProjectName>.mcp. The first connection prompts for credentials; persist them via Windows Credential Manager if the ES is rebooted often. - Perform all edits - graphics, scripts, tag connections - in this remote project. Save back to the server. The RC Client license allows full edit operations but does not permit creating a brand-new project on the ES share.
- To compile, choose Compile > Remote Compilation. WinCC performs the compile on the RT using the RT's own tag database; only changes are shipped back to the ES over the network.
- To switch to the second station, close the remote project on IPC #1 and open the remote project on IPC #2 using the same dialog. Keep two separate WinCC Explorer windows if you need to compare graphics side by side (allowed by RC Client licensing, but not simultaneous activation - activate only one runtime at a time from the ES).
- For future operator clients, install WinCC Client RT on a third IPC and configure it to point at either server. No engineering changes are required on the servers.
Verification
- On the ES, open WinCC Explorer > Diagnostics. Both remote projects must show
Status: Reachable. - Trigger a tag write from WinCC Explorer on the ES. Confirm the value lands on the connected PLC (use the WinCC tag simulator if no PLC is connected during commissioning).
- Compile a small change (e.g., rename a button label) and verify the runtime picks it up within one activation cycle.
- Check the WinCC license overview on the ES: WinCC Explorer > Help > About must report
RC Clientin use, notRC Demo.
When the Plant Uses TIA Portal / WinCC Professional
For WinCC Professional (TIA Portal) deployments, the equivalent of the SIMATIC Manager multi-project is the TIA multiuser engineering feature. According to the TIA Portal multiuser engineering manual, multiple configuration engineers work in parallel on a shared server project, reducing configuration time on large plants. The functional mapping is:
- SIMATIC Manager multiproject → TIA multiuser server project stored on a shared TIA Portal project server (TiaPortalProjectServer).
- RC license → TIA Portal Professional license with the WinCC Professional option.
- RC Client license → TIA Portal multiuser engineering seat.
For a two-RT topology under TIA, you would create a single multiuser server project containing both HMI stations as devices, configure from any ES, and download to either RT independently. This collapses the dual-IPC problem into a single engineering source, which is the recommended path for greenfield projects.
Common Failure Modes and Field Notes
| Symptom | Likely Root Cause | Fix |
|---|---|---|
| ES reports "License not found" on startup | RC dongle missing, RC Client installed where RC expected (or vice versa) | Verify license type matches the chosen architecture; check Automation License Manager |
| Compile errors only on one RT | WinCC version mismatch between ES and the affected RT | Align SP versions; e.g., V7.5 SP2 on ES with V7.5 SP2 Update X on RT |
| Download hangs at 50% | WinCC service account lacks write permission on RT share | Grant Modify on \\RT\WinCC_Project; restart WinCC CCAgent |
Tags show Connection failed after remote edit |
Channel/connection name changed during pull-in | Re-assign connections via SIMATIC Manager; never rename channels inside WinCC after first download |
| Second RT runs stale graphics after ES update | Forgot to download to the second station | Always select both sub-projects and choose Download All; verify in WinCC Explorer > Project Properties |
| ES cannot open remote project over UNC | UAC or SMB signing mismatch; wrong subnet | Add the ES to the RT's TrustedHosts; verify net use succeeds under the WinCC service account |
| Runtime crashes on activation after remote edit | RC Client edit introduced unsupported object (e.g., obsolete OCX) | Roll back the last remote save from \RT\WinCC_Project\Backup; reproduce locally on the RT with full RC |
Sizing and Capacity Considerations
For the ES hardware, plan capacity using the formula below when sizing disk and memory for the multiproject:
ProjectSize_MB = Sum(Archives_MB) + 2 * Sum(Tags * TagLength) / 1024 + Sum(Pictures * PictureKB)
A typical medium WinCC station (8,000 tags, 150 pictures, 5,000,000 archive records) consumes 1.5 - 2.5 GB. Plan the ES disk at 4× that figure to allow compile logs, backup generations, and GSD/GSDML caches. RAM should be at least 16 GB for V7.5 SP2 with a multiproject; WinCC compile is single-threaded but database lookups scale with project size.
For network, the download of a fully compiled WinCC project (100 MB typical) over a 100 Mbit link completes in roughly 10 - 15 s. For larger projects with full archives, allow 60 s and ensure Quality of Service prioritizes ES → RT traffic to avoid compile-then-activate conflicts.
Recommended Architecture by Scenario
| Scenario | Recommended Architecture | Rationale |
|---|---|---|
| Two IPCs, no growth, SIMATIC Manager present | Option 1 (multi-project + RC) | Lowest total license cost; one source of truth |
| Two IPCs with planned operator clients | Option 2 (Engineering Client + RC Client) | Future clients attach to existing server projects without rework |
| Two IPCs on TIA Portal | TIA multiuser engineering | Native multiuser workflow; avoids SIMATIC Manager entirely |
| Brownfield migration: V7 single stations becoming distributed | Option 2 first, then TIA later | Stepwise migration preserves licenses |
Operational Checklist
- Confirm WinCC and SIMATIC Manager SP versions on ES match the RT stations.
- Verify the ES holds either an RC license (Option 1) or an RC Client license (Option 2) - not both, not neither.
- Confirm network reachability between ES and each RT using
WinCC_RT_Pingortcps7.exediagnostics. - Ensure the WinCC service account has
SIMATIC HMIgroup membership on every machine. - Run a round-trip compile/download of a no-op change to validate the path before any production edit.
- Document the project storage location (ES share vs. RT share) in the plant engineering log so that on-call engineers know where to find the live source.
Which license do I need on the Engineering Station for two single-user RT projects?
You need a full WinCC RC license if the RTs stay single-station and you integrate the projects in a SIMATIC Manager multiproject. You need an RC Client license if you convert the RTs to multi-user servers and edit the projects remotely. RC Client is cheaper but requires a Server RT license on each IPC.
Can the ES download a project to both IPCs at the same time?
Yes, via SIMATIC Manager PLC > Compile and Download Objects with both sub-projects selected. The download is sequential per target but the overall operation is driven from a single dialog. Ensure both RT shares are reachable before initiating.
Do I need SIMATIC Manager if I use TIA Portal?
No. TIA Portal replaces SIMATIC Manager. For multiuser configurations on TIA, use the TIA multiuser engineering workflow with a shared server project.
What happens if I edit a single-user WinCC project from the ES without an RC license?
WinCC Explorer runs in demo mode: the runtime adds a watermark, the project auto-deactivates after 24 hours, and downloads abort with a license error. You must install the correct license before commissioning.
Is there an official Siemens reference for this topology?
Yes - entry 59216666 in the Siemens Industry Online Support describes configuring and operating WinCC from SIMATIC Manager across multiple stations, and the PCS 7 multi-project manual covers the master data library and parallel engineering pattern.