Problem Overview
A SINAMICS G120C controlled over PROFINET from a SIMATIC S7-1500 trips F01600 / F30600 and F01611 / F30611 after the Safe Torque Off (STO) safety function is triggered through the on-board digital inputs (typically DI4 and DI5) wired to an emergency-stop circuit. After the safety demand is removed, the drive remains in a faulted state and cannot be acknowledged through the standard control telegram. Only a power-off / power-on cycle restores the drive to a ready state. Because the S7-1500 (non-F variant) used in the original configuration does not support PROFIsafe, the conventional Internal Event ACK path is blocked.
This article consolidates the three supported acknowledgment paths, the diagnostic parameter set used to identify the exact sub-cause, the telegram combinations required for PROFIsafe, and the hardware prerequisites (F-CPU) that govern whether in-cycle acknowledgment is even possible.
Affected Components and Safety Architecture
The fault topology in the original incident comprises:
- Drive: SINAMICS G120C (CU230S-2 or CU240S-2 control unit, firmware ≥ V4.5 for Safety Integrated basic functions). See the SINAMICS G120C Operating Instructions for the firmware-to-control-unit mapping.
-
Safety inputs:
DI4andDI5wired in a dual-channel arrangement to an emergency-stop pushbutton; either input going low (or open, depending on wiring convention) requests STO. -
Controller: SIMATIC S7-1500 (e.g.,
6ES7513-1AL02-0AB0, CPU 1513-1 PN) configured without a safety program. -
PROFINET telegram: Standard telegram
352selected in the device properties; speed setpoint and control wordSTW1are exchanged but no PROFIsafe slot is added.
DI4 and DI5 are simultaneously low. When the safety demand is removed and the inputs return high, the drive is allowed to re-enable pulses — but only if the safety fault state has been acknowledged. A latched fault suppresses re-enable until explicit acknowledgment, which is exactly the failure mode reported.Fault Code Reference: F01600 / F30600 / F01611 / F30611
These four fault numbers represent a pair of mirrored faults across the two processors inside the SINAMICS control unit. The cross-mapping is documented in the SINAMICS G120 / G120C Safety Integrated Function Manual.
| Fault Number | Channel | Meaning |
|---|---|---|
F01600 |
Processor 1 (P1) | STOP A initiated — STO active. Forced checking procedure of the safe shutdown path on P1 unsuccessful, or subsequent response to F01611. |
F30600 |
Processor 2 (P2) | Mirror of F01600 on P2; both must agree for the drive to re-enable. |
F01611 |
Processor 1 (P1) | Defect in a monitoring channel; safe shutdown path discrepancy between P1 and P2. |
F30611 |
Processor 2 (P2) | Mirror of F01611 on P2. |
Reaction: OFF2 (pulse suppression via the safe shutdown path). The fault is latched and requires explicit acknowledgment; auto-restart on de-selection of STO is not the default.
Fault Value Diagnosis via r0949
The fault value in r0949 (decimal interpretation) pinpoints the immediate cause of F01600 / F30600. Read it using the drive's web server, Starter / Startdrive, or via the S7-1500 with RDREC on the DO index that returns the fault buffer.
| r0949 (dec) | Interpretation |
|---|---|
0 |
Stop request from processor 2 (P2 initiated the discrepancy). Cross-check the wiring of DI4 / DI5 — most common root cause when one input toggles faster than the other. |
1005 |
Pulses were suppressed although STO was not selected and no internal STOP A is present. Indicates an internal shutdown path fault — replacement of the control unit is required. |
1010 |
Pulses were enabled although STO is selected or an internal STOP A is present. Critical safety violation; drive must not be returned to service without investigation. |
9999 |
Subsequent response to F01611 — a channel defect already occurred; F01611 will be present in the fault buffer with its own r0949. |
Capture r0949 immediately after the fault trips. If 9999 is reported, scroll back through the fault buffer (the drive retains up to 8 fault entries) and read the value of the F01611 entry to find the underlying discrepancy code.
Why the Fault Will Not Acknowledge via Standard Telegram
Standard telegram 352 carries STW1 (control word 1) and ZSW1 (status word 1) only. The control bit that acknowledges a latched safety fault — STW bit 7 = Internal Event ACK — is defined inside the PROFIsafe telegram, not inside STW1 of standard telegrams. Therefore:
- Setting
STW1.7in telegram352is interpreted by the drive as Acknowledge fault, which clears standard faults but cannot clear the latched Internal Event of the Safety Integrated channel. - Only the PROFIsafe host's
F-Hostapplication generates the Internal Event ACK bit that reaches the drive's safety channel.
F01600 / F01611. A power-on reset or a manual parameter-level STO toggle are the only available options. Upgrading to an S7-1500F (e.g., 6ES7515-2FM02-0AB0) unlocks the PROFIsafe path.Acknowledgment Methods — Comparison
| Method | Hardware Required | Cycle Time to Clear | Suitable for Production |
|---|---|---|---|
| Power OFF / Power ON (24 V or line) | None | ~10–30 s (capacitor discharge + ramp) | No — downtime per trip |
STO select then de-select via p9762 / p9700
|
None | ~2–5 s with parameter access | Marginal — disables safety briefly |
| PROFIsafe Internal Event ACK (STW bit 7 of F-telegram) | F-CPU + PROFIsafe slot | ~50–200 ms | Yes — standard SIL 2 / PL d practice |
Method 1 — Power ON Reset
- Remove the safety demand (close the E-stop circuit so
DI4andDI5are both high). - Power down the SINAMICS line supply (or remove the Control Unit 24 V supply for a CU230S-2; verify the discharge time stated on the drive nameplate).
- Wait at least the discharge interval specified on the drive — typical SINAMICS G120C minimum: 5 minutes for the DC bus to drop below 50 V; this is read at
r0046in the drive. - Re-apply power. The drive performs the safety self-test;
F01600clears automatically if the shutdown path is consistent.
If the fault returns immediately, capture r0949 again — value 1005 or 1010 indicates internal hardware damage and the Control Unit must be replaced.
Method 2 — STO Terminal Deselection with Parameter Reset
This path uses parameter-level commands to perform the select / de-select handshake that the safety function requires. It is intended for commissioning; using it as a routine recovery procedure is discouraged because it momentarily allows the safety channel to enter an inactive state without external supervision.
- Confirm the safety demand is removed (
DI4= high,DI5= high). - Read the current safety password with
r9762(returns a decimal value used as the password in step 3). - Call the safety commissioning function: write the password to
p9762and writep9700 = 1(factory reset of safety parameters) — only if the previous configuration must be wiped. For a clean de-select of an existing configuration, setp9761 = 0(de-select STO) and triggerp9700 = 1as the commit. - Cycle the safety configuration by toggling
p9761: write the safety password fromr9762, then setp9761 = 0(de-select), then runp9700 = 1to commit. - Power-cycle the Control Unit to make the new configuration effective.
Equivalent sequence from Starter / Startdrive: select Drive > Functions > Safety Integrated > Change settings > De-select STO. The tool reads r9762, requests the password, and writes the parameter set in the correct order.
Method 3 — PROFIsafe Internal Event ACK (Bit 7 of STW)
This is the recommended in-cycle path for production systems. The PROFIsafe telegram extends the standard control word with a safety-specific STW in which bit 7 carries the Internal Event ACK signal. A falling edge on this bit clears the Internal Event of the Safety Integrated function and acknowledges the latched fault.
Pre-conditions:
- F-CPU (e.g.,
6ES7515-2FM02-0AB0S7-1515F-2 PN or6ES7513-1FM03-0AB0S7-1513F-1 PN). - PROFIsafe address configured on the G120C (
p9610) and matching F-destination address in the F-host. - Safety telegram selected on the drive — typically telegram 30 (Safety Integrated extended) or telegram 900 (vendor-specific safety payload). See the G120C list manual for the supported safety telegrams.
- F-runtime license active on the CPU.
Acknowledgment sequence in the F-application (F-FBD or F-CFC / Structured Text):
F-Host application:
// STW_S bit 7 = Internal Event ACK
// The PROFIsafe driver updates STW_S from the F-host's acknowledgment tag.
IF safety_fault THEN
ack_stw_bit7 := TRUE; // assert Internal Event ACK = 1
// safety_faults_word evaluates the drive's S_ZSW bits; clear when ZSW_S bit 7 = "Internal Event pending" goes low
WAIT_FOR ZSW_S.bit7 = 0;
ack_stw_bit7 := FALSE; // falling edge on STW_S bit 7 — drive acknowledges the Internal Event
END_IF;
The drive requires a falling edge, not a static level. Holding the bit high will not clear the fault on its own; the F-host must toggle the bit from 1 back to 0 after the safety fault clears.
Telegram Configuration: 352 vs 30 / 900
The standard control telegram (e.g., 352) and the PROFIsafe safety telegram are additive — they coexist on the same PROFINET slot, not mutually exclusive. The standard telegram continues to carry speed setpoints and STW1, while the safety telegram adds the safety payload.
| Telegram | Role | Required for PROFIsafe ACK? |
|---|---|---|
352 |
Standard control — speed setpoint, STW1 / ZSW1
|
Optional — typically kept for non-safety control |
30 |
Safety Integrated extended payload (S_STW, S_ZSW, S_GAMMA, etc.) | Yes — standard safety payload |
900 |
Vendor-specific safety payload (Siemens convention) | Yes — alternate safety payload |
Do not attempt to "switch" the drive from telegram 352 to a safety telegram. Instead, add the safety telegram slot in addition to 352 in the device configuration of TIA Portal. The drive's p0922 must list both telegrams, separated by a comma — e.g., p0922 = 352, 30. After writing p0922, the drive performs a restart to activate the new slot assignment.
Hardware Prerequisites for PROFIsafe
| Component | Minimum Requirement | Notes |
|---|---|---|
| CPU | S7-1500F (e.g., 1513F-1 PN, 1515F-2 PN, 1516F-3 PN/DP) | Standard S7-1500 cannot run the F-runtime. |
| F-runtime | STEP 7 Safety Advanced (TIA Portal) | License required; adds the F-FBD / F-CFC editors. |
| PROFIsafe profile | PROFIsafe V2.4 or V2.6.1 | Match the profile supported by the G120C firmware version. |
| G120C firmware | ≥ V4.5 for Safety Integrated basic functions | Verify via r0018 on the drive. |
| PROFINET slot | Sub-slot for safety payload configured in TIA Portal | Set F-destination address to match p9610 on the drive. |
For a retrofit, replacing a standard S7-1513-1 PN with an S7-1513F-1 PN requires only the CPU swap — the project, hardware configuration, and program logic transfer with no change in I/O mapping. The F-program block is then added as a separate F-runtime container parallel to the standard user program.
Commissioning Workflow in TIA Portal
- Open the project and swap the CPU to the F-variant. Transfer the configuration.
- Open the G120C device view. Under Device configuration > PROFINET interface > Telegram configuration, add telegram
30in addition to the existing352. - Assign the F-destination address (F_Dest_Add) — must match the value programmed into
p9610on the drive. The PROFIsafe address is a numeric value between1and65534;0disables PROFIsafe. - Compile the project and download to the F-CPU. The F-CPU will request a "safety mode activation" password the first time the F-blocks are downloaded.
- In the F-program, generate the F-I/O DB. Map the
S_STWoutput andS_ZSWinput. Drive bit 7 ofS_STWwith the Internal Event ACK tag. - Trigger an E-stop event; verify
F01600trips, then verify the F-program clears it within one PROFINET cycle after the E-stop is released.
Verification Checklist
| Step | Expected Result | Confirm via |
|---|---|---|
| Trigger E-stop, release after 1 s | Drive enters STO, pulses suppressed |
r0046 = 0, ZSW1.6 = 0 (inhibition) |
| Fault buffer after trip |
F01600 with r0949 = 0 or 9999 |
Drive webserver or Starter fault buffer |
| F-host sends Internal Event ACK | Fault clears within 200 ms |
ZSW_S.bit7 falls from 1 to 0 |
| Setpoint enabled, ON command | Drive accelerates to setpoint |
r0021 matches p1155; no F class entry in buffer |
| Forced dynamization test (once per shift) | No false trips; F01600 only appears when E-stop is actually actuated |
Log review, fault buffer |
Run a forced dynamization test weekly on drives that stay in STO-released state for long periods. The G120C performs this automatically if p9650 (test stop time) is configured — typical value: 8 hours. The drive will briefly trip STO and re-enable, exercising the safe shutdown path. A failure here generates C30711 first as a warning, then F30711 if not acknowledged within p9652.
Why does the G120C not clear F01600 / F01611 when I send STW1 bit 7 over telegram 352?
Bit 7 of STW1 in standard telegrams acknowledges ordinary faults only. Safety Integrated Internal Event acknowledgment requires bit 7 of S_STW carried inside a PROFIsafe safety telegram (30 or 900), which is only generated by an F-CPU running an F-runtime. With a non-F S7-1500 and telegram 352 only, there is no in-cycle acknowledgment path.
Do I need to switch from telegram 352 to a safety telegram?
No — safety telegrams are additive. Keep telegram 352 for non-safety control (speed setpoint, basic commands) and add telegram 30 or 900 for the PROFIsafe payload. The G120C supports both simultaneously via p0922 = 352, 30. After writing p0922, the drive performs a restart to activate the new slot assignment.
What is the difference between r0949 = 9999 and r0949 = 1010 on F01600?
Value 9999 means F01600 is a secondary reaction to a prior F01611 — the channel discrepancy is the real fault and F01600 is just the safety function reacting to it. Read the F01611 entry to find the cause. Value 1010 indicates pulses were enabled while STO was still selected or an internal STOP A was active — this is a safety-critical hardware failure that requires control unit replacement, not just acknowledgment.
Can I use p9700 / p9762 to clear the fault without power-cycling?
Yes — by writing the safety password (read from r9762), setting p9761 = 0 to de-select STO, and committing with p9700 = 1, the safety configuration is reset. However, this procedure is for commissioning only and temporarily disables active supervision; using it as a routine operational reset is a safety violation. Use PROFIsafe Internal Event ACK (Method 3) for production systems.
Does an S7-1500F work without changing the G120C firmware?
It works with any G120C firmware that has Safety Integrated basic functions enabled, typically firmware V4.5 or higher. Verify the firmware with r0018 on the drive. Older G120C control units (e.g., CU230S-2 V4.4) may not expose telegram 30 — check the parameter manual for p0922 supported telegram list before commissioning. If telegram 30 is missing, upgrade the Control Unit firmware via the Siemens SINAMICS firmware update tool.