WinCC V7 Redundant Server Licensing: Sizing Client Licenses
Siemens WinCC V7.0 SP1 is a SCADA system commonly deployed in redundant server / multi-client topologies for power, water, and process plants. The licensing model combines a per-tag PowerTags count, per-station Runtime (RT) authorization, optional Runtime and Configuration (RC) authorization, an explicit Client License (replacing the legacy RT-128 tag license), and a server-side Redundancy License that pairs with the WinCC Server option. The interaction of these components is the most common source of confusion when adding new client stations to an existing redundant pair.
1. WinCC V7 Redundancy Architecture Overview
A redundant WinCC V7 system consists of two server stations that mutually monitor each other. Process data is acquired on both servers in parallel; one server holds the active role (process server) while the partner holds the standby role. On standby failure of the active server, the partner takes over within the configured switchover time without operator intervention.
Each server hosts a complete project; data is exchanged via terminal bus and the WinCC Redundancy option, while clients connect to whichever server is currently the process server.
1.1 Logical Components
| Component | Role | License Surface |
|---|---|---|
| Server A | Redundant process server (active/standby) | WinCC Server, RT (8192), Redundancy, User Archives, PowerTags 8192 |
| Server B | Redundant partner server (active/standby) | WinCC Server, RT (8192), Redundancy, User Archives, PowerTags 8192 |
| Client 1..N | Operator / configuration station | WinCC Client (RC or RT variant) |
1.2 Why Redundancy Requires a Dedicated License
Although both servers run the same project and tag database, the runtime must explicitly know that the local instance is participating in redundancy. This is what the Redundancy License (sometimes referred to as the WinCC/Redundancy option) authorizes. Without it, the server runtime behaves as a standalone server even if the WinCC Redundancy option is configured in the project.
2. License Components Required per Station
The reference deployment in this article uses the following license stack, which represents a typical industrial-scale SCADA:
2.1 Server A and Server B (identical stacks)
| License | Function | Required Quantity |
|---|---|---|
| WinCC Server | Authorizes the station to act as a WinCC server (required to publish process data and accept client connections) | 1 per server |
| WinCC Runtime (RT) | Authorizes the local runtime to start, regardless of the number of clients | 1 per server (server-side RT is independent of client RT) |
| WinCC PowerTags 8192 | Allocates up to 8192 internal/external tags to the server's project | 1 per server (per-tag license) |
| WinCC Redundancy | Authorizes the redundant server pairing and switchover logic | 1 per server (both must hold the license) |
| WinCC User Archives | Authorizes the use of user archive data for setpoint storage, batch records, etc. | 1 per server |
2.2 Client Station
| License | Function | Required Quantity |
|---|---|---|
| WinCC Client License | Authorizes the client to start its own runtime and connect to a WinCC server | 1 per client station (single-seat) |
| (Legacy) WinCC RT 128 PowerTags | Pre-V7 client authorization based on a small per-client tag count | Replaced by Client License in V7; old RT-128 still valid for legacy deployments |
3. RT vs RC vs Client License: A Precise Comparison
Three authorization grades exist for V7 clients. Mis-selecting the grade is the most common licensing defect encountered during commissioning audits.
| Property | RT (Runtime) | RC (Runtime & Configuration) | Client License (V7) |
|---|---|---|---|
| Runtime mode on client | Yes | Yes | Yes |
| Configure server project remotely | No | Yes | No |
| Open WinCC Explorer locally | No | Yes | No |
| Edit graphics / scripts on the client | No | Yes | No |
| Tag count constraint on client | Implicit by license grade (e.g. RT 128, RT 256…) | Implicit by license grade | No per-client tag constraint — tags are read from the server |
| Typical use | Dedicated operator station | Engineer's HMI station used both to configure and to operate | Operator-only station in V7 (recommended) |
Selection rule for V7.0 SP1: If the new client is a pure operator station, install the Client License. If the new client must be able to edit the server project (download configuration changes, modify graphics, add tags, deploy), install the RC license instead. The legacy RT-128 tag-constrained license still operates against V7 servers when present on the client, but new deployments should use the Client License grade.
4. PowerTags Allocation: Where the Tag Count Lives
PowerTags is a per-tag licensing metric. A "PowerTag" is an internal or external process tag the project reads or writes, not an alarm or an archive tag. Alarm logging and archiving are not counted against the PowerTags limit.
4.1 Tag Counting Rules
- Counted: WinCC tags, structure tag elements, indirect tags (each pointer instance is a tag), and tags inside user archives when those tags are also process tags.
- Not counted: Archive tags, alarm tags, internal WinCC system tags, and connection-point tags.
- PowerTags is allocated at the server; the client sees all configured tags regardless of its own license grade when the Client License is used.
4.2 Verifying the Tag Count
Open the WinCC Explorer on the server, right-click "Tag Management" and choose "Statistics". The displayed total must be less than or equal to the licensed PowerTags count. In the reference deployment, 8192 PowerTags on each server is the project envelope; clients add no tag count to the server.
4.3 Upgrading PowerTags
Siemens ships PowerTags license upgrades as cumulative counts (e.g. 128, 256, 512, 1024, 2048, 4096, 8192, 16384, 65536). Licenses are additive on a given server. The 8192 count shown above is reached by stacking the standard package with cumulative upgrades. Verify the cumulative sum in the Automation License Manager on the server; do not trust the printed certificate alone.
5. How Many Clients Can Be Added?
The number of clients in a WinCC V7 server-client topology is limited by the WinCC Server license and by the project's Max Clients setting, not by the server's PowerTags count.
5.1 Default and Maximum Client Counts
| WinCC Server Variant | Concurrent Client Limit | Notes |
|---|---|---|
| WinCC Server (standard) | up to 32 clients | Default for V7.0 SP1 base install |
| WinCC Server (with client expansion option) | up to 64 clients | Requires additional "WinCC Server with 64 clients" upgrade license |
5.2 Single Client Reference Deployment
In the reference system described in the source, the project contains one client station. The system administrator can add up to 31 more clients (for a 32-client total) without acquiring additional server-side licenses, provided each new client installs a valid Client License (or RC license, depending on operator/engineering role). Each added client is a separate client PC with its own license key.
5.3 What Each New Client Requires
Adding a new operator-only client requires exactly one new authorization per client PC:
- WinCC Client License (preferred for V7.0 SP1) — a single license, not stacked on tag count.
- If a legacy RT-128 (or other RT-grade) license is already in stock, it is acceptable on the new client; it grants a tagged number of client-side subscriptions but functionally behaves as a client license for connection to a V7 server.
- If the new client must configure the server project, use the RC license instead of the Client License.
The new client does not require PowerTags license, a WinCC Server license, or a Redundancy license. Those are server-side only.
6. Redundancy License Behavior in Detail
The WinCC Redundancy license controls whether the WinCC runtime on a given server engages in the partner-monitoring protocol. Both partner servers must hold the license; a single-server deployment with a Redundancy license will simply run as a standalone server, with the redundancy logic dormant.
6.1 Required Server-Side Configuration
Beyond the license, the project must be configured for redundancy on each server:
- In WinCC Explorer: Redundancy > Server tab: set the partner server name and IP address.
- Set the watchdog / life-bit interval (default 5 s).
- Define the switchover time (default 30 s for slow networks, 5-10 s for switched gigabit).
- Enable or disable the User Archives redundancy sync if User Archives is licensed.
6.2 Switchover Time Versus Tag Count
Switchover time depends on the data volume to be reloaded into the partner server's picture cache and on network latency. With 8192 tags and a clean gigabit terminal bus, switchover typically completes in 15-25 seconds; with a saturated 100 Mbit link and high archive replay, 30-60 seconds is common. Plan operator handover procedures for the worst-case switchover.
7. License Server Configuration with Automation License Manager
WinCC V7.0 SP1 uses the Siemens Automation License Manager (ALM) and, beneath it, the Flexera FlexNet publisher for license storage and checkout. Each PC participating in WinCC runtime requires a functioning local ALM service.
7.1 Single-Node License Storage
On a standalone server, the ALM service runs on the server itself and licenses are stored on a local license key (USB dongle or hard-disk license file). This is the simplest configuration and is sufficient for the reference deployment.
7.2 Central / Redundant License Server Topology
For deployments that span multiple physical PCs and where license keys must be shared, Siemens supports a centralized or redundant license server. The license server itself does not need to be the WinCC server — it can be a dedicated machine running the ALM service.
When you have multiple ALM license servers configured as redundant, the same license key can be installed on both. The WinCC runtime will check out its license from whichever ALM server responds first; the second ALM server is a hot-standby. This protects against a license-server failure interrupting the SCADA. The principle is similar to other vendor license server pairs and follows the Flexera FlexNet redundant server model: each license server holds an independent copy of the same license key, and clients transparently fail over to the surviving server.
7.3 Verifying the License Server Is Reachable
- On the WinCC server, open the Automation License Manager.
- Confirm the connected license server hostname (or localhost) in the title bar.
- Open View > Licenses and verify each required WinCC license is present and not in "trial" state.
- Check the WinCC runtime startup log (
WinCC_Startup.login the project directory) for lines beginning withLIC:<date>showing each license being checked out.
8. Commissioning Checklist for a Redundant WinCC V7.0 SP1 System
Use this checklist to verify the licensing of a new redundant deployment before process values are routed through it.
- Each server has WinCC Server, RT, PowerTags 8192, Redundancy, and User Archives licenses present in the ALM.
- Both servers show identical tag counts in Tag Management > Statistics.
- Both servers connect to the same project directory (or mirror projects via redundancy-aware distribution).
- The Redundancy option is enabled in the project on both servers and the partner address is correct on each.
- At least one client has a Client License (or RC license) installed, with the correct server name configured in the client project.
- The redundant ALM license server is reachable from both WinCC servers and from each client (if clients use a remote ALM).
- Operator pictures, scripts, and alarm logging have been tested for switchover behavior — specifically, that the new client retains a working connection after the active server is forced to fail.
- WinCC startup logs on all stations contain no
LIC:ERRORentries and no "License not found" messages.
9. Common Licensing Errors and Their Meaning
| Symptom in Runtime | Likely Cause | Remediation |
|---|---|---|
| WinCC Runtime reports "No valid license found" on the server | WinCC Server or RT license missing | Install WinCC Server and WinCC Runtime licenses in ALM; confirm ALM service is running |
| Runtime starts but no tags update | PowerTags count exhausted | Add PowerTags upgrade license or remove unused tags from the project |
| Redundancy switchover never occurs; partner never visible | Redundancy license missing on the partner server | Install Redundancy license on both partner servers |
| Client shows "Server not available" or "Connection broken" | Client License missing on the client PC | Install Client License (or RC) on the client PC; restart WinCC Runtime |
| Client can run but cannot edit project | Client holds Client License but not RC | Replace the Client License with an RC license if the operator station needs configuration authority |
| License server connection timeout | ALM service on the license server is stopped, or network path to the license server is blocked | Restart the ALM service on the license server; check TCP port 21000 (FlexNet default) is open in both directions |
10. Migration Notes: From RT-128 to Client License
Sites upgrading from WinCC V6.x to V7.0 SP1 often have RT-128 client licenses already deployed. These are valid against V7 servers and may remain in service. The only difference is the tag count cap: an RT-128 client cannot subscribe to more than 128 tags as the "source of truth" for its local caches, while a Client License has no such cap and simply subscribes to whatever the server publishes.
For a retrofit where a client is being moved from operator-only to engineering, the operator-grade Client License should be replaced by an RC license, not stacked on top of it. Stacking two licenses on one client is wasteful and does not unlock additional capabilities.
11. Best Practices for License Management in a Redundant Plant
- Maintain a license inventory sheet per server, including the Automation License Manager screenshot at commissioning and at every change.
- Store physical license keys (USB dongles) in a labeled, ESD-safe enclosure attached to the server. Loss of a dongle stops the server's runtime.
- For hard-disk licenses, back up the license container file and the corresponding license certificate on a media separate from the server.
- When using a redundant ALM license server, install the same license keys on both ALM nodes and verify automatic failover by stopping one node during a scheduled outage.
- When increasing client count, the server-side cap is 32 (or 64 with the upgrade option). Plan hardware and licensing for that ceiling before the 30th client connects.
- Do not mix client license grades unnecessarily. Use Client License for operator stations, RC only on engineering stations, and never both on the same PC.
12. Frequently Asked Questions
How many clients can a WinCC V7.0 SP1 server support?
Up to 32 concurrent client connections per WinCC Server license by default. The WinCC Server with 64 clients upgrade extends this to 64. Each client PC requires its own Client License (or RC license) regardless of the server-side connection cap.
What licenses must be installed on a WinCC V7 client?
For a pure operator station, install the WinCC Client License only. If the client also needs to configure the server project remotely, install the WinCC RC (Runtime & Configuration) license instead. No PowerTags, Server, or Redundancy license is required on the client.
What is the difference between RT, RC, and Client License in WinCC V7?
RT is runtime-only. RC is runtime plus configuration authority (can edit the server project from the client). Client License is the V7 equivalent of a client-grade RT, with no per-client tag cap. The legacy RT-128 (or RT-256, RT-512, etc.) license grades are still valid on V7 clients.
Do both redundant WinCC servers need the Redundancy license?
Yes. Both partner servers must each hold a Redundancy license. A single Redundancy license on one server leaves the redundancy logic dormant on the partner and prevents automated switchover.
Can a redundant ALM license server contain duplicate license keys?
Yes. The two license servers in a redundant ALM pair are expected to hold identical license keys. The FlexNet-based ALM service arbitrates which server serves a given checkout, and clients transparently fail over if one ALM node becomes unreachable. The same principle applies to the WinCC server-side licenses (Server, RT, Redundancy, User Archives, PowerTags).
Does the client need its own PowerTags license?
No. In the V7 model, the client-side Client License has no per-client tag cap. All process tags are licensed at the server by the server's PowerTags license (e.g. 8192 in the reference deployment). The client simply subscribes to whichever tags the server publishes.
Can I add a Client License on top of an existing RT-128 client to extend tag count?
No. Stacking a Client License on an RT-128 client does not raise the tag cap. To remove the cap, retire the RT-128 license on that PC and replace it with a single Client License (or RC license if configuration authority is also required).