Backing Up a Siemens LOGO! 230RC (0BA5) Program: Step-by-Step Field Procedure
The Siemens LOGO! 230RC with order number 6ED1052-1FB00-0BA5 belongs to the 0BA5 hardware generation and is one of the most deployed micro-PLCs in light commercial and residential automation. Despite the device's age, the upload procedure still depends on a small set of specific tools: LOGO!Soft Comfort V6 or V7, the 6ED1057-1AA01-0BA0 USB PC cable, and a manual transfer-mode keystroke sequence on the 0BA5 base module. This article walks through the complete backup procedure, identifies the successor (0BA6) part number, and provides a troubleshooting matrix for the most common field failures.
1. Hardware Identification: Confirming the 0BA5 Variant
Before launching any software, confirm the exact MLFB printed on the side label of the LOGO! base module. The Siemens naming convention for the 230RC is:
| MLFB | Generation | Description |
|---|---|---|
| 6ED1052-1FB00-0BA5 | 0BA5 | LOGO! 230RC, 8 DI / 4 DO relay, 115–230 V AC supply, no display variant |
| 6ED1052-1FB00-0BA6 | 0BA6 | LOGO! 230RC, direct successor, 8 DI / 4 DO relay, identical footprint |
| 6ED1052-1FB00-0BA7 | 0BA7 | LOGO! 230RC, 8 DI / 4 DO relay, expanded function block set |
| 6ED1052-1FB00-0BA8 | 0BA8 | LOGO! 230RC, 8 DI / 4 DO relay, integrated Ethernet |
The 230RC designation decodes as 230 V AC supply, Relay outputs, C-variant. The "R" suffix indicates electromechanical relay outputs (Q1–Q4 rated 8 A resistive / 2 A inductive at 230 V AC). The "C" distinguishes the AC-powered variant from the 24 V DC versions (12/24RC, 24RCo, etc.).
Locate the order number on the right-hand side label of the device, in the format 6ED1052-1FB00-0BAx. The trailing -0BAx is the critical field: 0BA5 must be selected in LOGO!Soft Comfort as "0BA5 Standard" before uploading, otherwise the software rejects the connection.
2. Prerequisites: Software, Cable, and Host PC
Three components are required to back up a 0BA5 program:
- LOGO!Soft Comfort V7 (or V6.x) installed on a Windows PC with administrator rights.
-
LOGO! PC USB cable, MLFB
6ED1057-1AA01-0BA0. This cable integrates a USB-to-serial converter and exposes a virtual COM port to LOGO!Soft Comfort. The older6ED1057-1CA00-0BA0serial cable is a fallback for pre-USB hosts but requires a physical COM port. - The 0BA5 base module powered and wired with at least L1 / N mains supply (115–230 V AC, 50/60 Hz). The CPU does not need to be in RUN; the upload works in STOP or RUN.
| Item | MLFB / Version | Function |
|---|---|---|
| LOGO!Soft Comfort V7.0 | 6ED1058-0BA02-0YA1 (DVD) or download | Programming, upload, and online diagnostics |
| LOGO! PC USB cable | 6ED1057-1AA01-0BA0 | USB to LOGO! interface adapter (≈ 2.5 m) |
| LOGO! 230RC base unit | 6ED1052-1FB00-0BA5 | Target device |
3. Installing LOGO!Soft Comfort V7
LOGO!Soft Comfort V7 supports all generations from 0BA5 through 0BA7 on a single install. V8.x added 0BA8 Ethernet support but retained backward compatibility for older targets.
- Insert the LOGO!Soft Comfort V7 DVD or run the downloaded installer as Administrator. The default install path is
C:\Program Files\Siemens\LOGOComfort_V7\. - Accept the license agreement and choose Typical installation. This installs the FBD/LAD editor, the simulator, the online help, and the USB cable driver package.
- If the installer does not auto-install the USB cable driver (6ED1057-1AA01-0BA0), the driver package is located at
C:\Program Files\Siemens\LOGOComfort_V7\Drivers\. Point Windows Device Manager to this folder when prompted. - Reboot the PC. After reboot, confirm the cable is detected by plugging it in and checking Device Manager → Ports (COM & LPT). The cable should appear as
USB Serial Port (COMx)where x is the assigned COM number (typically COM3–COM6).
logo_usb_driver.inf in the LOGO!Soft Comfort installation folder. If the cable is still not recognized, try a different USB port — front-panel headers on industrial PCs often have insufficient power for the cable's onboard electronics.4. Wiring the 6ED1057-1AA01-0BA0 USB Cable
The 6ED1057-1AA01-0BA0 cable has two ends:
- USB-A: connects to the host PC.
- RJ12 (6P6C) modular plug: mates with the recessed serial socket behind the small cover on the front of the LOGO! base module.
To connect:
- Power the LOGO! 230RC at L1/N. The unit does not need to be in RUN.
- Flip open the small plastic cover on the front face of the LOGO! (between the display and the terminal block). The serial socket sits underneath.
- Insert the RJ12 plug of the 6ED1057-1AA01-0BA0 cable. It is keyed; do not force it. A positive click indicates a proper mate.
- Plug the USB-A end into the PC. The PC should emit the standard USB-enumeration chime, and Device Manager should show a new COM port.
5. Putting the 0BA5 into PC <-> LOGO! Transfer Mode
Unlike 0BA7 and 0BA8, the 0BA5 does not auto-detect the PC cable. The user must manually toggle the device into transfer mode. The procedure depends on whether the unit has a display (LOGO! 230RC with display, MLFB suffix differs) or is a display-less variant:
5.1 For 0BA5 units with integrated display (LOGO! 230RC, 6ED1052-1FB08-0BA5)
- On the LOGO! front panel, press ESC to enter the main menu.
- Navigate with the ↑ / ↓ keys to Start.
- Press OK.
- Select PC <-> LOGO! using the cursor keys.
- Press OK. The display now shows
PC <-> LOGO!with a status icon. The unit is in transfer mode.
5.2 For 0BA5 units without integrated display (the source MLFB 6ED1052-1FB00-0BA5, the "R" model)
The display-less variant has no on-screen menu. Transfer must be initiated from the host PC in LOGO!Soft Comfort:
- Open LOGO!Soft Comfort V7.
- Click Tools → Transfer → PC → LOGO! (or simply press the Upload button on the toolbar — the blue arrow pointing toward the PC).
- LOGO!Soft Comfort will issue a transfer command. The 0BA5 will respond by exiting RUN and entering STOP with the transfer active. The on-module LEDs (RUN green, STOP red) will indicate the state change.
6. Uploading the Program: Step-by-Step Procedure
Once the cable is connected and the COM port is visible:
- Launch LOGO!Soft Comfort V7.
- Click File → New (or press Ctrl+N). A blank FBD or LAD project opens.
- In the device-selection dialog, choose LOGO! 0BA5 Standard. This is critical — selecting "0BA6" or "0BA7" will prevent the upload from completing because the firmware versions are incompatible.
- From the menu, click LOGO! → PC (Upload). The keyboard shortcut is Ctrl+U in V7. The on-screen icon is a blue arrow pointing left (from LOGO! to PC).
- Select the COM port assigned to the 6ED1057-1AA01-0BA0 cable (e.g., COM3). If unsure, check Device Manager.
- Click Test to verify the cable connection. A green status indicator confirms communication. A red indicator means the LOGO! is not in transfer mode or the COM port is wrong.
- Click Upload. The progress bar shows the transfer. A typical 0BA5 program (40–60 function blocks) uploads in 5–15 seconds.
- When the upload completes, the FBD/LAD program appears in the editor window. Save the project immediately as a
.lscfile (LOGO!Soft Comfort project) and a.lmaexport (LOGO! program module archive) for redundancy.
7. Saving the Backup in Multiple Formats
A single .lsc file is the master copy, but storing additional formats protects against version-mismatch issues if the backup must be reloaded onto a different generation:
| Format | File Extension | Use Case |
|---|---|---|
| LOGO!Soft Comfort project | .lsc | Editable source, version-specific |
| LOGO! program module image | .lma | Direct copy to physical program module / memory card |
| PDF schematic | Paper archive for documentation | |
| Diagrama FBD / LAD printout | .pdf / .png | Hand-off to maintenance |
To export the .lma program-module image: File → Export → LOGO! Program Module File (.lma). This format is required if you intend to clone the program onto a spare 0BA5 (or compatible 0BA6) without going through the upload-over-cable path.
8. Verifying the Backup
A backup that uploads but does not match the running process is a liability. Verify integrity with these checks:
-
Function-block count parity. Open the original LOGO! menu (on a display-equipped unit): ESC → Program → Edit. Note the function-block count. Cross-check the count in the uploaded
.lscby selecting all blocks in the editor (Ctrl+A) and reading the status bar. - Online compare. In LOGO!Soft Comfort, click LOGO! → Compare with Online. Any difference highlights in red.
- Simulator run. Open the integrated simulator (Tools → Simulator) and step through the logic with simulated inputs. The simulator runs the same compiled code that the physical LOGO! runs, so behavior must match.
-
Cyclic reload test. If a spare 0BA5 (or 0BA6) is available, download the
.lscto it via LOGO! → PC (Download) and let it run for at least one full operating cycle of the controlled process. The original may be left in place as a hot spare.
9. Troubleshooting Matrix: Common Upload Failures
| Symptom | Likely Cause | Remediation |
|---|---|---|
| LOGO!Soft Comfort does not list 0BA5 in device selection | Wrong project type or older V5.x install | Install V7 explicitly. In File → Properties, verify the target device is "LOGO! 0BA5 Standard". |
| Cable detected, but upload returns "No connection" | 0BA5 not in transfer mode, or wrong COM port | On display-equipped units, manually enter PC <-> LOGO! mode. Verify COM port in Device Manager matches the one selected in LOGO!Soft Comfort. |
| Upload starts, then aborts with CRC error | EMI on the cable, bad USB port, or insufficient shield bonding | Re-seat the RJ12 plug. Move the USB end to a rear-port directly on the motherboard. Avoid USB hubs. |
| Driver not recognized on Windows 7 | Driver signature or USB power issue | Reinstall driver from C:\Program Files\Siemens\LOGOComfort_V7\Drivers\. Try a different USB port. Disable USB selective suspend in Windows power options. |
| Display-less 0BA5 unresponsive to upload | Firmware lock from previous session | Power-cycle the 0BA5. Wait 5 s with power removed. Re-apply power and retry upload within 10 s of power-up. |
| Uploaded program appears empty in editor | Password protection on the source program | The source LOGO! has a password set. The program is uploaded but the function blocks are scrambled. Request the password from the original programmer. |
| Driver install fails on Windows 10/11 | Unsigned legacy driver | Boot Windows in "Disable driver signature enforcement" mode, or use the V8.x driver package which is signed. |
10. Migrating from 0BA5 to 0BA6 (Direct Successor)
The 6ED1052-1FB00-0BA6 is the direct successor to the 0BA5. It shares the same footprint, terminal layout, and I/O assignment, making it a drop-in replacement. However, two differences must be accounted for:
- Newer function-block set. The 0BA6 firmware introduces additional blocks (e.g., astronomical timer, additional analog math). Programs uploaded from a 0BA5 to 0BA6 will run, but a 0BA6 program cannot always be downgraded to a 0BA5.
- LOGO!Soft Comfort device selection. When targeting a 0BA6, select LOGO! 0BA6 Standard in the project properties before downloading. Selecting 0BA5 by mistake will succeed in the upload but the program will use only the smaller 0BA5 instruction subset.
To perform the hardware swap after backing up the 0BA5 program:
- Power down the system. Label every wire on the 0BA5.
- Remove the 0BA5 and install the 0BA6. The terminal screws and pin-out are identical.
- Re-apply power. The 0BA6 will boot in STOP with all outputs off.
- Open the backup
.lscfile in LOGO!Soft Comfort V7, change the target device to 0BA6 Standard, and download via the 6ED1057-1AA01-0BA0 cable. - Toggle the 0BA6 to RUN. Verify I/O wiring by forcing inputs from LOGO!Soft Comfort (Tools → Online → Force Inputs).
11. Compatibility Matrix: Software and Firmware
| LOGO!Soft Comfort Version | Supported Generations | 0BA5 Upload Support |
|---|---|---|
| V5.x | 0BA4, 0BA5 | Yes |
| V6.x | 0BA4, 0BA5, 0BA6 | Yes |
| V7.0 / V7.x | 0BA5, 0BA6, 0BA7 | Yes (recommended for 0BA5) |
| V8.0 / V8.x | 0BA6, 0BA7, 0BA8 | Yes (read-only on some 8.x builds) |
For a 0BA5 target, LOGO!Soft Comfort V7 is the recommended version: it supports the upload, it recognizes the 6ED1057-1AA01-0BA0 USB cable out of the box, and it preserves the option to upgrade the target hardware to 0BA6 or 0BA7 without reformatting the program.
12. Frequently Asked Questions
What software do I need to back up a LOGO! 230RC 0BA5?
Use LOGO!Soft Comfort V7.0 (or V6.x). Earlier V5.x versions also work, but V7 is the most stable release with 0BA5 support and full read/write access.
Which cable connects a LOGO! 230RC 0BA5 to a PC?
Use the 6ED1057-1AA01-0BA0 USB PC cable. It terminates in an RJ12 modular plug at the LOGO! end and USB-A at the PC end. The older 6ED1057-1CA00-0BA0 serial cable is a fallback for hosts without USB.
Can a 0BA6 (6ED1052-1FB00-0BA6) directly replace a 0BA5 (6ED1052-1FB00-0BA5)?
Yes — the 0BA6 is a pin-compatible drop-in replacement with identical footprint, terminal layout, and 8 DI / 4 DO relay configuration. Programs uploaded from a 0BA5 run on a 0BA6 after re-selecting the target device in LOGO!Soft Comfort.
Why does my LOGO!Soft Comfort not show "0BA5" in the device list?
The device list is filtered by project type. Open a New project and select LOGO! 0BA5 Standard in the device-selection dialog. If the option is missing, your install is V8.x with restricted legacy support — downgrade to V7.0.
How do I put a display-less 0BA5 into transfer mode?
Display-less 0BA5 units have no front-panel menu. Transfer is initiated from the host: connect the 6ED1057-1AA01-0BA0 cable, open LOGO!Soft Comfort, and click LOGO! → PC (Upload). Power-cycle the 0BA5 if the first attempt fails.
Where is the official Siemens LOGO! manual?
The LOGO! installation and programming manual is published on Siemens Industry Online Support: SIMATIC LOGO! Manual (PDF). This covers wiring, program module handling, and transfer-mode operation for 0BA5 through 0BA6.