Overview: Direct Data Exchange Between S7-400 and IM151-7
Direct Data Exchange (often labeled DX, internode communication, or cross-traffic) is a PROFIBUS-DP operating mode in which a DP slave publishes selected input/output slots to a peer DP master without the master having to read them through a separate service. The mechanism is defined in the PROFIBUS-DP specification (EN 50170 / IEC 61158) and is implemented in SIMATIC controllers as the "Publish/Subscribe" or "Direct Data Exchange" link type in HW Config / TIA Portal.
In the typical configuration described in field practice, a SIMATIC S7-400 (e.g. CPU 414-3, CPU 416-3, CPU 417-4) acts as the PROFIBUS-DP master class 1 and the ET 200S CPU IM151-7 (6ES7151-7AA20-0AB0 or 6ES7151-7AB00-0AB0, depending on firmware level) acts as an I-slave that both consumes and publishes data with the S7-400. The two CPUs exchange alarms, status, interlock bits, and process data such as counters and analog values.
The question raised by integrators working with this topology is sharp and field-relevant: when the PROFIBUS segment between the S7-400 and the IM151-7 fails (cable break, connector pulled, slave powered down, master STOP/HOLD), what happens to the data that has been exchanged? The answer is not a single behavior; it depends on the slot configuration, the CPU operating mode, and the substitute-value strategy selected in STEP 7 or TIA Portal.
Hardware and Firmware Compatibility
Direct Data Exchange is supported only by SIMATIC modules that can act as DP slave (I-slave) and that expose the published slots to peer masters. The Siemens Support entry 17660809 lists every compatible module. The relevant subset for an S7-400 ↔ IM151-7 link is:
| Module | Order Number | Min. Firmware | Role |
|---|---|---|---|
| S7-400 CPU 412-2 / 414-2 / 414-3 / 416-2 / 416-3 / 417-4 | 6ES7412-2XK00-0AB0 and higher | FW 4.0+ for DX publisher | DP Master / Publisher / Subscriber |
| ET 200S IM151-7 CPU | 6ES7151-7AA20-0AB0 (FW 2.0+) | FW 2.0.0+ | DP Slave / Publisher / Subscriber |
| ET 200S IM151-7 CPU FO | 6ES7151-7AB00-0AB0 | FW 2.0.0+ | DP Slave / Publisher / Subscriber |
| ET 200S IM151-7 CPU (PN variant) | 6ES7151-7BA00-0AB0 | FW 2.5+ | DP Slave / PROFINET device |
| CP 443-5 Extended | 6GK7443-5DX02-0XE0 | FW 4.0+ | DP Master for S7-400 rack |
The IM151-7 must be configured as a DP slave with I-slave capability; the standard IM151-1 head module cannot publish. The S7-400 must be on PROFIBUS-DP master class 1 mode; S7-300 masters of class 2 cannot subscribe to the IM151-7 publication in this link.
For new projects, Siemens recommends moving to PROFINET IO with IRT, where the equivalent function is configured as Direct Data Exchange between S7-1500 CPUs in TIA Portal V16 or higher. The PROFIBUS path described here is the supported option for S7-400 + IM151-7 pairings and for migration projects where an installed bus already exists.
Configuring Direct Data Exchange in STEP 7 V5.x
For S7-400 paired with IM151-7 the typical engineering tool is STEP 7 V5.5 SP4 / SP5 (or STEP 7 Professional 2017 with the S7-400 add-on). TIA Portal V20 documents the same mechanism in Configuring direct data exchange (S7-300, S7-400, S7-1500), but field practice in brownfield sites still relies on HW Config. The required steps are:
- In HW Config, insert the IM151-7 as a DP slave on the S7-400 PROFIBUS subnet. Open the IM151-7 object properties and enable DP-Slave mode and check "Activate direct data exchange" (German: "Querverkehr", English: "Direct Data Exchange").
- Define the transfer areas on the IM151-7 side. Each area specifies a slot (input or output), a length (bytes), a consistency setting, and a slot name. Typical widths: 1 byte for status/interlocks, 4 bytes for a 32-bit counter, 8 bytes for two REAL analog values.
- For each transfer area that is to be published to the S7-400, set the direction to Input on the IM151-7 and enable the option "Slave-to-slave communication" in the area properties. The area becomes visible to the S7-400 master as a published slot.
- For each transfer area that the S7-400 master will subscribe from, the S7-400 station must insert the IM151-7 as a peer and add a matching input area whose source points to the IM151-7 transfer area. STEP 7 automatically creates a DB or an I/O address range on the S7-400.
- Compile and download to the S7-400 first, then to the IM151-7. On startup the master reads the DX configuration and establishes the publisher/subscriber links.
Fail-State Behavior of the Exchanged Data
The crucial question — do exchanged inputs and outputs hold their last value, substitute a configured value, or fall to 0 — is governed by three independent configuration switches. The behavior is not a property of the wire or the protocol; it is a property of how each CPU manages the slots during a DP station failure.
Inputs on the S7-400 (data published by the IM151-7)
When the PROFIBUS link to the IM151-7 fails, the S7-400 stops receiving updated telegrams. The I/O area mapped to the published slots will:
- Freeze the last valid value in the process image (PII) if the slots are accessed as peripheral inputs and the S7-400 CPU is configured for OB85 behavior = ignore and the S7-400 remains in RUN.
- Be re-initialized to 0 at the moment the slave is removed from the bus if OB85 is enabled (default in newer CPU firmware) and the PII is read directly via
L PIB / L PIDwithout SFC14/SFC15. - Be filled with the configured substitute value (any byte pattern) if the slot is read with SFC14 ("DPRD_DAT") and the call is wrapped in a wrapper block that supervises the return code.
The S7-400 does not automatically zero published inputs on link loss. Holding the last value is the default for process image reads; zeroing only happens when the application reads the slot directly through SFC14 and the SFC returns a fault.
Outputs on the IM151-7 (data written by the S7-400)
The IM151-7 behavior is configured in HW Config on the IM151-7 object, tab "DP-Slave Properties" → "Operating Mode". Three options exist:
| Option | Effect on outputs when S7-400 stops or link breaks |
|---|---|
| Output substitute value = 0 | All published outputs are forced to 0x00 by the IM151-7 within the configured fail-safe time (default 100 ms) |
| Output substitute value = last value | The IM151-7 retains the last cycle's values in the output process image (PIQ) and continues driving them onto the physical outputs |
| Output substitute value = configured replacement value | Each bit/byte slot can be assigned an explicit pattern (e.g. 0xFF for a "go to home" coil); the IM151-7 drives that pattern within the fail-safe window |
The fail-safe window is set in the DP slave properties of the IM151-7, default 100 ms, range 10 ms to 650 s. If the IM151-7 does not receive a new I/O telegram from the S7-400 within that window, the configured substitute behavior activates.
Outputs to the S7-400 (data published back from the S7-400 to the IM151-7)
The reverse direction behaves symmetrically. The IM151-7 side will see the S7-400's published outputs freeze at the last value or zero depending on the IM151-7's DP-slave configuration.
Diagnostic Organization Blocks for Link Supervision
Knowing the configured behavior is necessary but not sufficient. The application must observe the link state to interpret the data correctly. STEP 7 provides four OBs that fire on PROFIBUS events. All four are required to build a complete picture of link health.
| OB | Trigger | Information Available | Typical Use |
|---|---|---|---|
| OB82 | Diagnostic interrupt from a DP slave (module pulled, channel fault) | Local diagnostics, slot number, channel, error type | Detect a single module or channel fault on the IM151-7 |
| OB85 | Program execution error caused by I/O update failure | Event class, slot, OB not loaded flag | Suppress S7 STOP if the IM151-7 disappears; log and continue |
| OB86 | Rack failure / DP station failure | Failed DP station number, event ID W#16#39xx | Primary indicator that the IM151-7 is unreachable |
| OB122 | I/O access error during direct peripheral access (L PEW / T PAW) | Faulted slot, byte/word offset | Trap a direct access that targets a vanished slave |
A minimal but effective supervisor is OB86. Inside OB86, the event entry OB86_EV_CLASS, OB86_FLT_ID, and OB86_DP_FAULT_ID identify whether the failure is on entering (B#16#39) or leaving (B#16#38) and whether the failure affects a DP slave (B#16#C4) or a PROFINET station. The following STL snippet, valid for S7-400 with classic STEP 7, demonstrates a counter that the IM151-7 can read to confirm link presence:
// OB86 in the S7-400
// Local flags
DATA_BLOCK DB100
STRUCT
link_ok : BOOL; // TRUE while IM151-7 is reachable
lost_count : DWORD; // increments on each OB86 enter event
END_STRUCT
END_DATA_BLOCK
FUNCTION_BLOCK FB100 "LinkSupervisor"
VAR
cntLost : DWORD;
cntBack : DWORD;
END_VAR
BEGIN
// called from OB1 each cycle
// heartbeat logic here
END_FUNCTION_BLOCK
// OB86 (rising event)
L B#16#39 // entering event
L #OB86_EV_CLASS
==I
JC _lost
L B#16#38 // leaving event
L #OB86_EV_CLASS
==I
JC _back
BE
_lost:
L #OB86_DP_FAULT_ID
L W#16#C4 // DP-Slave failure
==I
JC _lostSlave
BE
_lostSlave:
L #OB86_RESERVED_1 // contains DP station number
T MW 200
SET
R DB100.DBX0.0 // link_ok = FALSE
L DB100.DBD2
+ 1
T DB100.DBD2 // lost_count++
BE
_back:
L #OB86_RESERVED_1
T MW 202
SET
S DB100.DBX0.0 // link_ok = TRUE
L DB100.DBD6
+ 1
T DB100.DBD6 // back_count++
END_ORGANIZATION_BLOCK
The same DB100 symbol can be added to the published transfer area from the S7-400 to the IM151-7. The IM151-7 reads the counter, and a counter that has stopped incrementing is direct evidence of link loss, exactly the technique field-proven in the original case.
Implementing Substitute Value Strategies
Choosing between hold last value, substitute 0, and configured replacement is a design decision driven by the controlled process. The two following patterns are the ones most commonly used in plants that combine S7-400 master and IM151-7.
Pattern A — Hold Last Value (Fail-Safe Freeze)
Use this for interlocking bits and analog setpoints that drive slowly-moving equipment (heaters, conveyors, level control). The system continues in the last commanded state. In HW Config on the IM151-7 object, set Output substitute value = last value. Pair the slot with OB86 in the S7-400 to avoid STOP, and add a watchdog in the S7-400 that writes a "heartbeat" pattern to a reserved byte of the published area. If the S7-400 itself enters STOP, the IM151-7 will see no new heartbeat and force the substitute value within the fail-safe window.
Pattern B — Forced Safe State (Go-Home)
Use this for safety-class actuators (valves, brakes, robot enable) that must move to a defined state on any loss of communication. Configure the IM151-7 with Output substitute value = 0 or a configured replacement pattern. The fail-safe window should be tightened to the smallest acceptable value (typically 20–50 ms) so the actuator moves quickly. Add a periodic confirmation to the S7-400 that the link is alive; if the confirmation fails for three cycles, treat the data as invalid regardless of the held value.
Pattern C — Application-Level Substitution
Use SFC14 ("DPRD_DAT") and SFC15 ("DPWR_DAT") on the S7-400 side to read/write the published areas with explicit consistency. The return code RET_VAL is 0 on success and a W#16#80xx error on failure. The application can then drive the consumer variables with a substitute value computed from local context (e.g. last good value, filtered average, or ramped target). This pattern is the most flexible and the one recommended for any new project using TIA Portal V16+:
// S7-400 SCL, TIA Portal V20, reading 4 bytes from IM151-7 publication
// Input area: I100..I103 (published by IM151-7)
// Output area: Q200..Q203 (subscribed by IM151-7)
FUNCTION "dxBlock" : VOID
VAR
retValRead : WORD;
retValWrite : WORD;
publishedInput : DWORD; // status, counter, etc.
outputToSlave : DWORD; // command, setpoint, etc.
linkOk : BOOL;
END_VAR
BEGIN
// Read the published input with consistency check
retValRead := DPRD_DAT(LADDR := W#16#64, RECORD := publishedInput);
// LADDR = 100 decimal = 0x64
IF retValRead = W#16#0 THEN
linkOk := TRUE;
ELSE
linkOk := FALSE;
publishedInput := 16#DEADBEEF; // sentinel value
END_IF;
// Write to the IM151-7 if link OK, otherwise force substitute
IF linkOk THEN
retValWrite := DPWR_DAT(LADDR := W#16#C8, RECORD := outputToSlave);
ELSE
outputToSlave := 16#00000000; // safe state
retValWrite := DPWR_DAT(LADDR := W#16#C8, RECORD := outputToSlave);
END_IF;
END_FUNCTION
Counter-Based Link Supervision on the IM151-7
The IM151-7 itself can be configured to publish an internal counter to the S7-400 and to subscribe to a counter published by the S7-400. The supervision principle is straightforward: an incrementing counter proves both the publisher and the consumer are alive and the data path is intact. field reports used this technique to detect breaks from both ends.
Implementation steps:
- Declare a 32-bit counter
cnt_localin a DB on each CPU. - Add the counter to the transfer area published by the IM151-7 to the S7-400 (4 bytes, consistency "Total length").
- Add a separate counter published by the S7-400 to the IM151-7 in the reverse transfer area.
- In OB1 of each CPU, increment the local counter by 1 each cycle, wrap on overflow.
- On the consumer side, run a check that the subscribed counter changes within a time window (e.g. 5 OB1 cycles). If it does not change, set a
link_failflag and trigger the substitute value logic.
The counter approach is preferred over relying on OB86 alone because OB86 reports the bus state from the master's view only, while a frozen counter proves end-to-end data freshness.
Verification and Commissioning Tests
Before declaring the link production-ready, perform the following checks. Each test is designed to expose one of the three failure modes described above.
| Test | Procedure | Expected Result |
|---|---|---|
| Last-value test | Power both CPUs, set outputs to a non-zero pattern, unplug PROFIBUS connector from IM151-7 | S7-400 process image retains the pattern; OB86 fires with FLT_ID C4; link_ok goes FALSE |
| Substitute-zero test | Configure substitute value = 0, repeat the unplug | IM151-7 outputs go to 0 within the configured fail-safe window (default 100 ms) |
| Substitute-pattern test | Configure a 0xA5A5A5A5 pattern, unplug, observe with a logic analyzer on the IM151-7 output terminals | 0xA5A5A5A5 visible on the bus within 100 ms |
| Master STOP test | Place S7-400 in STOP, observe IM151-7 outputs | Outputs go to substitute value (0, last, or pattern) as configured |
| Slave STOP test | Place IM151-7 in STOP, observe S7-400 published inputs | Inputs freeze at last value (if read via PI) or go to 0 (if read via SFC14 on failure) |
| Counter test | Publish a free-running counter from IM151-7, watch on S7-400 HMI tag | Counter increments; pulling the connector halts the counter within the bus timeout |
| Recovery test | Reconnect the PROFIBUS connector, restart the IM151-7 | OB86 fires the "leaving" event; link_ok returns TRUE; published data resumes; counter resumes |
Document the observed timing in the FAT/SAT protocol. The fail-safe window of 100 ms is the S7 default but is configurable to as low as 10 ms in HW Config when the application demands faster reaction.
Common Pitfalls and Field-Proven Caveats
Migrating to PROFINET IRT Direct Data Exchange
For new designs Siemens now recommends PROFINET IO with IRT and the equivalent "Direct Data Exchange" mechanism. The configuration in TIA Portal V20 for S7-1500 requires STEP 7 V16 or higher, but the conceptual model — publisher, subscriber, transfer areas with consistency settings, substitute values, and OB82/OB86 diagnostics — is identical to the PROFIBUS version described above. The TIA Portal direct data exchange configuration guide documents the procedure in detail. Existing S7-400 + IM151-7 sites can be migrated by replacing the IM151-7 with an IM151-7 PN (6ES7151-7BA00-0AB0) and configuring the publisher/subscriber relation as a PN IO device relation.
When the PROFIBUS link between an S7-400 master and IM151-7 is lost, do the exchanged inputs and outputs hold their last value?
Inputs on the S7-400 typically hold the last value when read through the process image, but zero out if read directly via SFC14 on a fault. Outputs to the IM151-7 follow the configured substitute-value strategy: 0, last value, or a configured replacement pattern, applied within the fail-safe window (default 100 ms, configurable down to 10 ms in HW Config).
Which OBs should I program to detect the failure of the IM151-7 link?
Program OB86 (DP station failure, primary indicator), OB82 (diagnostic interrupt from the IM151-7), OB85 (program execution error from I/O update failure), and OB122 (I/O access error on direct peripheral reads). OB86 alone is the minimum for clean detection without S7 STOP.
How can the IM151-7 know that the S7-400 has stopped or the link is broken?
Use a free-running 32-bit counter published from the S7-400 to the IM151-7. If the counter stops incrementing for more than the fail-safe window, the IM151-7 application should treat the exchanged data as invalid. Combine this with a flag set in OB86 of the S7-400 for a complete end-to-end check.
What is the difference between Direct Data Exchange and standard DP I/O?
Standard DP I/O requires the master class 1 to read or write each slot on the slave explicitly. Direct Data Exchange (cross-traffic) lets a slave publish slots so that a peer master receives them without an explicit read request, reducing bus load and cycle time. The wire format is identical; the difference is the master-slave relation in HW Config and the slots marked for "slave-to-slave communication".
Can I configure the S7-400 to substitute a specific pattern instead of zero on link loss?
Yes. The substitute value is configured per transfer area on the IM151-7 DP-slave properties tab in HW Config. For application-level substitution on the S7-400, use SFC14 with a wrapper that checks the RET_VAL and writes a local substitute pattern on W#16#80xx errors. This is the recommended pattern for TIA Portal V16 and later projects.
Does the S7-400 STOP when the IM151-7 fails if I have no OB86 loaded?
On S7-400 CPUs with firmware V5.x or higher, OB86 is enabled by default, so a missing OB86 does not cause a STOP. However, if application code performs a direct peripheral access (L PEW) to a vanished slot, OB122 will fire and STOP the CPU unless OB122 is also loaded. Always load OB82, OB85, OB86, and OB122 with at least a BE instruction for resilient behavior.