WinCC Flexible 2008 Compatibility with TP 277 6" HMI Transfer

David Krause11 min read
SiemensTechnical ReferenceWinCC
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Overview

The SIMATIC TP 277 6" touch panel with order number 6AV6 643-0AA01-1AX0 is one of the most commonly deployed mid-range HMIs from the Siemens 270/277 panel generation. It uses WinCC Flexible (not WinCC Comfort / TIA Portal) as its configuration environment, which makes the engineering software selection non-trivial once the panel is already installed in the field. This reference resolves the recurring question: Is WinCC Flexible 2008 compatible with the TP 277 6"? and the secondary question: Can a PC Adapter (MPI/DP) cable be used to upload the project from the panel?

The short answer is: yes to both, but with specific constraints. WinCC Flexible 2008 (any SP from SP1 through SP5) supports the TP 277 family across all display sizes (4", 6", 8", 10"). The PC Adapter USB A2 (MPI/DP) supports point-to-point transfer when the panel's RS-422/DP port is configured for MPI or PROFIBUS, and backtransfer is enabled on the panel side and was enabled at compile time on the engineering side.

Note: WinCC Flexible is a legacy product line. WinCC Flexible 2008 SP5 was the final update before migration to TIA Portal / WinCC Comfort. New TP 277 panels shipped today still run the same firmware and remain compatible with WinCC Flexible 2008 SP5 for the operational life of the installed base.

2. Hardware Identification: TP 277 6" MLFB Decoding

Before resolving any compatibility question, confirm the panel order number (MLFB - Machine-Readable Product Code). The 6AV6 643-0AA01-1AX0 breakdown:

MLFB Field Value Meaning
6AV6 SIMATIC HMI prefix Siemens HMI product family
643 Device class TP 277 series (Touch Panel 277)
0AA01 Display variant 6" STN color display, 320 x 240 pixels
1 Front design Standard (gray)
AX0 Configuration suffix WinCC Flexible runtime, MPI/PROFIBUS DP interface, no PROFINET

The TP 277 6" ships with a single configuration interface: an RS-422 / MPI / PROFIBUS DP combined port (sub-D female, 9-pin). There is no Ethernet, no USB host, and no PROFINET on this part number. The 10" variant (6AV6 643-0BA01-1AX0) and 8" variant (6AV6 643-0AE01-1AX0) carry the same interface layout.

Note: Some TP 277 panels sold with the suffix -1AX1 include Ethernet and are programmed through WinCC Flexible 2008 + Ethernet. The 6AV6 643-0AA01-1AX0 variant does not have Ethernet; only serial / MPI / PROFIBUS DP transfer is supported.

3. WinCC Flexible Compatibility Matrix

WinCC Flexible engineering software supports a defined matrix of panels. The TP 277 series is supported from WinCC Flexible 2004 onward, with full functionality delivered in WinCC Flexible 2005 and later. The following matrix lists the relevant service packs:

Software Version TP 277 6" Support Image / Compile Runtime Version Generated
WinCC Flexible 2004 Yes (basic) Yes V10.x
WinCC Flexible 2005 Yes Yes V11.x
WinCC Flexible 2007 Yes Yes V11.x
WinCC Flexible 2008 SP1 Yes Yes V12.x
WinCC Flexible 2008 SP2 Yes Yes V12.x
WinCC Flexible 2008 SP3 Yes Yes V13.x
WinCC Flexible 2008 SP4 Yes Yes V13.x
WinCC Flexible 2008 SP5 Yes (recommended) Yes V13.x (final)

When the source panel project was originally compiled with WinCC Flexible 2005, you can still load it with WinCC Flexible 2008 SP5. When uploading (backtransferring), the project is restored in the same source-format version as it was compiled; WinCC Flexible 2008 SP5 can convert it on import.

3.1 Engineering PC Requirements (WinCC Flexible 2008 SP5)

  • OS: Windows XP Professional SP3, Windows Vista Business SP2, Windows 7 Professional/Ultimate 32-bit (SP1), Windows Server 2003 SP2 / 2008 R2
  • CPU: 1.6 GHz minimum, 2.4 GHz recommended
  • RAM: 1 GB minimum (32-bit OS); 2 GB recommended
  • Disk: 3 GB free for installation
  • Display: 1024 x 768 minimum, 1280 x 1024 recommended
Note: WinCC Flexible 2008 is not certified for Windows 10 or later. To run on Windows 10/11, use a virtual machine with a supported OS or migrate the panel to a TIA Portal-supported successor (KTP400 Comfort / TP700 Comfort) before Windows 10-only hardware is forced onto the engineering workstation.

4. PC Adapter (MPI/DP) Cable: Selection and Pinout

The PC Adapter couples the engineering PC to the TP 277 panel via MPI or PROFIBUS DP. Two cable generations are commonly encountered in the field:

MLFB PC Interface Supported OS Baud Rate (max) Status
6ES7 972-0CA23-0XA0 USB 1.1 / 2.0 XP / Vista / Win7 1.5 Mbps Discontinued, still functional
6ES7 972-0CB20-0XA0 USB 2.0 XP / Vista / Win7 / Win10* 12 Mbps Current production
6ES7 972-0CA34-0XA0 USB, TI USB chip XP / Win7 (legacy drivers) 1.5 Mbps Legacy
6GK1 571-1AA00 Serial RS-232 All 32-bit Windows 187.5 kbps Discontinued

* The 6ES7 972-0CB20-0XA0 PC Adapter USB A2 includes signed drivers for Windows 7, 8.1, and 10. Windows 10 is officially not supported by WinCC Flexible, but the cable drivers alone install cleanly on Windows 10 when used for STEP 7 or TIA Portal transfer.

4.1 Cable Pinout (RS-422 Side, to Panel)

The PC Adapter terminates in a sub-D 9-pin male connector that mates with the panel's RS-422 / MPI / DP port. The pinout is the standard PROFIBUS DP connector assignment:

Pin Signal Function
3 RxD/TxD-P (B line) Data positive
8 RxD/TxD-N (A line) Data negative
5 DGND Data ground / shield
6 +5V Bus termination power (limited current)
Warning: When connecting the PC Adapter directly to the panel (point-to-point), set the bus termination ON at the PC Adapter end (DIP switch on the adapter housing) and leave termination OFF in the panel. Two terminators on a point-to-point segment cause bus errors.

5. Transfer Options on TP 277

The TP 277 supports four transfer channels:

  1. Serial (point-to-point, RS-422 null-modem) - legacy, used with the serial PC/PPI cable or serial PC Adapter.
  2. MPI - 187.5 kbps default, address 1 by default on the panel.
  3. PROFIBUS DP - up to 12 Mbps, address 1 by default.
  4. Ethernet (only on -1AX1 suffix panels) - not applicable to 6AV6 643-0AA01-1AX0.

For the 6AV6 643-0AA01-1AX0 TP 277 6", options 1-3 are available. The most common field workflow is MPI at 187.5 kbps because that rate is universally supported by the PC Adapter USB regardless of driver age.

6. Engineering Software Configuration (WinCC Flexible)

6.1 Set the Transfer Channel

  1. Open the WinCC Flexible 2008 project.
  2. In the project tree, right-click the panel (TP 277 6") and select Properties.
  3. Open the Transfer tab.
  4. Set Channel 1 to MPI (or PROFIBUS DP, depending on the cable).
  5. Set the MPI/DP address of the panel (default 1).
  6. Set the baud rate (default 187.5 kbps).
  7. Check Enable transfer.

6.2 Set the PG/PC Interface on the Engineering PC

  1. Open Start > SIMATIC > PG/PC Interface (or Set PG/PC Interface from the WinCC Flexible toolbar).
  2. Set the access point S7ONLINE (or WinCC Flexible) to PC Adapter (MPI) or PC Adapter (PROFIBUS).
  3. Click Properties and verify the cable is detected. The COM port is virtualized by the adapter driver.
  4. Set the PC Adapter's MPI address (default 0).
  5. Set the transmission rate to 187.5 kbps.
  6. Confirm with OK and close the PG/PC Interface dialog.

7. Backtransfer / Upload Procedure

Unlike a download (compile > transfer > panel), the backtransfer retrieves the project source from the panel back to the engineering PC. This requires two enabling conditions.

Critical: Backtransfer retrieves the project source code only when (a) the original project was compiled with the Enable backtransfer option AND (b) the panel has the source stored on its flash. If the project was downloaded in binary-only mode (compressed compiled runtime only), the source cannot be retrieved.

7.1 Verify Backtransfer Is Enabled at Compile Time

  1. Open the WinCC Flexible project.
  2. Right-click the TP 277 6" device > Properties.
  3. Open the Transfer tab.
  4. Under Settings for the transfer, check Enable backtransfer.
  5. Recompile and re-download the project so the source is committed to the panel flash with the backtransfer flag set.

7.2 Verify Backtransfer Is Enabled on the Panel

  1. On the panel, enter Control Panel (via the corresponding button in the loader).
  2. Open OP Properties > Transfer.
  3. Check Enable backtransfer (this is the runtime-side switch).
  4. Press OK and confirm the panel restart prompt.

7.3 Execute the Upload from WinCC Flexible

  1. In WinCC Flexible 2008, select Project > Transfer > Backtransfer (menu path varies slightly between SP levels; in SP4/SP5 it is Online > Backtransfer).
  2. Select the channel (MPI or PROFIBUS) and confirm.
  3. The status dialog shows the panel discovered at MPI address 1, the connection establishing, the file listing, and the upload progress.
  4. Choose a destination folder on the PC for the recovered project source.
  5. Click Start. The transfer typically takes 30 s - 5 min depending on project size.

After upload, the recovered project opens in WinCC Flexible and can be edited, recompiled, and re-downloaded. Note that recovered projects sometimes carry a flag indicating the compilation environment; if the original was compiled with WinCC Flexible 2005, the recovered project opens in that version's UI elements unless converted.

8. Direct Download Procedure (Binary)

When no backtransfer is needed (the panel needs only a runtime image), use the standard download path:

  1. Connect the PC Adapter between the engineering PC and the panel MPI/DP port.
  2. Set the PG/PC interface as described in Section 6.2.
  3. On the panel, open Control Panel > Transfer. The panel enters transfer mode.
  4. In WinCC Flexible, select Project > Transfer > Transfer (or click the transfer toolbar icon).
  5. Select MPI/DP as the channel. WinCC Flexible scans MPI address 1 by default.
  6. Click Transfer. The compiled runtime (.fwx) is sent and the panel reboots automatically.

Typical transfer time: 30-90 s for a typical TP 277 6" project (1-4 MB runtime image) at 187.5 kbps. At 1.5 Mbps, this drops to under 10 s.

9. Troubleshooting Matrix

Symptom Likely Root Cause Verification Remedy
WinCC Flexible cannot find the panel Wrong PG/PC interface setting Open Set PG/PC Interface; verify PC Adapter is selected Re-select PC Adapter (MPI) and click Diagnostics
Connection timeout at 187.5 kbps Baud rate mismatch between panel and PC Check panel Control Panel > MPI/DP Properties Set both sides to 187.5 kbps (default)
Backtransfer returns no source Backtransfer disabled at compile time Inspect original project > Properties > Transfer Re-compile with Enable backtransfer and re-download
Backtransfer returns no source Panel flash lost source due to firmware update Check panel firmware version vs. original Re-create project from PDFs/screenshots
Error "Port already in use" Another tool (STEP 7, TIA Portal) holds COM port Close all SIMATIC applications Close STEP 7 / TIA Portal / HMI Pro tool; retry
Driver error after Windows 10 upgrade WinCC Flexible not certified for Win10 Check Device Manager > USB Serial Port Reinstall driver from Siemens DVD; use XP Mode VM
Transfer stops at 50% EMI or poor shield termination Check cable shield continuity Replace cable; ensure shield grounded at panel end
Panel restarts during transfer Insufficient 24 VDC supply current Measure 24 V at panel terminal during transfer Increase supply to 1.5x panel rated current

10. Verification Checklist

  1. Confirm panel MLFB is 6AV6 643-0AA01-1AX0 (read the side label or Control Panel > OP Properties).
  2. Confirm panel firmware version is compatible with the runtime image generated by the WinCC Flexible SP installed on the engineering PC.
  3. Confirm PG/PC interface is set to PC Adapter (MPI) at 187.5 kbps, address 0.
  4. Confirm panel MPI address is 1 (default) and baud rate is 187.5 kbps.
  5. Confirm PC Adapter USB A2 driver installs cleanly and the cable is detected in Device Manager.
  6. Confirm transfer is enabled in Control Panel > Transfer on the panel.
  7. Confirm backtransfer flag is set on both project (compile) and panel (runtime) when an upload is needed.
  8. After transfer, verify the panel boots into the project and tag connections to the PLC are healthy (look at the status indicators / connection diagnostics).

11. Migration Considerations

When the TP 277 6" reaches end of life or spares become scarce, migrate to:

  • KTP400 Comfort (4.3") with 6AV2 124-1DC01-0AX0 for the smallest footprint.
  • TP700 Comfort (7") with 6AV2 124-1GC01-0AX0 for a like-for-like 6"-class replacement with PROFINET.

Migration requires WinCC Comfort (TIA Portal) and a project converter. WinCC Flexible 2008 SP5 projects can be migrated directly through the TIA Portal V13 - V17 migration tool. The migration preserves screen layout, tag names, alarm classes, and most scripts, but PLC tag pointers may need re-binding if the underlying S7 program has changed.

12. Reference Documentation

Is WinCC Flexible 2008 compatible with the TP 277 6" (6AV6 643-0AA01-1AX0)?

Yes. WinCC Flexible 2008 SP1 through SP5 fully supports the TP 277 6". The latest patch, SP5, is recommended because it is the final update with the most current runtime (V13.x) and the broadest OS support.

Can I use a PC Adapter (MPI/DP) cable to upload a project from the TP 277 6"?

Yes, but only if the original project was compiled with Enable backtransfer selected and the panel has the source stored on its flash. Set PG/PC interface to PC Adapter (MPI) at 187.5 kbps, then use Project > Transfer > Backtransfer in WinCC Flexible.

What is the difference between transfer and backtransfer on the TP 277?

Transfer (download) sends a compiled runtime image from the PC to the panel. Backtransfer (upload) retrieves the project source from the panel back to the PC. Backtransfer requires the project to have been compiled with the backtransfer flag set, otherwise only the binary runtime is on the panel.

Which PC Adapter cable MLFB should I buy today for the TP 277 6"?

Use 6ES7 972-0CB20-0XA0 (PC Adapter USB A2). It supports 12 Mbps PROFIBUS, runs on Windows XP / 7 / 10 with signed drivers, and replaces both the older USB (6ES7 972-0CA23-0XA0) and the legacy serial (6GK1 571-1AA00) variants.

The TP 277 6" has no Ethernet. Does that limit me to serial transfer only?

No. The 6AV6 643-0AA01-1AX0 variant supports MPI (187.5 kbps to 12 Mbps) and PROFIBUS DP (up to 12 Mbps) on its RS-422/DP port. The PC Adapter USB A2 uses this port and supports both protocols; Ethernet is the only feature missing on this MLFB.