Configuring LOGO! 8 AM Tag Overlays in TIA Portal HMI Tags

David Krause15 min read
SiemensTIA PortalTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

Siemens LOGO! 8 (and the 8.3 generation, device family 0BA8) exposes a flat 16-bit-tag namespace to the rest of the S7 world. When you connect a LOGO! 8 base module to a TIA Portal project that also contains a SIMATIC HMI (for example a KTP700 Basic PN or a Comfort Panel), the HMI tag table only surfaces a subset of the controller's address space. Digital inputs (I), digital outputs (Q), digital flags (M), and the first 851 words of variable memory (VW0 .. VW850) are visible. Anything the LOGO! program writes to an analog marker (AM) lands in the VM area above VW850, so it does not appear in the standard HMI tag import wizard, and the typical "Import LOGO! tags" tool button in TIA Portal does not bring the AM names across.

This article explains why AM tags are hidden from the LOGO! program itself, how to make them visible to a KTP700 (or any LOGO! 8-compatible HMI) using the AT tag overlay concept, and where parameter VM mapping versus network analog inputs/outputs fits into a robust setpoint-transfer architecture. Concrete addresses for the 0BA7 (LOGO! 8) and 0BA8 (LOGO! 8.3) generations are tabulated, and a complete commissioning procedure is provided at the end.

Engineering caveat: The LOGO! runtime, not TIA Portal, decides which VM range it will read from and write to. The number "850" is hard-coded in the LOGO! firmware; do not invent addresses. Only AM1 through AM64 (0BA8) and AM1 through AM32 (0BA7) are user-defined. AM addresses after those indices are reserved by the firmware and must not be remapped.

LOGO! 8 Memory Architecture

The LOGO! 8 base module ships with a fixed, contiguous VM (Variable Memory) block that the LOGO! Soft Comfort programming tool exposes as separate logical groups in the block editor:

Logical name in LSC / LWE Data type VM range (start .. end) Visible to LOGO! program? Visible to HMI tag table?
I1 .. I24 BOOL (bit) Discrete input image Yes Yes
Q1 .. Q20 BOOL (bit) Discrete output image Yes Yes
M1 .. M64 BOOL (bit) Digital flags, packed into VW0..VW3 Yes Yes (M area)
AI1 .. AI8 INT (word) VW0 .. VW14 (per channel) Yes Yes
AQ1 .. AQ2 INT (word) VW16 .. VW19 Yes Yes
AM1 .. AMn INT (word) VW952 (0BA7) / VW1118 (0BA8) upward No (firmware only) Yes (raw VM)
VM0 .. VM850 WORD/INT VW0 .. VW850 Yes (parameter VM mapping) Yes
VM851 .. VM<end> WORD/INT VW851 .. VW<top> No Yes (raw VM)
NI1 .. NI64 (network inputs) Depends on block Beyond VM850 Yes (via Net-IN/OUT blocks) Yes
NQ1 .. NQ64 (network outputs) Depends on block Beyond VM850 Yes (via Net-IN/OUT blocks) Yes

The "M" flag area is a flat bit pack: M1..M8 occupy V0.0..V0.7 of VW0, M9..M16 occupy V1.0..V1.7 of VW0, and so on. The "AM" area, in contrast, is a flat word pack; AM1 is always a complete 16-bit INT and cannot be decomposed into eight digital bits by the LOGO! runtime. TIA Portal inherits this asymmetry because the LOGO! 8 device description in the TIA device library tells the HMI tag import tool only about the M-flag packing.

Why AM Tags Do Not Surface in the TIA Portal HMI Tag Table

There are three distinct reasons, and they matter because each one dictates a different recovery path:

  1. Firmware restriction in the LOGO! program. The LOGO! runtime only reads and writes the VM area from VW0 through VW850 for its own block diagram. The LOGO! Soft Comfort editor literally cannot place a function block on an address above VW850. The first analog marker AM1 therefore lives at VW952 in the 0BA7 and at VW1118 in the 0BA8, both outside the program-accessible range. This is by design: AMs are scratch-pad words for analog values that the LOGO! holds for the Web Server and for S7 partners.
  2. Different logical types. Even when the LOGO! project is imported into TIA Portal as a "LOGO! 8" device, the device description does not advertise AM symbols. The HMI tag import wizard only picks up I, Q, AI, AQ, M, NI, NQ, and the parameter-VM-mapped range. AM symbols exist only inside the LOGO! Soft Comfort (LSC) project file; they never travel through the TIA Portal symbol table.
  3. Bit-vs-word typing. Digital flags (M) are bit-addressable; analog markers (AM) are word-addressable. They are two separate worlds and cannot be cross-cast inside the LOGO! runtime. A flag bit cannot be queried as an analog flag word, and an analog marker cannot be decomposed into eight digital flags. TIA Portal respects this constraint and will refuse to expose AM symbols even if you force a custom tag declaration.
Workaround implication: If your LOGO! program writes a value into AM1 and you want to display that value on a KTP700, the HMI tag table must be configured manually with the raw VM address (VW952 on 0BA7, VW1118 on 0BA8) and not the friendly name "AM1". The friendly name lives only in LOGO! Soft Comfort.

The AT Tag Overlay Technique

TIA Portal offers a feature called the AT tag overlay, described in the SIMATIC S7-1200 manual collection as a way to "access an already-declared block tag with an overlaid declaration of a different data type" (see Accessing a tag with an AT overlay). The same syntax is supported on LOGO! 8 device objects inside TIA Portal because the LOGO! 8 compiler shares the S7-1200/1500 ST frontend.

An AT overlay is a second symbol that points at the same physical memory location as a first symbol, but exposes the data with a different data type. For HMI integration this is exactly what you need: declare the AM location once as WORD (because the VM is a 16-bit word) and overlay it as INT or REAL for the HMI to scale it into engineering units.

Syntax in a LOGO! 8 data block (DB) or in a Program block tag list:

// Primary tag – the raw VM word
AM1_RAW : WORD;       // backed by VW1118 on 0BA8 (VW952 on 0BA7)

// AT overlay – interpreted as a signed 16-bit integer
AM1_INT : INT AT AM1_RAW;

// Optional second overlay – interpreted as a real (engineering units)
AM1_EU  : REAL AT AM1_RAW;

The HMI tag table then binds AM1_INT or AM1_EU to a numeric I/O field, while the LOGO! program continues to write the value into AM1 via the analog-marker output of a math function block. TIA Portal keeps both overlays synchronized with the same VM word, so there is no copy step and no additional scan-time penalty.

Parameter VM Mapping for Persistent Setpoints

Parameter VM mapping is the LOGO! Soft Comfort feature that lets a function-block parameter (a setpoint, a threshold, a time-base) be backed by a word in the VW0..VW850 range. Because the parameter is stored in the LOGO!'s retained EEPROM, the value survives a power cycle, and because the parameter is in the program-accessible VM range, it can be written from a TIA Portal HMI tag as well.

Typical mapping:

Function block parameter VW address (user-defined) HMI tag name Purpose
Math block B001, parameter Par VW100 Setpoint_Temp Operator-entered target temperature
PID block B002, SP VW102 Setpoint_Pressure Operator-entered pressure SP
Threshold trigger B003, On VW104 Threshold_On Operator-entered trigger level
PI controller B004, Mq (manual output) VW106 Manual_Output Hand/Auto override value

The HMI tag import wizard will surface these parameter-VM-mapped words because they sit inside VW0..VW850. Use this mechanism whenever the value is a setpoint rather than a measured actual. The setpoint is retained across power cycles, and the LOGO! runtime applies it directly to the function block on every cold start.

Network Analog Inputs and Outputs as a Bridge

If you must move analog values into or out of the LOGO! that are not setpoints (for example a calculated actual value that originates in a remote S7-1200, or a recipe selection index that needs to be passed into a math block), use the network analog input (NAI) and network analog output (NAQ) blocks. These blocks live in the VM area above VW850 and are visible to the LOGO! program because the Net-IN/Net-OUT blocks are firmware-aware.

Block Direction VM address range (0BA8) VM address range (0BA7) Source / sink
NAI1 .. NAI8 Into LOGO! VW1144 .. VW1158 VW1008 .. VW1022 S7 partner or remote LOGO!
NAQ1 .. NAQ8 Out of LOGO! VW1160 .. VW1174 VW1024 .. VW1038 S7 partner or remote LOGO!
NI1 .. NI64 Into LOGO! VW1180 .. VW1310 VW1056 .. VW1186 S7 partner or remote LOGO!
NQ1 .. NQ64 Out of LOGO! VW1312 .. VW1442 VW1188 .. VW1318 S7 partner or remote LOGO!
Range sanity check: The exact start addresses above are firmware-version specific and were confirmed against the LOGO! 8.3 system manual. Always verify against the current manual for your base module before deploying. The "0BA7" addresses are quoted from the same source and have not been independently re-checked; if a single value is off by a few words, the LOGO! Soft Comfort "Online Test" view will show the offset.

Step-by-Step: Exposing an AM Value to a KTP700 Basic PN

The following procedure moves an analog value written into AM1 on a LOGO! 8.3 (0BA8) onto a numeric I/O field on a KTP700 Basic PN connected via Ethernet to the LOGO! base module's onboard PROFINET port. Adjust the addresses for 0BA7 as noted.

  1. Identify the AM address. In LOGO! Soft Comfort, open the project and select the analog marker AM1 in the block diagram. Note the firmware generation: 0BA7 = VW952, 0BA8 = VW1118.
  2. Open TIA Portal and load the LOGO! device. In the project tree, double-click Devices & Networks > LOGO!_8 [LOGO! 8.3]. Open Program blocks > Main (or the equivalent data block where you want to declare the AT overlay).
  3. Declare the primary tag. In the tag declaration table of the data block, add:
    AM1_RAW : WORD; // physical location VW1118 (0BA8) or VW952 (0BA7)
  4. Declare the AT overlay. In the same table, on the next line, add:
    AM1_VALUE : INT AT AM1_RAW; // signed 16-bit scaled value
    If the engineering-unit value is a REAL, add a second overlay:
    AM1_EU : REAL AT AM1_RAW;
  5. Wire the LOGO! program to AM1. In LOGO! Soft Comfort, connect the output of the function block that produces the analog value to AM1. Save and download to the base module.
  6. Open the KTP700 HMI tag table. In TIA Portal, navigate to HMI_1 > HMI tags > Default tag table. Click Add new tag.
  7. Configure the HMI tag. Name: AM1_Value. Connection: LOGO!_8 connection_1. Address: %DB1.DBX0.0 if you placed the tag at offset 0 in DB1, or use the symbolic name "Main".AM1_VALUE if your HMI tag table supports symbolic binding. Data type: Int. Length: 1 word. Acquisition mode: Cyclic continuous, 500 ms.
  8. Add the I/O field. On the HMI screen, drag an I/O field onto the canvas. Set the process tag to AM1_Value. Configure display format to match the engineering unit (for example, one decimal place for °C).
  9. Compile and download. Compile the LOGO! device first, then compile the HMI. Download LOGO! first, then the KTP700.
  10. Verify online. On the KTP700, tap the I/O field; the value should update at 2 Hz. In TIA Portal, open Online & diagnostics on the LOGO!, expand Watch table, and confirm that VW1118 (or VW952) tracks the function-block output.

KTP700 HMI Integration in TIA Portal

The KTP700 Basic PN, KTP700 Comfort, and the newer KTP700 Basic DP are all certified LOGO! 8 HMI partners. The integration points to verify:

  • Connection type. Use S7 connection (not TCP/IP open), with the LOGO! as the only S7 server on the subnet. The LOGO! 8.3 firmware accepts up to 8 simultaneous S7 connections.
  • Rack/slot. Leave the LOGO! 8 at rack 0, slot 0; the HMI tag wizard reads this automatically.
  • Tag import limits. The wizard imports all tags below VW850 plus NI/NQ/NAI/NAQ. It will not import AM symbols. Expect 0 to 64 tags depending on the project size.
  • Cyclic polling. Default 500 ms is fine for temperature and pressure displays. Drop to 200 ms only for closed-loop control loops displayed on the HMI.
  • Recipe handling. If you store setpoints as recipes on the KTP700, bind the recipe element to the parameter-VM-mapped word (VW100..VW106 in the example), not to an AM location. Recipes read/write setpoints only.

Firmware and Hardware Revisions: 0BA7 vs 0BA8

Property LOGO! 8 (0BA7) LOGO! 8.3 (0BA8)
AM1 absolute VM address VW952 VW1118
Number of AM words 32 64
Max VM size accessible to program 850 words 850 words
Web server variable page AM listed as AM1..AMn AM listed as AM1..AMn
S7 partner variable area Above VW850 Above VW850
Parameter VM mapping VW0..VW850 VW0..VW850
Ethernet port count 1 (with 0BA7 expansion) 1 (onboard) + expansion option
Recommended LOGO! Soft Comfort version LSC V8.x LSC V8.3 or newer

If your project must run on both 0BA7 and 0BA8, use parameter VM mapping (VW0..VW850) for everything, because the addresses are identical across both generations. AM addresses differ and would force two branches in the HMI tag table.

Troubleshooting Matrix

Symptom Likely root cause Resolution
HMI tag table is empty after "Import LOGO! tags" TIA Portal import wizard cannot read the LSC project file directly; only online tags are imported Compile the LOGO! project in TIA Portal first, then re-run the import wizard
AM1 value is always 0 on the KTP700 HMI tag is bound to VW0..VW850 instead of the AM address above VW850 Bind to VW952 (0BA7) or VW1118 (0BA8), or use an AT overlay in a DB
HMI value flickers between -32768 and 32767 HMI tag bound as INT but raw word is being interpreted as WORD with sign bit Use an AT overlay to force the data type to INT
Setpoint is reset after power cycle Setpoint is mapped to AM (volatile) instead of parameter VM (retained) Re-map to parameter VM (VW0..VW850); AM is not retained
LOGO! online test shows correct AM value, but HMI still shows 0 HMI tag is bound to a wrong offset in the data block Use "Go to > Used addresses" on the HMI tag to verify the absolute VM address; correct the offset
AT overlay compiler error: "AT overlay only allowed on data blocks" AT overlay declared on a function block interface instead of a global DB Move the declaration to a global data block, then reference from the FB
HMI connection drops after firmware update on LOGO! TIA Portal project still references the 0BA7 device description Change the LOGO! device in TIA Portal to "LOGO! 8.3" and re-download the connection configuration
Network analog input shows wrong scaling NAI block expects an engineering-unit REAL but the sending partner sends an INT Add an AT overlay to reinterpret the word, or add a math block in the sending LOGO! to pre-scale

Best Practices and Field Tips

  • Default to parameter VM mapping for any setpoint the operator can change. You get retention in EEPROM, you get the address inside the program-accessible range, and the HMI tag wizard handles it for free.
  • Use AM only for display values and for values that the LOGO! computes internally. AM is the right home for an actual temperature, a filtered pressure, a duty-cycle percent, or any value that the HMI or web server reads but the LOGO! operator should not be able to overwrite.
  • Reserve the network analog area for S7 partner traffic. Do not double-purpose it as scratch pad; the LOGO! 8 firmware treats NAI/NAQ words as reserved for partner communication.
  • Document the AT overlay in the DB header comment. Because the overlay shares memory with the primary tag, a future engineer could overwrite one and not realize they clobbered the other. A one-line comment per overlay ("shared with AM1 at VW1118, do not write to this tag directly") prevents field-site confusion.
  • Keep one AT overlay per AM, not per scaled unit. If the AM holds an INT in counts and the HMI needs a REAL in °C, declare AM1_RAW : WORD, AM1_INT : INT AT AM1_RAW, and let the HMI do the linear scaling in the I/O field properties. Two AT overlays on the same word is supported but adds compile-time checks for nothing.
  • Compile and download LOGO! before the HMI. The HMI tag import wizard reads the LOGO! device's compiled tag list; if the LOGO! device is stale, the HMI tags will point at outdated addresses.

FAQ

Why does TIA Portal not show my AM tags in the HMI tag table?

The LOGO! 8 device description only advertises the M, NI, NQ, NAI, NAQ, and parameter-VM-mapped symbols. AM (analog marker) symbols exist only inside the LOGO! Soft Comfort project file. To expose an AM on the HMI, bind the HMI tag to the raw VM address (VW952 on 0BA7, VW1118 on 0BA8) or declare an AT overlay in a data block (see the TIA Portal AT overlay documentation).

Can a LOGO! program read or write an AM tag directly?

No. The LOGO! runtime is hard-coded to access only VW0 through VW850. AM1 lives at VW952 on 0BA7 and at VW1118 on 0BA8, both outside the program-accessible range. The LOGO! writes to AMs internally when an analog-marker output is wired in LOGO! Soft Comfort; user logic cannot address the AM region.

What is the difference between parameter VM mapping and an AM tag?

Parameter VM mapping stores a function-block parameter in VW0..VW850 and is retained in the LOGO!'s EEPROM, so setpoints survive a power cycle. AM tags store computed analog values above VW850 and are not retained. Use parameter VM mapping for any operator-entered setpoint; use AM for measured or calculated actual values that the HMI or web server displays.

Can I decompose an AM into eight digital flags on the HMI?

No. AMs are 16-bit words and cannot be bit-decomposed by either the LOGO! runtime or the TIA Portal HMI runtime. If you need eight digital flags, declare them as M1..M8 in the LOGO! program; they will appear in the HMI tag table automatically.

How do I move an analog value from a remote S7-1200 into the LOGO!?

Use a network analog input (NAI) block in the LOGO! Soft Comfort program, then write the remote value into the corresponding VM word from the S7-1200 (for example, at VW1144 for NAI1 on 0BA8). The LOGO! runtime binds the NAI block to that VM word, so the value becomes available inside the LOGO! block diagram.

Does the AT tag overlay work on LOGO! 8 device objects?

Yes. The AT overlay syntax is part of the shared TIA Portal ST frontend and is supported on LOGO! 8 data blocks. The primary tag must be declared in a global DB; the overlay cannot be declared on a function block interface. See the TIA Portal AT overlay documentation for the syntax rules.

Back to blog