Overview
WinCC Professional in TIA Portal separates engineering licenses (ES) from runtime licenses (RT). A common field scenario is an engineer inheriting a multi-thousand-tag WinCC Professional project built in TIA V13 SP2 with only a 4096 power tag ES license available in TIA V17, and a need to engineer new screens, simulate the runtime, and rebuild the RT package for an on-site RT PC. This reference documents the license components required, the migration constraints triggered by tag count overflow, the path to local runtime simulation, and the cost-driven decisions between tag expansion and a multi-client RT bundle.
The underlying behavior is governed by the Siemens Automation License Manager (ALM), the WinCC Professional V17 license key model, and the TIA Portal V13 SP2 to V17 migration toolchain. The two URLs in the Additional Research section (Licensing STEP 7 and WinCC and Licensing (RT Professional)) are the canonical references for the license key model used in this article.
Problem Details: Tag Count Overflow and Missing RT Component
Two distinct license issues surface when an engineer attempts to take over a large WinCC Professional project:
- Power tag overflow. The project was authored against a 19,000+ tag power tag license. The engineer's available license is a WinCC Professional V17 with 4096 power tags. The engineering client will open the migrated project, but TIA Portal will flag the project as exceeding the licensed tag count during the migration step and will block the compile/download for runtime.
- Missing RT Professional component. WinCC Professional (the ES package) only authorizes engineering. To simulate the runtime locally on the engineering PC or to generate a loadable RT image for an on-site RT PC, an additional WinCC RT Professional license is required on the same machine. Without the RT license, the simulation launches but tag connections report unhealthy and alarms/trends do not update.
Root Cause: License Key Mismatch vs. Feature Mismatch
The two symptoms have different root causes and require different remediations:
| Symptom | Root Cause | Detected At |
|---|---|---|
| Migration warning: "Project requires more tags than licensed" | WinCC Professional V17 license key is 4096 power tags; project carries 19,000+ tags | Project migration V13 SP2 → V17; compile |
| RT simulation launches but tags show bad quality / "no connection" | WinCC RT Professional license key is missing on the engineering PC | RT start / WinCC Runtime Professional launcher |
| Unable to build RT image for on-site PC | WinCC RT Professional license key missing or insufficient client count | Compile → Generate RT file |
| OPC UA / OPC DA server on RT PC will not start | WinCC Runtime Professional license required for WinCC OPC UA server and OPC DA server on RT Professional | RT start with OPC server enabled |
Per the official Siemens documentation at Licensing STEP 7 and WinCC, every WinCC component on a given PC must have a corresponding valid license key in the Automation License Manager. The ES package (WinCC Professional) is independent from the RT package (WinCC RT Professional); they are licensed and counted separately.
License Model: ES Professional vs. RT Professional
| Component | License Name (TIA Portal V17) | Purpose | Tag Scope |
|---|---|---|---|
| ES Engineering | SIMATIC WinCC Professional | Engineering in TIA Portal: screens, HMI tags, alarms, archives, scripting, user administration | 4096 / 8192 / 16384 / 32768 / 65536 / 131072 power tags (tiered) |
| RT Runtime | SIMATIC WinCC Runtime Professional | Run the compiled project on a PC; includes local simulation mode on the ES PC | Power tag count must be ≥ ES count used in project |
| RT Clients | WinCC Runtime Professional Clients (1 / 3 / 10 / 30 / 100) | Concurrent thin client / web client connections to the RT server | Per concurrent client, not per tag |
| Options | WinCC Server / WinCC Redundancy / WinCC User Archives / WinCC Logging / WinCC OPC server | Server mode, redundancy, archives, OPC UA/DA server | Each option is an add-on key |
The RT Professional license packages per the official WinCC documentation (Licensing (RT Professional)) are available with 1, 3, 10, 30, and 100 clients. Client count refers to the maximum number of concurrent operator stations (WinCC Viewer, WebNavigator, or thin clients) that can attach to the RT server at one time.
Migration Path: TIA V13 SP2 → V17
The migration sequence must be planned because the license audit happens at compile:
- Install TIA Portal V17 with WinCC Professional on the engineering PC.
- Open Automation License Manager and confirm the V17 4096 power tag key is on the local license container (or a network license server reachable from the PC).
- Open the V13 SP2 project in TIA V17. The portal will run the migration wizard. Expect the project to migrate; the tag-count warning appears at this point but does not block opening.
- Edit freely. Adding screens, HMI tags, alarms, and trends is allowed even if the cumulative tag count exceeds the license; TIA Portal will not prevent the edit.
- At compile, the portal reports the tag count delta and refuses to generate the RT image until either (a) the licensed tag count is raised, or (b) the active power tag count in the project is reduced.
Resolution: Three Valid Options
Option A — Order an Expanded ES + RT License
Order a WinCC Professional V17 license with sufficient power tag count (e.g., 32768 or 65536) to cover the 19,000+ tag project plus headroom, and a matching WinCC RT Professional license with a client count sized to the on-site topology. This is the cleanest path but, as the source indicates, the price delta between 4096 and the higher tiers can be in the order of several thousand to ten-thousand euros/USD, depending on region and distributor.
Option B — Reduce Active Power Tag Count
Audit the project for unused HMI tags, orphaned DB references from the S7-1500/S7-300 side, and historical tags left over from prior revisions. Use the "Cross-references" tool in TIA Portal and the WinCC tag statistics export to identify candidates for removal. If the live tag count can be brought below 4096, the existing ES license is sufficient. This is rarely practical for a 19,000-tag project because most of those tags are typically live.
Option C — Split the Project (Multi-HMI Topology)
For very large plants, the SCADA layer is often split: an ES license stays at the original tier, and the project is partitioned so each Runtime Professional instance handles a tag subset. This requires WinCC Server licensing on top of the base RT Professional. This option is structural, not a workaround, and is documented in the RT Professional manual.
Enabling Local RT Simulation on the Engineering PC
To simulate the WinCC Professional runtime locally, the engineering PC must host a WinCC RT Professional installation with a valid license key. The launch sequence is:
- From the WinCC Professional project tree, right-click the HMI device → "Start Runtime".
- The WinCC Runtime Professional launcher invokes the local RT service. If the RT license key is absent, the launcher fails and reports a license error in the dialog.
- With a valid RT Professional key, the runtime starts, opens the start screen, and tag connections become healthy once the S7-1500/S7-300 PLC is reachable on the configured subnet.
If tags still report bad quality after the RT license is verified, the issue is connectivity, not licensing. Validate with the following checks:
- PLC is online and the protection level on the S7 CPU matches the configured HMI connection password.
- The HMI connection's S7 subnet is bound to a network adapter that is up (TIA Portal → Devices & Networks → Subnet properties).
- PG/PC interface on the engineering PC is set to the correct Ethernet adapter (Set PG/PC Interface, S7ONLINE → TCP/IP).
- No firewall rule blocks port 102 (S7 communication) between the engineering PC and the PLC.
Generating the RT File for the On-Site PC
The compiled WinCC Professional project is packaged as an RT image for transfer to the on-site Runtime PC. Procedure:
- In TIA Portal, select the HMI device (PC station running WinCC RT Professional).
- Compile → Software (rebuild all). Confirm no errors.
- On the project tree, select the HMI device → "Load to file system". Choose a target path on the engineering PC.
- The output is a complete RT image including the runtime database, alarm logs, and script files. Copy this folder to the on-site PC.
- On the on-site PC, run the generated loader executable. The on-site PC must have a WinCC RT Professional license with a client count that matches the deployed operator station count.
OPC Server Licensing on RT Professional
If the WinCC Professional project exposes data to third-party systems via OPC UA or OPC DA, the on-site RT PC requires the WinCC Runtime Professional license plus the WinCC OPC server option. Per the official documentation at Licensing (RT Professional) — OPC, the OPC server option is a separate license key on top of the base RT Professional license. Without this option, the OPC server service will not start and external OPC clients will receive no data.
Automation License Manager Workflow
All WinCC and STEP 7 Professional license keys are managed through the Siemens Automation License Manager (ALM), which is installed alongside TIA Portal. Practical procedures:
- Open ALM from the Windows Start menu (Siemens Automation → Automation License Manager).
- The left pane lists available license containers: local drive, USB stick, or network license server.
- To move a key: right-click the key → "Transfer". Confirm the destination container.
- To return a key: right-click the key → "Return". This frees the key to be re-assigned to another PC.
- For network licensing, the engineering PC points to the license server via "Connect to License Server" in ALM. The server must be reachable on TCP port 4410.
Detailed step-by-step procedures are documented at Licensing STEP 7 and WinCC.
Troubleshooting Matrix
| Error / Symptom | Likely Cause | Resolution |
|---|---|---|
| "License is missing or invalid" at RT start | WinCC RT Professional key absent on this PC | Install RT Professional key in ALM |
| Migration warning "Project requires more power tags than licensed" | ES license tier too low for current project | Reduce tag count or upgrade ES license |
| Compile fails: "Power tag count exceeded" | Active tag count > 4096 against 4096 ES license | Upgrade ES license to next tier or remove tags |
| Tags show bad quality during simulation | RT license missing OR PLC connectivity issue | Verify RT key, then verify S7 subnet and CPU protection |
| OPC server will not start | OPC server option key missing | Install WinCC OPC server option in ALM |
| Client connections refused | RT client count exhausted | Order additional client count package (1/3/10/30/100) |
| License key not recognized after TIA upgrade | License key is older than target TIA version | Upgrade license key via Siemens License Web Portal; keys are forward-versioned |
Verification Checklist
After applying the chosen resolution, verify the configuration end-to-end:
- ALM shows the V17 WinCC Professional key (ES) and the V17 WinCC RT Professional key (RT) on the correct PCs.
- TIA Portal opens the migrated V17 project without license warnings other than the tag count audit.
- Compile → Software (rebuild all) completes with no errors.
- Right-click the HMI device → "Start Runtime". The WinCC Runtime Professional launches and the start screen appears.
- All configured HMI tags show "Good" quality in the tag diagnostics (online → tag simulation → status).
- Alarms can be acknowledged, trends update, and scripts execute.
- "Load to file system" generates a complete RT image folder; copy to on-site PC and verify it loads.
- On-site RT PC runs the project with healthy tag connections; all configured clients connect up to the licensed client count.
Cost-Driven Decision Path
The decision between upgrading the ES license tier and splitting the project depends on the following field-calibrated tradeoffs:
- If the project is expected to grow (more tags per revision), the higher ES license tier amortizes over time.
- If the project is being retired or handed off, a single non-recurring engineering purchase is cheaper than restructuring the topology.
- Multi-client RT bundles (10/30/100) are economically favorable when the on-site SCADA already has many operator stations.
- Splitting into a WinCC Server topology adds WinCC Server + WinCC Client licensing; it is justified only at the largest scales.
Can I engineer a 19,000-tag WinCC Professional project with a 4096-tag license?
Yes for editing (screens, HMI tags, alarms, trends). No for compiling and generating a runtime image — TIA Portal enforces the licensed power tag count at compile time and will block the RT build until the count is reduced or the license is upgraded.
Do I need a separate WinCC RT Professional license to simulate the runtime locally?
Yes. The WinCC Professional ES license authorizes engineering only. To start the runtime on the engineering PC for simulation, or to build an RT image for an on-site PC, a WinCC RT Professional license must be present in the Automation License Manager on the PC that runs the runtime.
Are WinCC Professional V17 licenses backward compatible with TIA V13 SP2 projects?
Yes. A V17 license key is forward-versioned and will open, edit, and migrate a V13 SP2 project. A V13 SP2 license key will not open a V17 project.
What is the difference between a power tag and an HMI tag in WinCC Professional licensing?
A power tag is any HMI tag, array element, or DB-derived tag that participates in a runtime communication, alarm, or archive. TIA Portal counts these against the license tier. Internal calculation tags that do not communicate to a PLC are not counted as power tags.
Does the on-site Runtime PC need a STEP 7 Professional license to run the WinCC RT image?
No. The on-site PC requires the WinCC RT Professional license only. STEP 7 Professional is required on the engineering PC for PLC programming, not on the runtime PC.
What client count package should I order for a 5-operator-station plant?
Order the 10-client RT Professional package to cover the 5 operator stations plus a concurrent engineering client and a maintenance client. The 1 and 3-client packages are too small; the 30/100 packages are typically not cost-justified for this size.