Configuring Ignition Tag History Deadband Style for Step Trends

Patricia Callen6 min read
B&R AutomationOther TopicTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

When an Ignition report chart draws sloped lines between logged values, the tag history is being handled as analog. The sloped line appears even when Sample Mode is set to on-change, and you usually want a stepped trace that holds each value until the next change. Float and Double tags default to the Analog Deadband Style, and the historian and chart interpolate between analog points. Change the Deadband Style on the tag to Discrete, then check the trend on data that was recorded after the change.

What is the chart actually showing you?

Look at the trend first. Compare the sloped trace with the value the tag held at each moment. On-change logging stores a row only when the value moves by more than the deadband. With Analog style, the chart joins two stored points with a straight line. For a value that jumped instantly, such as a setpoint, a mode value, or a recipe parameter, that line shows intermediate values the tag never held. With Discrete style, the chart holds the last stored value flat and draws a vertical edge when the next row arrives. This is the stepped trace most engineers expect from a setpoint.

"Point to point" can mean either shape, so settle which one you want before you change anything:

  • Stepped (sample-and-hold): the tag represents a value that changes instantly, such as a setpoint, count, state, or operator entry. Use Discrete.
  • Straight lines between samples: the tag represents a continuous process variable, such as a temperature, pressure, or level. Keep Analog, which is the correct model for it.

Why does an on-change Float tag trend as a ramp?

Sample Mode and Deadband Style are separate settings that do different jobs. Sample Mode decides when the historian evaluates the tag. Deadband Style decides how the historian filters stored values and how queries reconstruct the values between stored rows.

The Deadband Style property has three options:

  • Auto resolves to Analog for Float and Double data types and to Discrete for the other types.
  • Analog treats the value as continuous. Its deadband compression evaluates the shape of the trend, and retrieval interpolates linearly between stored points.
  • Discrete stores a value when it leaves the deadband around the last stored value. Retrieval holds that value until the next stored row.

A Float setpoint therefore inherits analog behaviour by default, so an on-change setting alone does not produce steps. Tuning does not fix a model mismatch. The chart renders what the query returns, and the query returns what the Deadband Style tells it to reconstruct.

Which signal in the chain is producing the wrong shape?

Trace the signal from the tag through the historian and the report query to the chart before you change any settings.

Signal Where it is set Symptom when wrong
Deadband Style Tag > History properties Sloped ramps between setpoint changes (Analog/Auto on a Float or Double tag)
Sample Mode Tag > History properties Periodic logging creates flat runs of duplicate points and can miss short excursions
Deadband value Tag > History properties Small changes never reach the database, so steps are missing or merged
Min/Max time between samples Tag > History properties Rapid changes are suppressed, or no point is written for long stretches
Query sample size / aggregation Report Tag Historian Query data source Interval-based averaging smears steps into ramps even with Discrete storage
Chart series renderer Report chart component Correct data drawn as connected lines; this changes only the drawing, not the data

How do you switch the tag to discrete trending?

  1. In the Designer Tag Browser, open the tag editor for the Float or Double tag that should trend as steps.
  2. Under History, confirm History Enabled is true and the correct storage provider is selected.
  3. Change Deadband Style from Auto or Analog to Discrete.
  4. Check the Deadband and Deadband Mode settings. For a setpoint, use a deadband of zero or one smaller than the smallest meaningful change, so every real change is stored.
  5. Keep Sample Mode set to on-change for event-type values. Set a maximum time between samples if you need a periodic confirmation point during long flat periods.
  6. Save the tag. Apply the same change to any UDT definition that drives the tag, or a later UDT edit will overwrite the instance setting.
  7. In the report, open the Tag Historian Query data source. Use raw or as-stored retrieval instead of an interval with an average aggregation, because averaging across a step recreates a ramp.

How do you verify the trend is correct?

  1. Write a known sequence to the tag, for example three distinct values a few minutes apart, and record the times.
  2. Preview the report over a time range that contains only data recorded after the setting change.
  3. Each value should run flat and change with a vertical edge at the recorded write time. There should be no diagonal between two different values.
  4. Compare against a Designer Easy Chart or Power Chart on the same tag. If the Designer chart shows steps but the report does not, the problem is in the report query or chart settings, not the tag.
  5. Check that the number of stored rows matches the number of writes. Too few rows means the deadband or minimum-time setting is filtering changes.

What goes wrong after the change?

  • Old data still ramps. Test on data recorded after the edit before you conclude the change failed. Trending history that spans the change can mix the old and new behaviour.
  • Discrete applied to real process variables. A temperature logged as discrete with a coarse deadband shows false plateaus and sudden jumps. Apply Discrete only to values that actually change in steps.
  • UDT overrides. An instance-level change silently reverts when the parent definition is edited. Make the change in the definition.
  • Report aggregation. Interval sampling with averaging makes steps look like ramps regardless of the storage style. Check the query before you blame the tag.
  • Renderer-only fixes. Changing the chart's line style hides the symptom in one report. Other trends and history queries still interpolate until you change the tag setting.

FAQ

Does setting Sample Mode to on-change make an Ignition trend stepped?

No. Sample Mode controls only when the historian evaluates and stores a value. The stepped shape comes from setting Deadband Style to Discrete, which Float and Double tags do not use by default.

Can I keep Analog style and get steps only in the report?

Only by changing how the report chart draws the series, which leaves the stored data and other trends interpolated. For values that genuinely change in steps, fix the tag's Deadband Style so every consumer of the history sees the same shape.

Can I get help if the chart still ramps after switching to Discrete?

Check that the test range contains only post-change data, that the Designer chart shows steps, and that the report query uses raw retrieval without averaging. If all three checks pass and the report still interpolates, stop changing settings. Export the tag configuration and the report, note your Ignition version, and open a case with Inductive Automation support.

Back to blog