S7-400 EXTF and BUS2F LED: PROFIBUS DP Fault Diagnostics

David Krause15 min read
PLC HardwareSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

After a power supply replacement on a SIMATIC S7-400 automation system, the field engineer observed a stable RUN state on the CPU 412-2DP but two non-fatal indicators remained active: the EXTF (external fault) LED was continuously lit and the BUS2F (bus fault on the second interface) LED was blinking. The diagnostics buffer of the CPU reported an I/O access error when writing to the process image of the output modules, specifically a P-area word access at access address 544, originating from FC3 and tied to module address 238. The I/O devices were all present on the PROFIBUS segment and powered, but the CPU could not see them as reachable DP slaves.

This article consolidates the diagnostic path, the root-cause analysis, and the field-proven recovery procedure that allowed the controller to come back into production without a CPU replacement.

Hardware Configuration and Affected Components

Component Order Number (MLFB) Function
PS407 4A (defective) 6ES7407-0DA02-0AA0 4 A output, replaced due to failure
PS407 10A (replacement) 6ES7407-0KA02-0AA0 10 A redundant-margin PSU
CPU 412-2DP 6ES7412-2EK06-0AB0 (typical) MPI/DP + dedicated DP port
HMI panel MSystem / Micro Innovation GFO-57SQD-002 Connected via MPI network
DP slaves (I/O) ET200M / ET200S family Distributed I/O on PROFIBUS DP

The PS407 10A is mechanically and electrically compatible with the PS407 4A slot in the S7-400 rack. Either PSU can deliver 5 V DC and 24 V DC backplane voltages; the 10 A version simply has headroom for a fully populated rack with high-consumption I/O modules such as the SM 321 digital input (6ES7321-1BL00-0AA0) or SM 332 analog output (6ES7332-5HF00-0AB0). No hardware configuration change is required when migrating from 4 A to 10 A other than updating the part number in HW Config so the diagnostics buffer does not flag a "module type mismatch".

LED Status Interpretation on the S7-400 CPU

LED Color State in this fault Meaning
RUN Green Solid ON CPU in RUN; user program executing
STOP Yellow OFF CPU not in STOP
SF Red OFF No group error; usually paired with EXTF or INTF
BF / BUS1F Red OFF First interface OK
BUS2F Red Blinking Bus fault on second (DP) interface; slaves not all reachable
EXTF Red Solid ON External fault: I/O access error, redundancy loss, or battery
INTF Red OFF No internal programming or runtime error
FRCE Yellow OFF No force operations active
MAINT Yellow OFF No maintenance demand

The combination of RUN plus EXTF plus blinking BUS2F is a textbook signature for a CPU whose dedicated PROFIBUS DP interface (IF2) cannot establish token-passing communication with the configured slave population. Because the CPU does not transition to STOP, the OB1 / OB82 / OB86 / OB122 default behavior is being executed; the program continues to run while the diagnostic event is logged in the diagnostic buffer.

Important: The S7-400 diagnostic LEDs (SF, BF, BUS2F, EXTF, INTF) are independent of RUN/STOP. A blinking BUS2F does not indicate a STOP condition. Always read the CPU's operating mode from the RUN/STOP pair, not from SF or BF.

Interpreting the Diagnostics Buffer

Open STEP 7 (or TIA Portal with the legacy S7-400H support package) and navigate to PLC → Module Information → Diagnostic Buffer. The relevant entries for this case decode as follows:

Field Value Decoded Meaning
Event ID 0x3942 / "I/O access error, writing" OB122 was triggered by a write to a non-existent slave
Access type P area, word access Process image output (PIQ), 16-bit write
Access address 544 Byte 544, word-aligned; corresponds to slot offset in the process image
FC number 3 User program block performing the write (FC3)
Module address 238 Configured DP slave diagnostic address (slot index in the PROFIBUS configuration)

Module address 238 is the diagnostic address STEP 7 assigns to a configured but unreachable slave. The CPU is trying to write a 16-bit process image word to the output area of that slave, the slave does not respond, and OB122 fires. OB122 can be left empty (no user logic) so the CPU just records the event and continues — which is why production is technically running, but no I/O updates are reaching the field.

Additional buffer entries that confirm the second DP interface failure typically include:

  • DP slave failure (event ID 0x3901 / 0x3902 / 0x38B1) repeated for every configured slave on IF2.
  • Station failure or Station return toggling every few seconds, indicating a flapping bus.
  • PROFIBUS DP: bus fault, hardware fault of the interface (event ID 0x3E0B) — the smoking gun when the DP port itself is electrically damaged.

Root Cause Analysis

The combination of evidence — a PSU that failed catastrophically, a CPU that boots cleanly, an I/O-access error stack pointing at IF2, and a PC/PG that cannot see the slaves when attached to the DP port — points to electrical damage to the DP interface of the CPU. The most common field cause is a transient or sustained overvoltage on the PROFIBUS trunk:

  1. 230 V AC on the bus from a miswired terminator or a failed insulation on a Simocode, Sirius, or other PROFIBUS-connected device.
  2. Lightning-induced surge on a long outdoor cable run.
  3. Hot-swap of a DP slave with the bus still energized and the connector shorted.
  4. Cumulative damage from a previous short on a 24 V field conductor sharing the cable tray.

When the original PS407 4A failed, the fault event itself may have generated a back-EMF or short-circuit transient that propagated through the backplane to the CPU's IF2 transceiver. The 4 A PSU died first because the overcurrent was drawn through the 5 V rail that powers the DP transceiver, but the resulting inrush damaged the RS-485 driver ASIC on the CPU. After replacement of the PSU, the port remains electrically shorted or biased, so the CPU's DP master cannot drive the bus.

A secondary but related cause is mechanical: the DP connector's terminating resistor switch may have been left in the wrong position when the PSU swap was performed, or a piggy-back PG socket may be missing, leaving the bus unterminated. Always check this first; it is a free fix.

Step-by-Step Diagnostic Procedure

1. Verify the Physical PROFIBUS Segment

  1. Power down the rack (PSU selector switch to standby or remove the PS407).
  2. Inspect every DP connector on the trunk. Confirm that the termination switch is ON only at the two physical ends of the segment (typically the CPU DP port and the last ET200 station) and OFF on every intermediate drop.
  3. Measure the trunk voltage between pins 3 (RxD/TxD-P) and 8 (RxD/TxD-N) with the segment powered. A healthy PROFIBUS segment reads roughly 1 V DC of idle bias with 50 mV of differential activity when polled. A reading near 0 V or near 5 V indicates a shorted or pulled-up bus.
  4. Measure between pin 6 (VP) and pin 5 (DGND) for 24 V field supply. This voltage should be sourced by only one device on the segment. Multiple 24 V sources will fight each other and bias the line.

2. Isolate Slaves One-by-One

  1. With the CPU in STOP, open STEP 7 HW Config and disconnect one DP slave at a time by unplugging its bus connector.
  2. Re-power the rack. Watch BUS2F. If BUS2F goes dark after unplugging a particular slave, that slave or its connector is the fault source.
  3. Field experience: a terminated Simocode (3UF7) with a failed insulation path is a frequent culprit because the integrated PROFIBUS terminator ties the bus directly to the device's 24 V supply.

3. Test the CPU DP Port with a PC/PG

  1. Attach a Siemens PC Adapter USB (6GK1571-1AA00) or CP 5512 / CP 5711 to a DP connector that has a piggy-back PG socket.
  2. In STEP 7, set the PG/PC interface to PC Adapter (PROFIBUS) and the station address to 0.
  3. Click Accessible Nodes. The CPU should appear at address 2 (the default PROFIBUS address of the CPU's DP master). If no CPU appears and BUS2F continues blinking, the DP master port is electrically non-functional.
  4. As a cross-check, attach the PC/PG to the MPI/DP port. If the CPU is visible there but not on the second port, the IF2 transceiver is confirmed damaged.

4. Read the Diagnostic Buffer in Detail

  1. Open PLC → Module Information → Diagnostic Buffer in online mode.
  2. Click Help on Event for the top three entries — the S7-400 firmware provides a detailed explanation of each event ID, including the module address and the slot offset.
  3. Note the timestamp of the most recent DP slave-failure event. If events occur at a regular 10-second cadence, the CPU's DP watchdog is firing; if they are random, the bus is flapping.

Recovery Path A — Reconfigure the MPI/DP Port as DP

If the dedicated DP port (IF2) is damaged and no spare CPU is on site, the field-proven workaround is to migrate the PROFIBUS master role to the MPI/DP port (IF1). The CPU 412-2DP supports this because IF1 can be software-selected to operate as either MPI or DP master. The drawback is that the HMI panel, which currently uses the MPI network, must be moved to PROFIBUS DP as well.

Prerequisites

  • Source backup of the STEP 7 project (.s7p / .s7l).
  • Configuration software for the HMI panel (ProTool / WinCC flexible / TIA Portal) to change the HMI's network assignment.
  • Verified good DP cable with a terminator at each end of the new segment.

Procedure

  1. Open HW Config in STEP 7. Double-click the CPU 412-2DP.
  2. Select the MPI/DP interface. In the properties dialog, change Interface Type from MPI to PROFIBUS DP Master.
  3. Set the PROFIBUS address of IF1 to the address formerly held by IF2 (typically 2). Set the baud rate to 1.5 Mbit/s (default and most robust for short segments).
  4. Cut the DP subnet in HW Config and paste the slaves onto IF1. Save and compile. The system data (SDB) is regenerated.
  5. Download the new hardware configuration to the CPU using the MPI/DP port (now still addressable as MPI for the download, or temporarily revert IF1 to MPI just for the download).
  6. Verify that BUS2F is now dark and a new BF or BUS1F on IF1 is also dark once slaves are polled.
Critical: Before changing IF1 from MPI to DP, confirm that no other MPI device on the segment requires an MPI master. If there are additional MPI panels or S7-200 / S7-300 / LOGO! devices that need MPI protocol, they will lose connectivity.

Recovery Path B — Reconfigure the HMI to PROFIBUS DP

Once IF1 is converted to DP, the HMI panel (MSystem / Micro Innovation GFO-57SQD-002) can be reconfigured as a DP slave on the same segment. The GFO-57SQD-002 is a 5.7-inch QVGA panel that natively supports both MPI and PROFIBUS DP; only the project file needs to be rebuilt and downloaded.

Procedure

  1. Open the HMI project in ProTool / WinCC flexible 2008 SP5 (or the equivalent TIA Portal project).
  2. Change the HMI's Connection from MPI S7-400 to PROFIBUS DP S7-400. Set the HMI's PROFIBUS address to a free value (e.g., 4) to avoid collision with the CPU master (2) and any ET200 stations (3, 5, 6, …).
  3. Add a PROFIBUS DP partner entry for the CPU at address 2. Recompile and download the HMI image via Ethernet or serial.
  4. Cycle power on the HMI. Confirm that the HMI is visible in STEP 7 Accessible Nodes at the new DP address.
Caveat: If the HMI source project is unavailable (third-party panel with proprietary software, as in the Romaco Horn Noack Blister Machine case), the original machine builder (Romaco) must be contacted. Without the project, the HMI cannot be re-parameterized to DP and a replacement panel of the same type, or a new panel with a freshly built project, is the only option.

Recovery Path C — Replace the CPU

If both ports on the spare CPU are needed (one for HMI, one for I/O) and the damaged CPU cannot be repaired in place, the only clean recovery is a CPU swap. The CPU 412-2DP is hot-swappable on a powered rack when using a memory card and a backup project. Order a replacement using the MLFB 6ES7412-2EK06-0AB0 (firmware V6.0.7 or later). After replacement:

  1. Insert the memory card with the project backup.
  2. Power up. The CPU boots, copies the project from the card, and enters RUN automatically.
  3. Confirm the EXTF and BUS2F LEDs are dark and that all DP slaves are reachable.

Verification Checklist

Check Method Pass Criterion
CPU operating mode LED RUN / STOP RUN solid green
EXTF cleared LED and diagnostic buffer No external fault event in last 60 s
BUS2F cleared LED Dark
All DP slaves online STEP 7 → Accessible Nodes Every configured slave responds
I/O access errors Diagnostic buffer No new OB122 events in last 5 min
HMI communication Screen refresh and tag test Process values update live
Watchdog timing STEP 7 → Module Information → Communication DP cycle time within configured tolerance

Extended Diagnostic Considerations for S7-400H Systems

If the rack is part of an S7-400H fault-tolerant pair, the EXTF LED has an additional meaning: it can be lit by an asymmetric event where one CPU has lost a redundant link or where the buffer battery of the partner CPU has failed. The Siemens support portal documents that an S7-400H with EXTF always on a single PLC was traced to buffer battery monitoring — replacing the battery cleared the LED without touching the I/O configuration. Always check the buffer battery first on an H system before assuming a bus fault.

For the H system, the diagnostic buffer entries differ slightly. The OS blocks SFC 13 / SFB 52 / SFB 54 read structured diagnostic data and the system status list (SZL) with index 0x0A92 and 0x0A94 provide a direct map of redundant link states. Reading these SZLs from the user program is a reliable way to localize the EXTF cause.

Commissioning Procedure After Recovery

  1. Power down and re-power the rack to clear all latched diagnostic state.
  2. Connect STEP 7 online and read the diagnostic buffer top-down. Confirm the latest entry is a station return for every configured slave.
  3. Run the user program in single-scan (CPU in STOP, then one RUN cycle) to test that FC3 write operations to address 544 complete without OB122.
  4. Force a single output bit on the affected module and verify with a multimeter at the field terminal.
  5. Force an input bit and verify the value in the variable table (VAT).
  6. From the HMI, jog a motor or open a valve to confirm end-to-end operation.
  7. Log the recovery steps in the maintenance log; document the bus topology and the new port assignment.

Preventive Measures

  • Install a Siemens PROFIBUS terminator (6ES7972-0DA00-0AA0) only at the two physical ends. Remove the active terminator from every device in between.
  • Add surge protection (Siemens 6ES7972-0DA00-0AA0 active terminator with surge, or a Phoenix Contact PT-IQ series) at any cable that leaves the cabinet.
  • Verify the shield bonding of the PROFIBUS cable. The shield should be bonded to ground at the cabinet entry using a 360-degree clamp, not a pigtail.
  • Avoid sharing a 24 V field conductor with PROFIBUS devices that can fail short. The 24 V common-mode voltage on a Simocode that has lost insulation is the most frequent cause of a destroyed CPU DP port.
  • Replace the buffer battery (3.6 V lithium, 1.5 Ah, e.g., 6ES7971-0BA00) on a fixed schedule (every 3-5 years) to prevent EXTF from the battery monitor.
  • Maintain a spare PS407 4A or PS407 10A and a spare CPU 412-2DP on the shelf for production-critical cells.

When to Escalate to Siemens Support

Escalate when:

  • The diagnostic buffer shows event ID 0x3E0B (DP hardware fault of the interface) that reappears after every power cycle.
  • Replacing the PS407 and re-cabling the bus does not clear BUS2F.
  • The HMI project source is lost and the original machine builder cannot be reached.
  • The system is a S7-400H and the EXTF LED persists after battery replacement and bus verification.

Have the following ready when opening a support request: the full diagnostic buffer export, the HW Config printout, the station list, the firmware version of the CPU (read from the module information), the order numbers of all components, and a wiring diagram of the PROFIBUS segment.

Why is the EXTF LED on an S7-400 lit after a power supply replacement?

The EXTF LED indicates an external fault such as a missing DP slave, a battery low condition, or a redundant link loss. After a PSU replacement on a 412-2DP, the most common cause is a damaged DP port on the CPU that now reports every configured slave as unreachable. Read the diagnostic buffer (PLC → Module Information → Diagnostic Buffer) and look for event ID 0x3E0B and OB122 I/O access errors to confirm.

What does a blinking BUS2F LED mean on an S7-400 CPU?

BUS2F is the bus-fault LED for the second PROFIBUS interface (IF2). A steady OFF is healthy; a blinking pattern means one or more configured DP slaves are not responding. The CPU is still in RUN but the process image for those slaves is not updated, and OB122 will fire on every read/write attempt.

Can the MPI/DP port of a CPU 412-2DP be reconfigured to PROFIBUS DP master?

Yes. In HW Config, double-click the CPU, select the MPI/DP interface, and change the interface type from MPI to PROFIBUS DP master. Set the address to a free PROFIBUS node ID and recompile. After download, IF1 becomes a full DP master and the dedicated DP port (IF2) is no longer needed for I/O. The HMI must be moved to the same DP segment or to a separate network.

How do I read a module address 238 I/O access error in STEP 7?

Open the diagnostic buffer online, click the entry "I/O access error, writing P area, word access, Access address 544, FC 3, Module address 238". The module address 238 is the STEP 7 diagnostic address of the unreachable slave. Cross-reference this address in HW Config: right-click the slave and choose "Properties" to see its slot and PROFIBUS station. The bus to that station is the physical segment to inspect.

What is the most common field cause of a destroyed CPU DP port?

A 230 V AC fault on the PROFIBUS trunk from a failed insulation on a connected device, most often a Simocode (3UF7) motor management unit, a Sirius soft-starter, or a drive with a damaged bus interface. The active terminator in such a device ties the bus directly to its 24 V / 230 V supply, so an internal short drives the bus voltage far outside the RS-485 spec and burns out the CPU's transceiver. Always disconnect the bus, measure the trunk with a multimeter, and isolate devices one at a time.

Back to blog