Yaskawa YRC1000 Cubic Interference Zones for Teach Mode Safety

Jason IP15 min read
RoboticsTutorial / How-toYaskawa
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Yaskawa Motoman YRC1000 controller exposes a powerful workspace-limiting feature called cubic interference that, when combined with the controller's Concurrent I/O ladder, lets you build positive safe-volume protection for Teach mode. The standard approach is to define one or more "safe" cubes where the TCP may roam freely during manual operation, then write ladder logic that monitors the cube-status bits and asserts a Hold or drops the Servo-On (SVON) request if the TCP leaves the authorized volume. This is the cleanest way to prevent an operator from jogging the arm into fixtures, fixtures-mounted tooling, light curtains, or other equipment that would otherwise be at risk during recovery from an emergency stop or program teach session.

This reference covers the full implementation path: enabling the cubic interference tables, defining the geometric cubes via the YRC1000 teach pendant, capturing the in-cube / out-of-cube status into the I/O image, building a Concurrent I/O ladder that interlocks Hold with the cube-out condition, and recovering motion with a dedicated reset path. It also covers when the Functional Safety Unit (FSU) option should be used instead of, or in addition to, software-based cube logic, and how to verify the system with a controlled commissioning test.

Cube interlock logic is a workspace management mechanism, not a Category 3/PL d safety function. If the requirement is a guarded safety zone with EU Machinery Directive / ISO 13849-1 compliance, you must use the YRC1000 FSU option together with hardware safety devices. See YRC1000 Coordinated and Multiple Robot Control Group Programming Module for advanced multi-robot cube management, and the YRC1000 Functional Safety Unit manual for certified stop categories.

Prerequisites

Before starting, confirm the following are in place on the YRC1000:

  • Controller: YRC1000 with firmware current to the maintenance release installed at your site. The cube-interference and Concurrent I/O features have been continuously supported across the YRC1000 product life; confirm the exact firmware label on the pendant Main Menu → System → Setup → Function.
  • Robot: GP180 (or any 6-axis / 7-axis Yaskawa manipulator that supports the cubic interference table; this includes the entire GP, MH, MS, and DX-generation series that the YRC1000 supports).
  • Option license: The Concurrent I/O function (sometimes labeled as "FD" in option management) must be enabled. If the ladder editor is not visible under Main Menu → Input/Output → Concurrent I/O, the option is not installed and must be activated by Yaskawa or an authorized integrator.
  • Pendant: Yaskawa Smart Pendant (PHG-style) with full programming access (Management or Editor security level). Operator-level access cannot modify cubes or ladder.
  • Backup: A full controller image backup via Main Menu → System → Setup → Function → Backup. Modifying ladder and cube tables should always be preceded by a verified backup.
  • Knowledge: Basic familiarity with Yaskawa INFORM II job syntax, the YRC1000 I/O image (B-relay, W-relay, D-relay numbering), and ladder logic. Engineers trained only on Siemens or Allen-Bradley should expect a small learning curve: Yaskawa ladder is bit/coil/contact based, but rung scan order and I/O numbering follow the YRC1000 conventions in the Concurrent I/O manual.

YRC1000 Workspace Safety Architecture

Three distinct layers contribute to teach-mode motion safety on a YRC1000 installation, and a well-engineered system uses all three in defense-in-depth:

  1. Cubic interference zones — Geometric boxes stored inside the controller that the motion planner consults every cycle. Each cube is defined by two diagonal corner coordinates (X, Y, Z) in the robot base frame, plus a class indicating whether motion into the cube is prohibited or required. Status bits reflect whether the TCP is currently inside, outside, or crossing the boundary.
  2. Concurrent I/O ladder — A user-editable ladder program scanned every controller cycle (default 8 ms) that can read status bits, B-relay contact states, and operator-panel inputs, and write to outputs and control flags such as Hold, Servo-On request, and alarm annunciation.
  3. Functional Safety Unit (FSU) — Optional hardware-based safety controller that monitors dedicated safety inputs (E-Stops, light curtains, safety-rated enable switches) and produces safety-rated outputs including safe torque off (STO) and safe stop. FSU is mandatory for any application where a software-only interlock would be insufficient for compliance.

The cube feature alone can be configured so that motion planning refuses to command joints into a prohibited cube. For a Teach-mode volume limiter, the typical configuration is to define a single large permitted cube (one required zone) and use the "out of cube" status bit in ladder to assert a hold whenever the TCP is at the boundary or beyond it. This gives the operator a positive envelope: movement is allowed as long as the TCP remains inside the cube, and any attempt to drive out triggers an immediate hold.

Step 1 — Define the Safe Cube on the Teach Pendant

  1. Set the pendant to Management or Editor security level and switch the controller to Teach mode.
  2. Navigate to Main Menu → Robot → Interference → Cubic Interference.
  3. Select an unused cube number (1 through 32, depending on option; the YRC1000 supports up to 32 simultaneous cubes).
  4. Choose Required Zone (the motion planner will refuse commands that leave this volume) rather than Prohibited Zone for the safe volume itself. Use Prohibited Zones for obstacles inside the safe volume if needed.
  5. Jog the robot to the first corner of the safe volume, capture the (X, Y, Z, Rx, Ry, Rz) pose with Modify → Record. Repeat for the diagonally opposite corner. The YRC1000 stores the cube as an axis-aligned bounding box; orientation is not used for the volume test.
  6. Set a Disable Bit address (optional) so the cube can be temporarily bypassed from a B-relay — useful for the operator "reset to recover" path described in Step 4.
  7. Save and exit. Verify the table entry via Display; the controller will plot the cube overlay on the position screen.
Always leave a safety margin (typically 25 to 50 mm) between the cube boundary and the nearest physical hazard. The cubic interference test fires at the boundary; mechanical backlash and pendant dead-man latency mean the TCP can transiently cross before the hold is honored.

Step 2 — Read Cube Status into the I/O Image

Every cubic interference zone exposes a set of dedicated status bits in the YRC1000 system area. The exact labels and indices are documented in the Concurrent I/O manual; the canonical bit group is typically referenced as B4A / B4B for cube "in" / "out" status. Confirm against the manual that ships with your firmware build, but the functional behavior is stable across releases:

Bit (typical) Name Meaning
B4A0B4A31 Cube In TCP is currently inside cube n
B4B0B4B31 Cube Out TCP is currently outside cube n
B4C0B4C31 Cube Boundary TCP is within the boundary tolerance of cube n (rising edge = crossing)
B4D0&hell…B4D31 Cube Active Cube n is enabled (Disable bit is OFF)

The "in" / "out" / "boundary" bits are updated every motion-control cycle and remain valid regardless of mode. They are read-only; your ladder consumes them as contacts.

Step 3 — Build the Concurrent I/O Ladder

Open Main Menu → Input/Output → Concurrent I/O. If the editor is not visible, the option is not licensed. Yaskawa's offline tool M-LADDER can edit the same file (.LAD) in a text or graphical format and the file can be transferred to the controller; the field report thread on Mladder notes that "Mladder shows the ladder graphically but the changes need to be made in text." Use whichever method your site supports, but always back up the original *.LAD file first.

The ladder below is a minimal, representative implementation for a single permitted safe cube. It is written in Yaskawa ladder text format. Adapt the bit addresses to the ones confirmed in your manual page.

|--[ B4A0 ]--+--[ B0100 ]--( OUT  B0200 )--|   ; "Inside Safe Cube" lamp
|            |
|            +--[ B0100 ]--( OUT  B0201 )--|   ; "Operator In Teach" latched
|
|--[ B4B0 ]--+--[ B0100 ]--+--[ B0210 ]--( OUT  B0030 )--|   ; Hold request when out-of-cube in teach
|            |              |
|            |              +--[ NOT B0210 ]--( OUT  B0031 )--|  ; alarm output
|
|--[ B0101 ]--+--( RST  B0201 )--|                          ; Operator reset pushbutton
|
|--[ B0100 ]--+--( RST  B0030 )--+--[ B4A0 ]--|              ; Allow reset only if TCP is back inside

Where:

  • B0100 = "Teach Mode Active" (system status input)
  • B0101 = "Operator Reset" pushbutton on the operator panel (debounced in PLC input)
  • B0030 = "Cube Out Hold" (wired to the controller's external Hold input via the user I/O mapping)
  • B0031 = "Cube Out Alarm" (annunciator + tower light)
  • B0200 / B0201 = internal status for HMI indication

The key behavior is the interlock at the bottom rung: the operator can press Reset, but the Hold will only clear if the TCP is back inside the cube. The Hold remains asserted the entire time the TCP is out-of-cube, so the operator cannot simply press Reset and continue jogging out of the safe volume. A small corrective jog brings the TCP back in, the "in" contact closes, and the reset takes effect on the next press.

Step 4 — Operator Reset and Controlled Recovery

The original question raised a concern: how does the operator recover once a hold has latched at the boundary? The answer is that the hold is conditional on the cube-out state, not latched. As long as the TCP remains outside, the hold reasserts on every cycle. The operator's only legal recovery path is to:

  1. Recognize the alarm condition (tower light, pendant message, or HMI pop-up).
  2. Use slow-step Teach jog (±5%, with the dead-man engaged) to move the TCP back into the safe cube.
  3. Once the "in" contact is true, press the dedicated Reset button on the operator panel.
  4. The hold clears, motion is restored, and the operator can continue in the authorized volume.
Do not wire a hardware bypass that allows the operator to disable the cube Disable bit from the operator panel. The Disable bit should be tied to a controlled, logged engineering action (Management security level required) so that any disabling of the safety envelope is auditable.

Servo-On vs. Hold — Choosing the Right Action

The discussion raises whether to drop the Servo-On (SVON) signal or just assert a Hold. The recommended approach for a Teach-mode volume limiter is Hold, not Servo-Off:

Method Effect Recovery Best Use
Hold (preferred) Motion stops, servo power remains on, brakes stay released, joints remain compliant under gravity-compensation Operator jogs back into the cube, presses reset, continues Teach-mode volume limits where the operator may need to back away from the boundary
Servo-Off (SVON cut) Servo power removed, brakes engage, arm can sag under gravity depending on axis Full servo-on sequence required; risk of arm drop and operator startle Severe collision avoidance where continued servo power is itself a hazard

Cutting SVON in a teach-only violation creates a worse recovery story than a Hold and is not necessary because the controller's motion planner already prevents motion into prohibited cubes at the trajectory level. Use SVON cut only when the application demands it (for example, when the entire safe volume is configured as a required zone and any motion outside is impossible by design).

Functional Safety Unit (FSU) Integration

  • Safe Torque Off (STO) on every axis with redundant hardware paths
  • Safe Stop 1 (SS1) and Safe Stop 2 (SS2) with monitored deceleration
  • Safe Operating Stop (SOS)
  • Safely-Limited Speed (SLS) with monitored speed feedback
  • Safely-Limited Position (SLP), which is the FSU-equivalent of a "cube" but with safety-rated monitoring

If your application requires the operator to enter the cell with the cell in automatic mode under reduced speed, or if compliance with ISO 10218-1 / ISO 13849-1 PL d is required, configure SLP zones in the FSU and wire the SLS to a 250 mm/s enable. The cube feature is then a soft envelope used during full-speed teaching, while the FSU is the hard envelope for all operational states.

Verification and Commissioning

After saving the ladder and cube definitions, perform a documented commissioning pass before allowing the operator on the cell:

  1. Backup: Save a controller image and a copy of the *.LAD file to the engineering workstation.
  2. Static test: With the robot in Teach and the TCP parked at the geometric center of the cube, verify the "in" bit is on and the hold output is off.
  3. Boundary drive test: At 5% Teach speed, drive the TCP slowly toward the cube boundary along +X, +Y, +Z, -X, -Y, -Z. The hold should engage within 25 mm of the boundary on each axis, and the operator should not be able to push through with the dead-man fully engaged.
  4. Reset test: With the hold engaged, press Reset. The hold should not clear because the TCP is still out. Drive back inside, press Reset, verify motion is restored.
  5. Mode test: Switch to Play/Remote. The cube interlock should not interfere with normal job execution unless the job itself is configured to honor it. If the job requires motion into a prohibited cube (for example, to pick a part stored outside the safe volume), the cube is correctly configured as "Prohibited" only for Teach-mode teaching, not for production paths. Confirm the cube class and the job's path coverage before running production.
  6. Power-cycle test: Cycle the controller main power. The ladder and cube table should reload from non-volatile storage. Verify the cube status bits are correct on the first scan.
  7. Alarm acknowledgment: Force the cube-out condition from the I/O monitor screen, confirm the alarm text appears on the pendant, confirm the tower light pattern matches the E-Stop matrix, and confirm the HMI displays the in-cube / out-of-cube status correctly.

Troubleshooting Matrix

Symptom Likely Cause Corrective Action
Cube menu not visible under Robot → Interference Cubic Interference option not installed or out of date Verify option license in System → Setup → Function → Option; contact Yaskawa if absent
Concurrent I/O editor not visible FD (Concurrent I/O) option not licensed Activate option; otherwise use a separate safety PLC for the interlock
Cube-out bit never clears even at robot home Cube coordinates entered in the wrong reference frame (e.g., user frame vs. base frame) Re-record the corners with the correct frame selected; verify on Display that the cube plot overlays the physical volume
Hold does not engage when TCP leaves the cube B4B address wrong for this firmware; the "out" bit is active-low on some releases Cross-check with the Concurrent I/O manual's bit map; add a NOT contact in ladder if inverted
Operator can jog out of cube on one axis only Cube was defined as a diagonal pair with one corner inside the desired safe volume; the controller treats it as a valid bounded region Re-measure corners; consider drawing the cube on paper and walking the operator through the boundary
Ladder changes don't take effect Ladder file not transferred; or pendant security is below Editor Verify file transfer; elevate to Editor security; cycle controller if required
Operator cannot reset even when TCP is back inside Reset input is not debounced, or the reset coil is wired to the wrong rung Add a one-shot rising-edge contact; verify the reset rung clears the Hold and not the latch for the alarm
Production job alarms on cube-out Job legitimately traverses a Prohibited zone Reclassify the zone as Required, or split the job path so the TCP stays inside the permitted volume

Best Practices Checklist

  • Always back up the controller image and the *.LAD file before editing the cube table or ladder.
  • Always keep one engineering-level Disable bit per cube, but never expose that bit to the operator panel.
  • Use Hold, not Servo-Off, for teach-mode volume violations to preserve controlled recovery.
  • Deploy the FSU option for any application with regulatory safety requirements; the cube feature complements but does not replace FSU.
  • Document the cube geometry on the cell layout drawing and in the operator manual so the team can verify boundary alignment over time.
  • Schedule a quarterly boundary test as part of preventive maintenance; mechanical drift or fixture changes can invalidate a previously verified cube.
  • If you have multiple robots sharing a workspace (for example an ArcWorld 6200/6300/6400 cell as described in the YRC1000 Coordinated and Multiple Robot Control Group Programming Module), consider the coordinated cube tables and shared interference zones, and re-verify the boundary logic with both robots energized.

FAQ

How do I restrict Teach mode movement to a safe cube on a YRC1000?

Define a Required Zone cubic interference under Main Menu → Robot → Interference → Cubic Interference, then read the cube "in" / "out" status bits (typically the B4A/B4B group) into a Concurrent I/O ladder that asserts the controller's external Hold input whenever the "out" bit is true in Teach mode. The operator can jog freely inside the cube and is held at the boundary.

Do I need the Concurrent I/O option to use cube interlock logic?

Yes, for the recommended Hold-based recovery. The cubic interference table itself prevents trajectory-level motion into prohibited cubes, but the "out-of-cube" status-to-Hold mapping requires user ladder. If Concurrent I/O is not licensed, the cube will still block motion into Prohibited Zones at the planner level, but you cannot implement a permissive Teach-mode safe-volume behavior.

Should I cut the Servo-On signal or assert Hold when the operator exits the cube?

Assert Hold. Cutting SVON drops servo power and engages brakes, which can cause arm sag on vertically-mounted axes and forces a full servo-on sequence to recover. Hold keeps the arm compliant under gravity-compensation, lets the operator jog back inside the cube at low speed, and clears the moment the operator presses Reset while the TCP is in-cube.

How do I let the operator recover from a latched cube-out hold?

Wire the Hold so it self-clears only when the cube "in" contact closes. The operator dead-man jogs the TCP back into the safe volume at 5% speed, then presses a dedicated Reset button on the operator panel. The reset coil is interlocked with the "in" bit, so the operator cannot clear the hold from outside the cube.

Is the cube feature the same as the Functional Safety Unit (FSU)?

No. Cube interference is a workspace management feature enforced by the motion planner and available to user ladder. The FSU is a certified safety controller that implements ISO 13849-1 PL d / SIL 2 functions such as STO, SS1, SS2, SLS, and SLP. Use cube interlock for software envelopes and operator guidance; use FSU for any safety-rated stop, speed, or position limit required by your risk assessment.

Back to blog