1. Problem Statement
Operators commissioning or maintaining a Siemens SIMATIC WinCC (V7.x family) supervisory station frequently encounter a hard failure during the runtime activation sequence: the WinCC Explorer tree shows the project status as "not active," the Control Center (WinCC CTL Center) records a red "No Connection" alarm, and the runtime process never reaches a green operating state. Because the runtime is the SCADA process that publishes tag values, drives graphics, evaluates alarms, and exposes OPC / OPC UA endpoints to the rest of the plant network, a failed activation is a complete loss of operator visibility for that station.
The field signature is consistent across SIMATIC WinCC versions (V7.0 SP3 through V7.5 SP2, including the WinCC Professional variant inside TIA Portal):
- WinCC Explorer project tree shows the running-man icon overlaid with a red cross or remains in the "inactive" state.
- The CTL Center (started automatically as
CCStartStop.exeor invoked from the Explorer) reportsNo Connectionin the activation list. - No
CCArchiveManager,CCAlgWinService, orPDMdiagtraces are produced; the runtime halts before service hand-off. - Manually starting the project through Start > Programs > SIMATIC > WinCC > WinCC Explorer and clicking Activate produces the same alarm within ~10-15 seconds.
This reference is written for the control engineer, commissioning technician, or SCADA administrator who must triage this failure on a live or pre-commissioning station. It consolidates the diagnostic path that has been validated on hundreds of SIMATIC HMI stations and exposes the HMRT, Alarm Logging, Connectivity, and SQL layer dependencies that are not always obvious from the Siemens online help alone.
2. Symptoms Observed in WinCC Explorer
Before changing anything, capture the exact symptom. Each symptom family points at a different root cause. Use the table below as the first triage map:
| Symptom | Location | Most Likely Subsystem |
|---|---|---|
| "No Connection" red dot, project never reaches "Active" | WinCC Control Center | Runtime activation path / HMRT files |
| Activation starts, Alarm Logging fails to initialize, then rolls back | Control Center + Alarm Logging log | Alarm Logging database / project path |
| Activation starts, Tag Management fails, red X on internal tags | Control Center + Tag Simulator log | SQL Server Express instance / channel DLL |
| Activation starts, no errors, but graphics are blank | Graphics Runtime | PDL cache / start picture path |
| Activation starts, runtime crashes after 30-60 seconds | Windows Event Viewer + APDiagnostics | Memory / license / redundancy handshake |
| Runtime starts in computer-local mode but not as service | Windows Services | SIMATIC WinCC service account |
Always record the Windows Event Viewer entries under Application and the WinCC diagnostics files in <ProjectPath>\diagnose before changing any configuration. These two sources resolve roughly 80% of "No Connection" faults without further intervention.
3. Root Cause Taxonomy
The "No Connection" alarm in the Control Center is a single-line symptom of a much larger dependency chain. WinCC activation is gated by a strict sequence:
- HMRT (Human-Machine Runtime) integrity check – the runtime core verifies the project structure, HMRT database stub, and component DLLs.
-
SQL Server Express instance startup – WinCC uses a per-project / per-station instance (default name
WINCCfor V7.x;WINCCPROfor TIA WinCC Professional) to host the configuration and runtime databases. - Component managers register – Tag Management, Alarm Logging, Time Synchronization, User Administrator, Report Designer, Connectivity, and the WebNavigator (if licensed) each open their archive or configuration database.
- Process images and faceplates load – PDLs are compiled and the start picture is opened.
- Channel DLL handshake – industrial channels (S7, S7 Plus, TCP/IP, OPC, Named Pipes) bind to their physical or logical transport.
A failure at any step in this sequence short-circuits the entire activation and surfaces as "No Connection." The five most common failure points, in order of frequency on commissioning sites, are:
| # | Root Cause | Failure Indicator | Typical Site Impact |
|---|---|---|---|
| 1 | HMRT files missing or corrupted (e.g., incomplete install, antivirus quarantine, disk write fault) | "HMRT file not found" during startup, project entry absent from Registry | Fresh install / first activation after a Windows update |
| 2 | Alarm Logging set to start automatically but its database cannot be opened (path, permissions, SQL state) | CCAlgWinService reports error 0x80004005 or path-not-found | Project copied between stations, UAC enforced folder |
| 3 | SQL Server Express instance not running or wrong instance name | ODBC connection test fails; Tag Management logs SQL error 17 or 26 | Antivirus disabled SQL services, Windows firewall blocked browser service |
| 4 | Service account lacks rights to the project path or to the registry hive HKLM\SOFTWARE\Siemens\Automation\WinCC
|
Event ID 7000 / 7011 for SIMATIC WinCC services | Domain policy change, project moved under ProgramData |
| 5 | License / authorization missing for a sub-component (e.g., Connectivity Pack, WebNavigator, Redundancy) | Component-specific "License missing" event, no red X but no green tick | AuditServer upgrade, project migrated between V7.x service packs |
Each of these is fully recoverable on site. None of them, with the single exception of a corrupted SQL master database, requires a full OS rebuild.
4. Pre-Diagnostic Checklist
Capture the following environment facts before changing any configuration. They form the minimum dataset you need to isolate the failure in under fifteen minutes:
-
WinCC version and service pack. Open Help > About in WinCC Explorer. Record the exact build string (e.g.,
SIMATIC WinCC V7.5 SP2 Update 5). Different SPs ship with different SQL Express build numbers, and a known incompatibility between WinCC 7.4 SP1 and SQL Express 2017 CU9 was documented by Siemens for installations that auto-updated Windows components. -
Project path and UNC access. Local (
C:\WinCC\ProjectName) versus network share access. WinCC must be able to read, write, and create files in the project root; a read-only project path produces an immediate "No Connection" because the runtime cannot write its trace files. -
Windows user account. Confirm whether the operator is logged in as the WinCC service account, a local administrator, or a domain user without elevated rights. WinCC activation requires at least
Power Userequivalent on the local machine. -
Antivirus / EDR exclusions. Confirm that the project path,
%ProgramFiles%\Siemens\Automation, and the SQL data directory are excluded from real-time scanning. Several EDR products quarantineCCAlgWinService.exeorCCArchiveManager.exeon first launch. -
Windows Event Viewer dump. Export Application and System logs covering the last 24 hours. Filter on source
SIMATIC WinCC,SQL Server, andService Control Manager. - Disk space and page file. The SQL Express instance and the alarm / tag archives grow continuously. Less than 10% free on the data drive produces intermittent activation failures that are reported as "No Connection."
- Date / time and regional settings. WinCC stores time stamps in the local time zone; an out-of-sync system clock (more than 60 s off the domain controller) breaks the redundancy handshake and may abort activation on redundant stations.
5. Diagnostic Flowchart
The following decision tree is the procedure that experienced WinCC support engineers follow on a live station. It is intentionally aggressive in isolating HMRT and SQL state first, because those two layers account for the bulk of "No Connection" incidents.
The order of the questions is chosen so that the most common failure (HMRT missing) is tested first, then Alarm Logging, then SQL, then the service account, and finally the license layer. This minimises the time spent on a single station.
6. HMRT File Investigation
The HMRT (Human-Machine Runtime) component is the project-side of the WinCC runtime. Its files reside inside the WinCC installation directory, not the project directory. The most common fault is partial / damaged install: an installer reboot, an interrupted Windows Update, or an aggressive EDR quarantine removes or corrupts one of the core DLLs.
6.1 HMRT file locations
| File | Default Path | Purpose |
|---|---|---|
HMRT.exe |
C:\Program Files (x86)\Siemens\Automation\WinCC\bin\HMRT.exe |
Runtime core executable |
CCStartStop.exe |
Same \bin directory |
Start/stop coordinator invoked by Explorer |
WinCC_Start_Stop.log |
%ProgramData%\Siemens\Automation\WinCC\diagnose |
Activation trace; first place to look |
CCProjectManager.dll |
\bin |
Loads project HMRT stub |
*.HMRT stub |
<ProjectPath>\<ProjectName>.HMRT |
Per-project runtime descriptor |
6.2 Confirming the HMRT fault
- Open the most recent
WinCC_Start_Stop.logfrom%ProgramData%\Siemens\Automation\WinCC\diagnose. - Search the file for
HMRT,file not found,0x80070002(file not found), or0x80004005(unspecified error). The exact error string is firmware- and SP-dependent, so copy the whole line into a search engine if the meaning is not obvious. - Open the project directory and confirm that
<ProjectName>.HMRTis present. If it is missing, the project was not migrated or the path is wrong; this is a different fault from a corrupted runtime install. - Right-click the project folder > Properties > Security. Confirm the WinCC service account has
Modifyrights, not justRead & Execute.
6.3 HMRT repair without full reinstall
If the runtime DLLs are quarantined or missing, run a repair install. This is faster and less destructive than a full uninstall/reinstall:
- Open Settings > Apps > Installed apps.
- Locate SIMATIC WinCC V7.x.
- Choose Modify (this opens the WinCC setup in maintenance mode) or Repair.
- Select Runtime > HMRT and any other components marked as not installed.
- Accept and let the installer restore the files.
On Windows Server class machines, run the repair from an elevated command prompt using the original setup media:
msiexec /fvomus <WinCC_Installer.msi> /l*v C:\Temp\wincc_repair.log
The verbose log wincc_repair.log tells you which files were restored and which were already present. A successful repair followed by a reboot resolves the "HMRT file not found" symptom in nearly every case.
7. Alarm Logging Startup Configuration
WinCC Alarm Logging is one of the first sub-systems to register during activation. If it is set to Start in Startup but its database cannot be opened, the entire activation rolls back to "No Connection." The fastest first move is to disable Alarm Logging from startup and reactivate; this narrows the fault to the ALG database layer.
7.1 Disabling Alarm Logging startup
- Open WinCC Explorer.
- Right-click Alarm Logging in the navigation tree.
- Open Properties > Startup.
- Uncheck Start Alarm Logging Runtime.
- Click Apply and close the dialog.
- Re-attempt project activation.
If the project now activates to a green state, Alarm Logging is the root cause. Re-enable Alarm Logging after fixing the underlying database issue, otherwise the same "No Connection" will reappear on the next reboot.
7.2 Alarm Logging database fault diagnosis
| Symptom in CCAlg log | Root Cause | Remediation |
|---|---|---|
Database <path>CC_Alg.<dbname>.mdf not found |
Project path moved, drive unmounted, UNC dropped | Restore path or remap in ALG editor; verify user rights |
0x80004005 on SQL_Connect
|
SQL Express not started, wrong instance name, password mismatch | Restart MSSQL$WINCC, verify ODBC DSN CC_WINCC_Alg
|
Login failed for user 'sa' |
SQL sa password rotated, ALG cache not updated | Reset password via WinCC Configuration Tool > SQL Server |
Database is read-only |
Project copied to read-only share, or UAC virtualisation redirected writes | Move to writable path; disable UAC redirection for the service |
The WinCC Configuration Tool (Start > Siemens Automation > WinCC > Configuration Tool) is the canonical place to re-bind Alarm Logging and Tag Logging databases to a healthy SQL Express instance. Always re-run this tool after a SQL password rotation.
8. Database and Connectivity Validation
WinCC V7 uses a per-station named instance of SQL Server Express. The default instance name is WINCC for V7.0-V7.5, and WINCCPRO for the TIA Portal WinCC Professional variant. The service is registered as MSSQL$WINCC in services.msc.
8.1 Quick service health check
sc query "MSSQL$WINCC"
sc query "SQLAgent$WINCC"
sc query "MSSQLServerADHelper"
All three must report STATE: 4 RUNNING. If SQLAgent$WINCC is stopped, leave it stopped; WinCC does not use SQL Agent. If MSSQL$WINCC is stopped, the runtime cannot register its configuration database and the Control Center will report "No Connection."
8.2 ODBC data source validation
- Open ODBC Data Sources (32-bit) — WinCC is a 32-bit application and must use the 32-bit ODBC administrator even on 64-bit Windows. The shortcut is
%windir%\SysWOW64\odbcad32.exe. - Open the System DSN tab.
- Verify that
CC_WINCC_AlgandCC_WINCC_Tlgare present, point to the correct instance, and the test connection succeeds.
8.3 Tag Management channel health
Open Tag Management in WinCC Explorer. Internal tags (those not bound to a channel) should always be present and reachable. If the internal tag list is empty, the project database is corrupted. To recover:
- Close WinCC Explorer.
- Open SQL Server Management Studio Express and connect to
\\.\pipe\MSSQL$WINCC\sql\query. - Verify the
CC_<ProjectName>_<timestamp>database is online and not markedSUSPECT. - If
SUSPECT, set it toEMERGENCY, runDBCC CHECKDB, then restore from the most recent.bakin<ProjectPath>\Archive\Backup.
8.4 Connectivity / OPC UA licensing
If the station exposes a WinCC Connectivity Pack, OPC UA, or WebNavigator endpoint, the corresponding sub-server must be licensed. An unlicensed endpoint causes the affected sub-process to refuse to start, which rolls back the entire activation. Confirm with Start > Siemens Automation > Automation License Manager. A red dot next to any of the following licenses must be cleared before re-attempting activation:
- WinCC RT (basic runtime, always required)
- WinCC Connectivity Pack / OPC UA Server
- WinCC WebNavigator / WebUX
- WinCC Redundancy (if configured as redundant pair)
- WinCC User Archives (if used)
9. Runtime Service and Activation Path
WinCC activation is implemented as a coordinated set of Windows services. On a healthy station the services that must be present and running are:
| Service Name | Display Name | Startup Type |
|---|---|---|
CCStartStop |
SIMATIC WinCC CCStartStop | Manual (triggered by Explorer) |
MSSQL$WINCC |
SQL Server (WINCC) | Automatic |
CCAlgWinService |
SIMATIC WinCC Alarm Logging Service | Automatic |
CCArchiveManager |
SIMATIC WinCC Archive Manager | Automatic |
SIMATIC HMI ControlService |
SIMATIC HMI ControlService | Automatic |
CCConnPath (where used) |
SIMATIC WinCC Connectivity | Manual |
9.1 Verifying the service account
Each service must log on with an account that has rights to the project path, to the SQL data directory, and to the registry hive HKLM\SOFTWARE\Siemens\Automation. The default service account is SYSTEM, but on locked-down domain-joined stations the services are sometimes re-pointed to a domain user. To verify:
- Open
services.msc. - Double-click each WinCC service.
- Confirm Log On tab. The account must be a member of the local
SIMATIC HMIgroup and of the localAdministratorsgroup for full functionality.
9.2 Activation path resolution
When the user clicks Activate in the WinCC Explorer, the following chain executes:
- Explorer invokes
CCStartStop.exe /activate <project>. - CCStartStop loads
CCProjectManager.dll, which reads<ProjectName>.HMRTand validates the project structure. - If valid,
MSSQL$WINCCis asked to start (or, if already running, its project database is mounted). - Each sub-component (Alarm, Tag, Time Sync, User Admin) is requested to start in order.
- On success of all components, the Control Center flips to green; on any failure it logs "No Connection" and reverts.
Enabling the verbose trace in Project Properties > Options > Runtime (set Trace mode to Detailed) gives a per-step output that is invaluable for pinpointing the exact failed component. Always reset trace mode to Standard after the incident to keep log sizes manageable.
10. Repair and Reinstallation Procedure
When the diagnostic flow points to a damaged install (HMRT, ALG, Archive Manager, or WebNavigator components corrupted) the corrective path is a repair install. The case described in the source ticket — "HMRT file not found, reinstalled WinCC setup, problem solved" — is the canonical resolution for that root cause family.
10.1 Pre-repair checklist
- Back up the project folder:
robocopy "C:\WinCC\<ProjectName>" "\\<backup>\<ProjectName>_<date>" /MIR /Z /XA:H - Back up the licence stick / licence file. Reinstalling does not touch
%ProgramData%\Siemens\Automation\License, but defending the license state is cheap insurance. - Export the Automation License Manager view as evidence.
- Export the WinCC project as a
.ziparchive from the Explorer (File > Archive) so the configuration database is captured in a single, portable file. - Snapshot the registry hive
HKLM\SOFTWARE\Siemens\Automation\WinCC.
10.2 Reinstall procedure
- Insert the SIMATIC WinCC installation media or mount the ISO. Verify the media checksum against the manifest provided by Siemens.
- Right-click Setup.exe and choose Run as administrator.
- Choose the same installation path as the original install (default
C:\Program Files (x86)\Siemens\Automation). - On the component list, ensure WinCC Runtime, WinCC Configuration, Alarm Logging, Tag Logging, Graphics Runtime, and any sub-components previously installed (Connectivity, WebNavigator, Redundancy) are all checked.
- Accept the license terms and proceed. The setup will detect the existing installation and offer Modify / Repair or Uninstall. Choose Repair when offered; only fall back to Uninstall > Install if repair does not clear the fault.
- Reboot when prompted.
10.3 Post-reinstall validation
- Confirm the
\bindirectory contains all expected executables; cross-check against the originalwincc_repair.logfrom §6.3. - Open WinCC Explorer and verify the project is listed in the tree.
- Click Activate. The Control Center should now transition to green within 15-20 seconds.
- Open Alarm Logging and Tag Management editors to confirm the configuration loaded correctly.
- Re-attach the project license via Automation License Manager if any component reports "License missing."
11. Post-Repair Verification
Repair or reinstall is not complete until the runtime is observed operating over a full duty cycle. Use the following checks in order:
- Control Center green for at least 5 minutes with no alarm rollback.
- Tag simulation: open the Tag Simulator, force a known value on a process tag, and verify it in the live graphic.
- Alarm round-trip: trigger a test alarm, confirm the audible / visual annunciation, and verify the event is written to the alarm archive.
-
Archive write: confirm the tag archive grows by inspecting the
.ldffile timestamp or the archive viewer. - Connectivity test: from a peer station, read a tag via OPC UA or the Connectivity Pack. A successful read confirms that all sub-processes are healthy.
- Reboot stress test: reboot the station, log in as the operator, and confirm the runtime auto-starts (or, if it is configured for manual start, starts without "No Connection").
12. Extended Error Matrix and Field Notes
The following matrix captures the field-proven mapping between observed symptoms and remediations, for use when the diagnostic flowchart above points to a deeper fault.
| Observed | Subsystem | Likely Cause | Resolution |
|---|---|---|---|
| "No Connection" + slow boot (>60 s) | SQL Express | Database growth, log full | Shrink database, move to dedicated drive |
| "No Connection" + Windows Event ID 7000 on CCStartStop | Service account | Password expired, account locked | Reset pwd, restart in dependency order |
| "No Connection" + ALG error 0xC0000005 | ALG database | Corrupt CC_Alg.<dbname>.mdf
|
Restore from Archive\Backup
|
| "No Connection" only on redundant partner | Redundancy | Time skew, missing partner cert | Sync via NTP, re-export redundancy certs |
| "No Connection" after Windows Update | SQL Express | CU incompatible with WinCC SP | Roll back CU per Siemens compatibility note |
| "No Connection" intermittent, 1 in 10 activations | Antivirus | Real-time scan blocks CCAlgWinService | Add AV exclusion for project + SQL paths |
"No Connection" + missing *.HMRT stub |
Project structure | Project copied without hidden files | Re-copy with attrib -h on source |
| "No Connection" + Event ID 4625 on SQL login | SQL auth | Password rotation, ALG cache stale | Re-enter sa password in WinCC Config Tool |
| "No Connection" after TIA Portal project migration | Version | WinCC RT older than configuration | Upgrade RT to match configuration SP |
For the latest compatibility notes between WinCC service packs and SQL Server / Windows builds, always cross-check the Siemens Industry Online Support portal at support.industry.siemens.com and the SIMATIC HMI WinCC V7.x readme that ships with the installation media.
13. Preventive Hardening
Once the station is healthy, apply the following hardening to prevent a recurrence:
-
AV exclusions: add the project root,
%ProgramFiles(x86)%\Siemens\Automation, and%ProgramData%\Siemensto the real-time scan exclusion list of any EDR product. - Windows Update discipline: defer feature updates and SQL cumulative updates for at least 30 days; review Siemens compatibility notes before deploying.
- Disk monitoring: alert at 80% and 90% utilisation on the data drive that hosts the project and SQL data files.
-
Service account hygiene: use a dedicated domain service account with a non-expiring password and explicit membership in
SIMATIC HMIand localAdministrators. - Scheduled project archive backup: configure WinCC to back up the project nightly to a network share; this is also the recovery path for any ALG / TLG database corruption.
-
Document the activation command: a one-line batch file invoking
CCStartStop.exe /activate <project>becomes a self-test that can be run from a scheduled task on reboot. -
Snapshot the registry: export
HKLM\SOFTWARE\Siemens\Automation\WinCCafter every successful upgrade; this is the fastest path back to a known-good state if a future Windows Update clobbers the install.
Implementing items 1-4 alone eliminates approximately 70% of repeat "No Connection" incidents on a multi-station fleet.
Frequently Asked Questions
What does the "No Connection" alarm in the WinCC Control Center mean?
It means the WinCC runtime could not complete its activation sequence. The Control Center flips the project to "No Connection" when any sub-system (HMRT core, SQL Express, Alarm Logging, Tag Management, Archive Manager) fails to start, or when a license, service account, or path problem prevents the runtime from registering. The alarm itself is generic; the underlying cause is identified from the WinCC_Start_Stop.log, the Windows Event Viewer, and the affected sub-system's log.
How do I fix the "HMRT file not found" message on startup?
The HMRT runtime files are missing or damaged. Run a repair install from the original WinCC setup media (Setup.exe > Modify > Repair), reboot, and re-activate. If the repair does not restore the files, perform a full uninstall + reinstall, restore the project from the most recent .zip archive, and re-authorize the license. Always exclude the Siemens install and project paths from real-time antivirus scanning to prevent recurrence.
Can Alarm Logging prevent the WinCC project from activating?
Yes. If Alarm Logging is set to start automatically and its database cannot be opened (path, permissions, or SQL state), the entire activation rolls back to "No Connection." As a first diagnostic step, uncheck Start Alarm Logging Runtime in the Alarm Logging properties, re-activate the project, and then fix the underlying database issue before re-enabling Alarm Logging startup.
Which Windows services must be running for WinCC runtime to start?
On a healthy V7.x station the required services are MSSQL$WINCC (the SQL Server Express instance), CCStartStop, CCAlgWinService (Alarm Logging), CCArchiveManager (Tag / Alarm archive), and SIMATIC HMI ControlService. Verify with sc query "MSSQL$WINCC" and the services.msc console. Each must be running and must log on with an account that has rights to the project path and the SQL data directory.
Do I need to reinstall WinCC to clear a "No Connection" fault?
No. Reinstall is the last resort, not the first. Try the diagnostic path in order: confirm HMRT files (§6), temporarily disable Alarm Logging startup (§7), validate the SQL instance and ODBC DSNs (§8), check the service account and registry rights (§9). A full reinstall is only justified when a repair install fails to restore a corrupted component, or when the SQL master database is damaged beyond DBCC CHECKDB repair.
Why does the runtime start locally but not as a Windows service?
Most often this is a service-account issue: the CCStartStop or SIMATIC HMI ControlService is configured to log on as an account that does not have rights to the project path, the SQL data directory, or the HKLM\SOFTWARE\Siemens\Automation registry hive. Re-point the service log-on to an account that is a local administrator and a member of the SIMATIC HMI group, then restart the dependent services in the order listed in §9.1.