C200H-LK201-V1 Host Link Module: Programming Legacy Omron PLCs

James Nishida12 min read
OmronPLC HardwareTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

C200H-LK201-V1 Host Link Module: Programming Legacy Omron C200H PLCs

The Omron C200H is a mid-1980s modular PLC platform that Omron formally discontinued, yet thousands of machines in the field still run on it. Program upload, edit, and monitor operations require either a CPU-mount host link module (3G2A6-LK201-EV1) or a single-slot backplane module (C200H-LK201-V1), both of which expose an RS-232C serial port to a host PC running SYSWIN or CX-Programmer. This reference consolidates the part numbers, port pinouts, cable requirements, peripheral-port hazards, and replacement strategy every maintenance engineer needs before touching a C200H that has no backup.

1. C200H Family Overview and Lifecyle Status

The C200H family spans several generations. Engineers must identify which CPU is in the chassis before selecting a host link, because the mount style and electrical interface differ between the original C200H and the later Alpha series (C200HS, C200HE, C200HG, C200HX).

CPU Status CPU-Mount Host Link Backplane Host Link
C200H Discontinued 3G2A6-LK201-EV1 (48-pin horizontal connector) C200H-LK201-V1
C200HS Discontinued Not supported on the 48-pin connector C200H-LK201-V1
C200HE / C200HG / C200HX (Alpha) Discontinued Not applicable - use backplane module or built-in port C200H-LK201-V1

The Alpha generation (C200HS and above) introduced an upgraded peripheral port with 5 V CMOS-compatible logic. The original C200H peripheral port uses different voltage levels and pinout, which is why cables designed for the Alpha line will physically seat but will either fail to communicate or, in the worst case, blow the CPU board fuse. This distinction is the single most common cause of field damage when an engineer grabs the nearest Omron programming cable off the shelf.

Critical: Never plug a CQM1-CIF02 cable or a CPM1-CIF01 adapter into the C200H peripheral port. They fit, they will not work, and they can damage the CPU.

2. C200H-LK201-V1 Backplane Host Link Module

The C200H-LK201-V1 is a single-slot Host Link module that mounts in any open slot on the C200H / C200HS / C200H Alpha backplane and provides a standard RS-232C (also called RS-232-C) interface to a host computer. It is the preferred path when a free slot exists because it does not require any modification to the CPU and is electrically isolated from the peripheral-port hazard discussed above.

2.1 Part Status and Sourcing

Omron has marked the C200H-LK201-V1 as a discontinued part. Major authorized distributors still list the part in their catalogs for reference but flag the lifecycle as Obsolete and report zero factory stock:

Although the part is obsolete at the factory, NOS (new-old-stock) and refurbished inventory routinely surfaces at Omron-specialist resellers. Verify warranty terms (typically 90 days to one year for refurbished) and request a burn-in test report before installing in a production line.

2.2 Module Specifications

Parameter Value
Omron Part Number C200H-LK201-V1
Function Host Link serial communication module
Electrical Interface RS-232C (EIA-232-D compatible)
Connector DB-25 female (25-pin) on module faceplate
Mounting Single slot, C200H / C200HS / C200H-Alpha backplane
Front-Panel Indicators RD (receive), SD (send), COMM OK
Switched Parameters Node address (00-31), baud rate, protocol mode (Host Link)
Supported Software SYSWIN, CX-Programmer (v3.x and earlier for direct support)

3. 3G2A6-LK201-EV1 CPU-Mount Host Link

If every backplane slot is populated, the original C200H (only) supports a CPU-mount host link that snaps onto the long 48-pin horizontal connector on the front of the CPU. This is part number 3G2A6-LK201-EV1 and it brings the same RS-232C Host Link capability as the C200H-LK201-V1 without consuming a slot.

The CPU-mount host link is mechanically compatible with the C200H only. C200HS and C200H-Alpha CPUs expose a different 48-pin connector geometry, so the 3G2A6-LK201-EV1 will not seat correctly and must not be forced. For the C200HS and Alpha, use the backplane C200H-LK201-V1 instead.

Mechanical warning: Confirm the CPU faceplate label reads exactly "C200H" (not C200HS, C200HE, C200HG, or C200HX) before ordering the 3G2A6-LK201-EV1. The Alpha series uses a different connector keying.

4. Port Extenders: C200H-BP001 and C200H-BP002

Both the C200H-LK201-V1 (in some chassis configurations) and the 3G2A6-LK201-EV1 may require a port extender to clear adjacent modules and present the 25-pin connector at the chassis lip:

  • C200H-BP001 - short extender, typical for CPU-mount host link applications.
  • C200H-BP002 - extended-length variant for deep rack or wiring-duct clearance.

The port extender does not appear in current Omron price lists. Treat it as a long-lead part and source it together with the host link module. If the extender is unavailable, a third-party DB-25 male-to-female hood extension cable is an acceptable substitute provided the shield is bonded at one end only.

5. RS-232C Cable Requirements

The LK201 family presents a DB-25 female on the PLC side. The host PC almost always terminates in DB-9 (legacy industrial PCs and many modern industrial tablets still have DB-9; USB-to-RS-232 adapters are also acceptable when based on FTDI FT232 or equivalent industrial-grade bridges).

For Host Link protocol on the C200H, the standard cable is a straight-through RS-232C shielded cable wired as follows. Note that the C200H-LK201-V1 uses a minimal subset of the RS-232C signals; RTS/CTS handshaking is not required at the default Host Link settings.

Signal DB-25 (PLC side) DB-9 (PC side)
Frame Ground (chassis) 1 Shell
TXD (PLC transmit, PC receive) 2 2 (RD)
RXD (PLC receive, PC transmit) 3 3 (TD)
RTS (PLC side, optional) 4 7 (RTS)
CTS (PLC side, optional) 5 8 (CTS)
Signal Ground 7 5 (GND)
DCD (PLC side, optional) 8 1 (DCD)
DTR (PC side, optional) 20 4 (DTR)

5.1 Standard Host Link Communication Parameters

Parameter Typical C200H Value
Baud rate 9600 bps (default), 19200 bps supported
Data bits 7
Parity Even
Stop bits 2
Node address 00 (set on LK201 DIP switches)
Protocol Omron Host Link (C-mode)

6. Peripheral Port: What It Is, What It Is Not

The C200H CPU faceplate has a second connector under a small drop-down flap. This is the Peripheral Port, a 16-pin connector intended only for the C200H-PRO27 handheld programmer. Connection is via Omron cable C200H-CN222. The C200H-PRO15 "handheld" programmer is a different device: it occupies the 48-pin horizontal connector shared with the host link modules and the port extenders, not the Peripheral Port.

The Peripheral Port is the single most abused connector on the C200H. The following cables physically fit the Peripheral Port socket and will either fail silently or destroy the CPU:

Cable / Adapter Intended For Effect on C200H
CQM1-CIF02 CQM1 / CPM1 / SRM1 peripheral port to RS-232C Does not function; can blow CPU board fuse
CPM1-CIF01 CPM1 peripheral port to RS-232C Does not function; can damage CPU port driver
NT2S-CN212 NT2S HMI to Omron PLC peripheral port (5 V level) Level mismatch; blows CPU fuse on C200H
Field-proven rule: On an original C200H, the only safe items to plug into the Peripheral Port are a C200H-PRO27 handheld programmer via the C200H-CN222 cable. Nothing else.

The Alpha series (C200HS and above) upgraded the Peripheral Port to a 5 V CMOS logic level that is compatible with the CQM1-CIF02 / CPM1-CIF01 adapters. This change is what made the adapters viable on Alpha hardware. The original C200H does not have that protection, so the level translators in the newer adapters do not engage and the raw RS-232 line driver hits the 5 V CMOS input on the C200H, which is what blows the fuse.

7. Software: SYSWIN and CX-Programmer

SYSWIN version 3.x is the canonical programming environment for the C200H family and supports every C200H, C200HS, and C200H-Alpha CPU directly. It uses the standard Omron Host Link protocol and communicates at the parameters listed in section 5.1.

CX-Programmer (versions up to 9.x) also supports the C200H family under the "C200H" device family selection. For modern Windows hosts (Windows 10 / 11), use CX-Programmer 9.6 or later, install in XP compatibility mode if necessary, and create a logical COM port mapped to the USB-to-RS-232 adapter. The default baud/parity/data/stop settings in CX-Programmer's C200H device driver match the values in the table above.

SYSWIN can be run inside a Windows XP Mode virtual machine under Windows 7 Professional, or under DOSBox / PCem for legacy host compatibility. When using a USB-to-RS-232 adapter, select an FTDI-based unit and explicitly assign a fixed COM port number (e.g., COM3) from Device Manager to keep SYSWIN's port list predictable.

8. Program Upload Procedure

The following procedure applies to a C200H-LK201-V1 in an open backplane slot and a host PC running SYSWIN 3.x.

8.1 Prerequisites

  1. C200H-LK201-V1 module installed and seated in an open backplane slot.
  2. PLC powered and in PROGRAM mode (key switch on CPU set to PROGRAM).
  3. RS-232C shielded cable, DB-25 male to DB-9 female, wired per section 5.
  4. SYSWIN 3.x installed on the host PC, with the correct COM port selected.
  5. Host Link parameters on the LK201 DIP switches: Node 00, 9600, 7-E-2.

8.2 Step-by-Step

  1. Power the PLC. Observe the LK201 PWR LED is steady green.
  2. Verify the LK201 RD and SD LEDs flash once at power-up, indicating the module passed self-test.
  3. Connect the RS-232C cable from the LK201 faceplate to the host PC COM port.
  4. Launch SYSWIN. From the PLC menu select Online, then Connect.
  5. In the connection dialog, set:
    • Network: Host Link
    • COM Port: 3 (or as assigned)
    • Baud: 9600
    • Data: 7, Parity: Even, Stop: 2
    • Node: 00
  6. Click Test. A successful test returns "Host Link OK".
  7. From the File menu select Save Program from PLC to File. Specify a filename with the .csy or .cxt extension depending on the SYSWIN / CX-Programmer version.
  8. After the upload completes, verify the program checksum by comparing the displayed file size and ladder area count against a known-good program from the same model, or by downloading to a second C200H and confirming identical I/O behavior.

9. Sourcing Strategy for Obsolete Parts

For factory-original, never-installed parts, expect lead times in the 8-16 week range or unavailability. The practical strategy is:

  1. Pull two C200H-LK201-V1 modules from non-critical surplus equipment for every production line that must be supported. Burn-in test each for at least 48 hours at 35 degC ambient.
  2. Stock at least one C200H-PRO27 handheld programmer and one C200H-CN222 cable per site. The handheld programmer is the fastest offline backup tool and does not require a free backplane slot.
  3. Maintain a verified host PC image with SYSWIN and CX-Programmer installed, locked to a specific COM port numbering scheme. USB-to-RS-232 adapters should be the same SKU across the site to avoid driver churn.
  4. For long-term support, plan a migration to a current-generation Omron platform (CP1E, CP1H, NJ, or NX) using a documented I/O and program conversion. The Omron CX-Programmer migration tool can import C200H ladder and remap I/O addresses.

10. Field-Proven Safety Checklist

Before applying power with a host link module installed for the first time on a machine that has been running unattended, complete the following:

  • Confirm the CPU is in PROGRAM mode and that the process is in a safe state. Uploading does not write to the PLC, but a misclick in the software can transition the PLC to MONITOR or RUN.
  • Verify the LK201 faceplate DIP switches match the planned node address and baud rate. The factory default is node 00, 9600 bps.
  • Confirm the RS-232C cable shield is bonded at the PLC end only. Floating or double-bonded shields inject common-mode noise into the Host Link UART and produce intermittent timeouts.
  • Measure +5 V and +24 V on the CPU power supply before insertion. A sagging +5 V rail (below 4.85 V) can cause the LK201 to repeatedly reset its Host Link state machine.
  • Mark the Peripheral Port with a label stating "PRO27 ONLY - DO NOT INSERT CQM1/CPM1 ADAPTER". This is the single most effective preventive measure against field damage.

11. Troubleshooting Matrix

Symptom Likely Cause Corrective Action
SYSWIN reports "No Response from PLC" Wrong COM port or baud rate Verify COM port in Device Manager; match baud/data/parity/stop to LK201 DIP switches
LK201 PWR LED off Module not fully seated or backplane +5 V absent Reseat module; measure backplane +5 V at an adjacent known-good slot
RD LED active, SD LED never flashes Cable TX/RX crossed or PC COM port disabled Loopback test the PC COM port; swap pins 2 and 3 if needed
Comm test passes, upload errors mid-transfer Shield not bonded; EMI from VFD nearby Bond shield at PLC end only; reroute cable away from VFD output conductors
CPU will not enter PROGRAM mode via key switch Remote RUN signal from another host link node Disconnect all other host link nodes; cycle power
CPU board fuse blown after adapter inserted CQM1-CIF02 / CPM1-CIF01 / NT2S-CN212 inserted into original C200H peripheral port Replace fuse; relabel port; never insert non-PRO27 cables again
SYSWIN Test dialog returns "Timeout" within 5 s Wrong node address or LK201 in programming mode Confirm LK201 DIP switch node matches SYSWIN setting; toggle RUN/PROGRAM on module faceplate

12. Specifications Summary

Specification C200H-LK201-V1 3G2A6-LK201-EV1
Mounting Single backplane slot CPU 48-pin horizontal connector
CPU Compatibility C200H, C200HS, C200H-Alpha C200H only
Interface RS-232C, DB-25 female RS-232C, DB-25 female
Protocol Omron Host Link (C-mode) Omron Host Link (C-mode)
Lifecycle Obsolete (per distributor listings) Obsolete (per distributor listings)
Required Extender C200H-BP001 or C200H-BP002 (chassis dependent) None (mounts on CPU)

FAQ

Is the C200H-LK201-V1 still available new from Omron?

No. The C200H-LK201-V1 is listed as obsolete by major authorized distributors including DigiKey and Mouser. The only sources are NOS, refurbished resellers, and used pulls from surplus equipment.

Can I use a CQM1-CIF02 cable on a C200H peripheral port to program it from a PC?

No. The CQM1-CIF02 physically seats on the C200H peripheral port but does not function and can blow the CPU board fuse. The C200H peripheral port is designed for the C200H-PRO27 handheld programmer via the C200H-CN222 cable only.

What is the difference between the C200H-LK201-V1 and the 3G2A6-LK201-EV1?

The C200H-LK201-V1 occupies one backplane slot and works in C200H, C200HS, and C200H-Alpha CPUs. The 3G2A6-LK201-EV1 mounts on the CPU 48-pin horizontal connector and is compatible with the original C200H only. Use the backplane module whenever a free slot exists.

What serial parameters should I configure for Host Link communication with a C200H?

Use 9600 bps, 7 data bits, even parity, 2 stop bits (9600-7-E-2), and node address 00 by default. These match the LK201 factory DIP-switch settings and are accepted by both SYSWIN 3.x and CX-Programmer's C200H device driver.

Which programming software works with the C200H family?

SYSWIN 3.x supports every C200H, C200HS, and C200H-Alpha CPU. CX-Programmer (up to v9.x) also supports the C200H family under the C200H device family selection. Both communicate using the standard Omron Host Link protocol over RS-232C.