Problem Statement
When launching the WinCC Information Server 2014 SP3 web administration page on a Windows 10 Enterprise workstation and selecting the SQL Server Reporting Services (SSRS) instance Computer\WINCC, the browser or the configuration tool returns:
System.Runtime.InteropServices.COMException: The Network path was not found
at System.Runtime.InteropServices.Marshal.ThrowExceptionForHRInternal(Int32 errorCode)
at System.Management.ManagementObject.Get()
at Microsoft.SqlServer.Management.UI.VSIntegration.ObjectExplorer.SlcServerNodeConnection.OnAsyncExecWorkItem(Object obj)
at Microsoft.SqlServer.Management.UI.VSIntegration.ObjectExplorer.SlcServerNodeConnection.Connect()\code>
The exception originates from System.Management when the WinCC Information Server administration UI tries to enumerate the local WMI namespace \\Computer\root\Microsoft\SqlServer\ComputerManagement10. The same message appears on hosts that were previously able to load the setup web page but failed to bind to the SSRS instance, then regressed after a forced reboot triggered a Windows inbox-app update pass.
Environment and Affected Versions
| Component | Tested / Reported Version | Notes |
|---|---|---|
| Operating system | Windows 10 Enterprise 21H2/22H2 (LTSC/IoT variants observed) | Same error reproduced on Windows 10 Pro 21H2 with SQL Server 2019 Standard per Microsoft Q&A 1132685 |
| WinCC Information Server | 2014 SP3 (V7.4 SP3 generation), also reported on 2016 / 2017 / 2020 / RT Professional V20 | Always co-installed with SIMATIC Process Historian |
| Process Historian | 2014 SP3 or matching Information Server generation | Must be installed before Information Server; shared SQL Server instance |
| SQL Server / SSRS | SQL Server 2014 SP3 (Information Server 2014), SQL 2019 Standard (SSRS 2019) | SSRS must be running before IS configuration is opened |
| TIA Portal | V15.1 Professional with WinCC Professional add-on | Acts as the runtime / datasource for the Information Server archive |
| Internet Explorer | 11 (compatibility view forced for the IS administration URL) | Edge is not supported for the configuration web UI |
| .NET Framework | 4.7.2 minimum, 4.8 recommended | Required for IS administration COM interop |
Reference confirmation of the underlying SSRS connection path is documented in the Microsoft Q&A thread SSRS 2019 Report Configuration can't start up, which mirrors the same WMI/COMException returned by Report Manager when local security or WMI service state is broken.
Root Cause Analysis
The COMException 0x80070035 (The Network path was not found) returned by the WinCC Information Server administration web UI is the .NET projection of the Win32 error ERROR_NETNAME_DELETED. In a SIMATIC Information Server deployment it is almost always produced by one of four failure layers, listed in order of frequency seen in the field:
-
Stale SID / lost local profile. After a Windows 10 feature update or an inbox-app update pass (the "updating 5 apps" message reported in the case), local user SIDs that were used to install SIMATIC components may no longer resolve to a profile directory. WMI providers under
root\Microsoft\SqlServerare launched in the user context and fail to find the home directory, surfacing as a network-path error. -
WMI service dependency broken. The Information Server setup invokes WMI through
winmgmt. IfWinmgmtdepends onRPCSSwhich in turn depends on a stoppedDHCP Client,DNS Client, orTCP/IP NetBIOS Helper, the local\\Computer\rootconnection returnsERROR_NETNAME_DELETED. -
SSRS not yet bound to instance. Information Server 2014 SP3 calls SSRS via the Report Manager SOAP endpoint over
http://Computer:80/ReportServer_WINCC. If the Reporting Services instance is not started, the call falls back to a WMI query against the instance that does not yet exist, again returning the network-path error. -
Domain vs. workgroup SID history. Joining or leaving a Windows domain re-keys the local SAM database. SIMATIC components installed in one domain context carry SIDs that the new SAM cannot resolve, particularly for the
S-1-5-32-544Administrators group and the local SQL service accounts (SQLServerReportServerUser$Computer$MSSQLSERVER).
rsconfig.ini, the ReportServer database, and the WinCC project archive directories. A WinCC Information Server install in the same generation as a SIMATIC Process Historian cannot be repaired in-place without losing the PHI/IS security keys.Pre-Installation Prerequisites Checklist
To prevent the COMException at first launch, verify each item below before running setup.exe from the SIMATIC Information Server DVD or downloaded image.
| # | Check | Command / Location | Required value |
|---|---|---|---|
| 1 | Windows edition | winver |
Windows 10 Pro / Enterprise, 64-bit, full GUI, no Server Core |
| 2 | Local administrator | net user %USERNAME% |
Member of Administrators group |
| 3 | UAC | Group Policy | Run all administrators in Admin Approval Mode = Disabled for the install session, then re-enabled |
| 4 | Domain state | systeminfo | findstr /i "Domain" |
Machine must remain in Workgroup during install; join domain only after configuration succeeds |
| 5 | WMI service | sc qc winmgmt |
State: Running, Start: Automatic; dependencies include RPCSS
|
| 6 | RPCSS | sc qc rpcss |
Running |
| 7 | SSRS service | sc query "SQL Server Reporting Services" |
Running, type: own process |
| 8 | IIS / .NET | appwiz.cpl |
IIS 7.5+ with ASP.NET, .NET Extensibility, ISAPI Extensions, Windows Auth; .NET 4.7.2+ |
| 9 | Internet Explorer | iexplore -version |
11 only; add http://localhost/InformationServer to compatibility view and trusted sites |
| 10 | Process Historian prerequisite | services.msc |
SIMATIC Process Historian installed first, service running, archive created |
Step-by-Step Recovery Procedure
The field-proven recovery is identical to the resolution reported by the originating engineer: full OS reset, sequential install in a workgroup, configuration in IE, and only then join the domain. The expanded, repeatable version is documented below.
Step 1 — Rebuild the host
- Back up the WinCC project and the Process Historian archive directories under
C:\Program Files\Siemens\Automation\PH\Archiveand the IS templates underC:\Program Files\Siemens\Automation\IS\Templates. - Rebuild Windows 10 Enterprise from the OEM media and apply only critical/security updates.
- Disable Windows Update for the maintenance window:
net stop wuauservand set the service to Disabled temporarily. - Join the machine to a dedicated Workgroup (for example
WINCCWG). Do not add to the production AD domain. - Create the local install account (e.g.
WinCCAdmin) and add it to Administrators, Power Users, and the local SQL sysadmin group viasysadminmembership inSSMS.
Step 2 — Install SQL Server and Reporting Services
- Install SQL Server 2014 SP3 (or the generation matched to IS 2014 SP3) as a default instance
MSSQLSERVERwith mixed-mode authentication. Set a strongsapassword and the SQL service accounts to a local virtual account (NT AUTHORITY\SYSTEMfor the engine;NT SERVICE\ReportServerfor SSRS). - During the SQL setup, select Reporting Services — Native so that
ReportServerandReportServerTempDBdatabases are deployed. - Verify Report Manager opens at
http://localhost/Reportsbefore continuing. - If Report Manager also throws the COMException reported in Microsoft Q&A 1132685, reset WMI:
winmgmt /salvagerepository, thenwinmgmt /resetrepository, then reboot.
Step 3 — Install SIMATIC Process Historian
- Mount the Process Historian DVD/image that matches the WinCC Information Server generation (2014 SP3 ships with Process Historian 2014 SP3).
- Launch
Setup.exeas the localWinCCAdminand accept the SQL Server instance found in Step 2. - The installer registers the
SIMATIC Process Historianservice and creates thePHdatabase on the same SQL instance. - Confirm service state:
sc query "SIMATIC Process Historian"shows RUNNING.
Step 4 — Install SIMATIC Information Server
- Mount the Information Server media and run
Setup.exe. Choose Install Information Server and Information Server Web. - Point the setup to the SQL instance created in Step 2:
Computer\WINCC. The instance nameWINCCmust be entered in the dialog and validated by the setup. - During installation, the setup registers the IS web site under IIS at
http://localhost/InformationServerand creates theSIMATIC Information Serverservice. - Do not modify the IIS application pool identity; the default
ApplicationPoolIdentityplus theS-1-5-32-544local admin SID are required for the COM+ package SimaticInformationServer.
Step 5 — Configure Information Server in Internet Explorer
- Open Internet Explorer 11 as the
WinCCAdminaccount. VerifyIntranet Compatibility Modeis on for the localhost zone and the site is in Trusted Sites. - Navigate to
http://localhost/InformationServer. The setup page should load without the COMException. - Select the SQL Server instance
Computer\WINCC. The dropdown must populate via WMI; if it remains empty, return to Step 2 of the prerequisites and repair WMI. - Click Connect and complete the configuration wizard (define archive scope, select Process Historian datasource, set report repository path).
- Generate one test report from the bundled Microsoft Report template to confirm end-to-end binding.
Step 6 — Domain migration after verification
- Once the configuration succeeds in the workgroup, unjoin and re-join the host to the production AD domain.
- Re-add the local
WinCCAdmin(now a domain account) to the local Administrators and to the SQL sysadmin role. - Start the SIMATIC services in order:
SQL Server→SQL Server Reporting Services→SIMATIC Process Historian→SIMATIC Information Server. - Re-validate the configuration page and one end-to-end report. The COMException must not return.
Verification and Acceptance Tests
Run these checks immediately after each install step. They convert the COMException from "blocked at startup" into a deterministic pass/fail sequence.
| Check | Command / Action | Pass criterion |
|---|---|---|
| WMI local namespace |
wbemtest → \\Computer\root\default
|
Connection succeeds |
| SSRS WMI namespace |
wbemtest → \\Computer\root\Microsoft\SqlServer\ComputerManagement10
|
Connection succeeds, IS no longer returns COMException |
| Report Manager | Browser to http://localhost/Reports
|
200 OK, folder list visible |
| IS web home | Browser to http://localhost/InformationServer
|
Setup page renders |
| Instance picker | Dropdown SQL Server instance | Lists Computer\WINCC without empty result |
| Test report render | Select bundled Tag Overview → Generate | Returns a PDF / HTML within 60 s on a 50 k tag archive |
| Event log |
eventvwr → Application
|
No Event ID 7000, 7024, 10016 on the Information Server source |
Troubleshooting Matrix
| Symptom | Layer | Fix |
|---|---|---|
| COMException 0x80070035 right after install | SID / profile | Rebuild per Step 1 |
| Was working, regressed after Windows update | WMI repository |
winmgmt /resetrepository, reboot |
| Instance dropdown empty | SSRS not started | net start "SQL Server Reporting Services" |
| Setup page never loaded even pre-update | IIS pipeline | Reinstall ASP.NET role, run aspnet_regiis -i
|
| Works in workgroup, fails after join | SAM re-keying | Reinstall IS in the domain context |
| Event ID 10016 (DCOM access denied) | DCOM permissions | Grant S-1-5-32-544 Launch + Activation on the IS COM+ package |
| SSRS reports similar COMException per Microsoft Q&A 1132685 | SSRS account / WMI | Reinstall SSRS in the same generation as SQL Server, repair WMI |
Related SSRS Considerations
The same COMException is documented on SQL Server 2019 Standard / Windows 10 Pro 21H2 in Microsoft Q&A 1132685. When upgrading an Information Server 2014 host to Information Server 2020 / RT Professional V20, perform a side-by-side SSRS upgrade on a fresh SQL instance. Mixed-generation SSRS + IS without a co-shipped SQL Server patch level reintroduces the WMI provider mismatch. Also verify the architecture overview of the SIMATIC Information Server as part of the Information Server (RT Professional) documentation: it confirms that the server is built on SQL Server Reporting Services and that the SSRS + Process Historian components must be installed and reachable before the IS web layer is started.
Recurrence Prevention
- Pin the host to a Windows 10 Long-Term Servicing Channel edition if possible; consumer/feature-update branches repeatedly break the WMI repository on Information Server hosts.
- Defer Windows inbox-app updates via Group Policy: Configure Automatic Updates = 3 (auto-download, do not auto-install) so the "updating 5 apps" prompt cannot interrupt a live Information Server session.
- Create a weekly maintenance task that runs
winmgmt /salvagerepositoryand validates the SSRS service state. - Document the install order as a change-control record: OS → SQL → SSRS → PH → IS → Workgroup configuration → Domain join. Do not deviate.
- Keep the Information Server, Process Historian, and SQL Server at matched generations and patch levels.
Commissioning Checklist (one page)
1. Win10 Enterprise, workgroup WINCCWG
2. Local admin: WinCCAdmin, password in vault
3. SQL 2014 SP3 + SSRS native, instance MSSQLSERVER
4. http://localhost/Reports -> 200 OK
5. wbemtest -> \\Computer\root\default -> OK
6. wbemtest -> \\Computer\root\Microsoft\SqlServer\ComputerManagement10 -> OK
7. Install Process Historian 2014 SP3
8. Install Information Server 2014 SP3
9. http://localhost/InformationServer -> renders setup page
10. Select Computer\WINCC, complete wizard
11. Generate Tag Overview report -> success
12. Unjoin workgroup, join AD domain
13. Re-arm administrators, restart services SQL → SSRS → PH → IS
14. Re-run step 9, 10, 11 -> success
15. Hand over to operations
What causes COMException 0x80070035 "Network path was not found" in WinCC Information Server 2014 SP3?
The exception is produced when the Information Server administration page tries to connect to the local WMI namespace \\Computer\root\Microsoft\SqlServer\ComputerManagement10. The most frequent causes are a corrupt WMI repository after a Windows feature/inbox-app update, a local account SID that no longer matches a loaded profile, or an SSRS service that is stopped so the underlying instance object has not registered. Reset WMI with winmgmt /resetrepository, confirm the Reporting Services service is running, and verify the local admin profile directory exists.
Can I repair the Information Server in place instead of reinstalling the OS?
Rarely. The Information Server 2014 SP3 install registers SID-bound COM+ packages, IIS application pools, and SSRS security keys; a domain re-key or a Windows feature update that re-seeds SIDs makes an in-place repair unreliable. The field-proven fix is a fresh Windows 10 host, install in a workgroup, configure in IE, then join the domain — as documented in this article's Step 1 → 6.
Do I need to install Process Historian before Information Server?
Yes. Information Server reads its archive data from the SIMATIC Process Historian database. Setup blocks the Information Server install until a Process Historian of the same generation is detected. On WinCC Information Server 2014 SP3, install Process Historian 2014 SP3 first, then Information Server 2014 SP3, both pointing at the same SQL instance.
Which Windows edition and IE version is supported?
Windows 10 Pro or Enterprise, 64-bit, full GUI (Server Core and Education editions are not supported). Internet Explorer 11 is the only browser validated for the Information Server configuration web UI; add http://localhost/InformationServer to Compatibility View and the Trusted Sites zone. Microsoft Edge (Chromium) is not supported for configuration.
Why does the error appear only after joining the Active Directory domain?
Joining an AD domain re-keys the local SAM. SIMATIC install accounts, the SSRS service accounts (NT SERVICE\ReportServer), and the IS COM+ package ACLs were created in a workgroup context. After the join, the cached SIDs no longer authorize the same paths, and the WMI provider raises the COMException. Configure the host fully in a workgroup first, then unjoin/rejoin and re-arm the local administrators group and SQL sysadmin role before restarting services.