Integrating SITRANS Probe LU HART Signal with Siemens S7-300 AI

David Krause16 min read
S7-300SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Description: Incorrect PLC Readings from a HART Loop-Powered Level Transmitter

A field engineer reports a recurring integration problem between the SITRANS Probe LU240 (and the original SITRANS Probe LU) ultrasonic level transmitter and a Siemens SIMATIC S7-300 PLC. The transmitter is configured for volume measurement, and the on-board LCD of the Probe LU correctly displays the engineered volume in cubic meters, liters, or gallons depending on the vessel curve selected. The 4–20 mA loop is wired to a standard SIMATIC S7-300 analog input module (an AI8 × 13-bit, type 6ES7331-1KF02-0AB0 or similar), and the raw count is scaled in the CPU with the standard "Scale" function (FC105 in STEP 7). Despite the LCD being correct, FC105 outputs erratic, drifting, or systematically biased values.

This is not a transducer fault, not a programming fault in the strict sense, and not a wiring polarity issue. The root cause is that a standard (non-HART) S7-300 AI module does not provide a low-impedance, HART-compliant loop interface. When the Probe LU is operated in HART mode, the module's input impedance, common-mode filtering, and lack of HART band-pass filtering distort the 4–20 mA analog signal that rides on top of the HART carrier. The transducer itself is fine — the analog acquisition path is wrong for the chosen device.

Field note: If the LCD on the Probe LU is correct but the PLC is wrong, the problem is almost always on the analog acquisition side, not in the SITRANS Probe LU itself. Do not re-range or re-zero the transmitter until the input module has been qualified.

Root Cause: HART Carrier on a Non-HART Analog Input

The SITRANS Probe LU operating instructions specify a 2-wire, loop-powered 4–20 mA output with optional HART 7 communication. HART (Highway Addressable Remote Transducer) superimposes a 1.2 kHz / 2.2 kHz FSK signal at ±0.5 mA on the 4–20 mA DC loop. For a HART master to communicate, the loop must present a total impedance of 230–600 Ω at the HART frequencies, and the analog input of the receiving device must not shunt or filter out the HART band.

Standard S7-300 SM331 modules such as:

  • 6ES7331-1KF02-0AB0 (AI8 × 13 bit)
  • 6ES7331-7KB02-0AB0 (AI2 × 14 bit)
  • 6ES7331-1KF01-0AB0 (AI8 × 13 bit, earlier revision)

are designed for clean 4–20 mA or ±10 V signals. Their input stages include filtering that attenuates the HART band, and their loop impedance is not characterized for HART communication. According to the Siemens Industry Online Support FAQ entry 27839768 ("What should you watch out for when using HART measuring transducers in conjunction with S7-300 analog input modules that do not support HART signals?"), HART transmitters connected to non-HART SM331 modules can:

  1. Read systematically low because the module's input current is reduced by the HART coupling network.
  2. Read high with overshoot or oscillation when the HART multidrop poll occurs (HART burst mode).
  3. Read with increased noise when the long cable acts as an antenna in industrial environments.
  4. Be unable to communicate with a HART handheld (375/475, FMR, or SITRANS MDS) unless a 250 Ω HART communicator resistor is added and the module is bypassed.

FC105 (the standard scale block in STEP 7 / STEP 7 V5.x) is not the source of the error. FC105 simply converts an integer (-27648 to +27648 for the unipolar 4–20 mA range) to a floating-point engineering value. If the raw input count is wrong because the HART signal is being attenuated or rectified by the module, FC105 faithfully produces a wrong engineering value. The scale block cannot fix a corrupted input.

Solution Path: Use a HART-Capable AI Module or Decouple the HART Layer

There are three proven solutions, in order of preference for new installations.

Solution 1: Replace the SM331 with a HART-Capable SM331 in ET 200M

The cleanest fix is to swap the non-HART AI8 for the HART-capable 6ES7331-7TF01-0AB0 (AI8 × 31 bit HART) in an ET 200M distributed I/O station. The module is documented in the Siemens manual SIMATIC ET 200M distributed I/O HART analog modules (entry 22063748).

Table 1. Comparison of standard SM331 vs. HART SM331 modules
Feature Standard SM331 (e.g. 6ES7331-1KF02) HART SM331 6ES7331-7TF01-0AB0
Resolution 13 bit 16/31 bit (2- / 4-wire mode)
Number of channels 8 8 (configurable 2/4-wire)
HART support No Yes, HART rev. 5/6/7
Input impedance at HART band High, attenuates carrier Compliant 230–600 Ω
Channel diagnostics Wire break, overflow Wire break, overflow, HART status, PV/SV/TV/QV
Configuration in HW Config 4–20 mA, ±10 V, RTD, TC 4–20 mA + HART, with PV scaling
Recommended for Probe LU No (works only if HART is disabled in Probe LU) Yes

The HART module 6ES7331-7TF01-0AB0 provides transparent HART pass-through to the PLC program. With the PDM (Process Device Manager) routing through PROFINET or PROFIBUS, the user can read primary variable (PV = level), secondary variable (SV = distance), tertiary variable (TV = volume), and quaternary variable (QV = temperature) directly from the Probe LU and still use the analog input for fast-loop control.

Solution 2: Add an External HART-to-Analog Isolator (Active Barrier)

If the S7-300 architecture must be retained and the slot cannot be changed, install an active HART isolator between the Probe LU and the SM331. Suitable products include:

  • Phoenix Contact MACX MCR-EX-SL – 2-wire HART transparent isolator
  • WAGO 857-980 – HART transparent signal conditioner
  • Siemens SITRANS I300 – universal HART isolator / repeater

The isolator provides the 250 Ω HART termination, presents a clean 4–20 mA signal to the SM331, and supplies loop power if the transmitter is not loop-powered from the PLC side. The Probe LU remains HART-communicable with a 475 handheld across the isolator.

Solution 3: Disable HART in the Probe LU (Short-term only)

If the customer accepts losing HART diagnostics and remote configuration, set the Probe LU output to 4–20 mA only (HART multidrop = 0, burst mode off). The transmitter then emits a clean DC loop signal, and a standard 6ES7331-1KF02-0AB0 will read correctly. This is acceptable for simple level-only applications but removes the ability to do remote PV/SV reading, range changes, echo profile diagnostics, and Bluetooth configuration (Probe LU240 with Bluetooth option). Use this only when no future HART integration is planned.

Prerequisites Before Re-Wiring

  1. Verify the Probe LU firmware and configuration by reading the on-board LCD; the value in the loop-test mode must match an independent reference (hand-held ultrasonic or manual tape measurement).
  2. Read the Probe LU order code and confirm whether the unit has HART (option H) or HART with Bluetooth (option BT). The Bluetooth option is only available on the Probe LU240 family.
  3. Identify the existing S7-300 module order number on the door label (the 6ES7 MLFB on the right side of the module).
  4. Pull the STEP 7 hardware configuration and confirm whether the module is configured as 4-wire current, 2-wire current, or voltage. A Probe LU is a 2-wire loop-powered device and must be configured as "2-wire current" (4DMU in HW Config) for a standard SM331, or as "4DMU HART" for the 6ES7331-7TF01-0AB0.
  5. Measure loop voltage at the Probe LU terminals. Loop voltage must be ≥ 12 V DC (Probe LU needs 12–30 V DC for the 4–20 mA/HART output). Anything below 12 V at the transmitter terminals indicates cable resistance is too high or the PS 305/PS 307 power supply is undersized.

Step-by-Step: Wiring and Configuring the HART SM331 (Recommended Path)

The following procedure assumes the user has STEP 7 V5.5 (or TIA Portal with S7-300 compatibility) and an ET 200M interface module such as 6ES7153-1AA03-0XB0 (IM153-1) on PROFIBUS DP.

Step 1 — Mechanical Installation

  1. Power down the ET 200M station.
  2. Remove the existing non-HART SM331 from the slot. Place a blank cover (6ES7393-4AA00-0AA0) over the unused slot if the module is relocated.
  3. Insert 6ES7331-7TF01-0AB0 into the same slot. Tighten the two front-screws to 0.8 Nm.
  4. Open the front cover and note channel 0–7. Connect the Probe LU positive lead to terminal In+ and the negative lead to terminal In–. With a 2-wire Probe LU the shield is terminated at the module's shield bar, not at the Probe LU housing (to avoid ground loops).
  5. Add a 24 V DC supply to the module's power terminals (L+ and M).

Step 2 — STEP 7 Hardware Configuration

  1. Open the SIMATIC Manager and the S7 project.
  2. In HW Config, locate the ET 200M station and drag the SM331 AI8 HART (order 6ES7331-7TF01-0AB0) from the catalog to the correct slot.
  3. Double-click the module to open Properties. For each used channel set:
    
      Measurement type:    4DMU (4-wire transmitter with HART) or 2-wire HART (Probe LU)
      Output range:        4 … 20 mA
      HART:                Enabled
      Channel diagnostics: Wire break, Upper/lower limit, HART failure
  4. Save and compile the hardware configuration. Download to the CPU.

Step 3 — STEP 7 Program: FC105 with HART-correct Limits

For a HART SM331, the nominal input count is 0 to 27648 (unipolar) regardless of HART. However, the user can also access the digital HART variables in addition to the analog count. The recommended FC105 call for the analog count is:


  // ST (Structured Text) — STEP 7 V5.5
  // Inputs to FC105
      IN      := PIW 304;        // analog input word, channel 0
      HI_LIM  := 1.0E+02;        // engineering upper value, e.g. 100.0 % volume
      LO_LIM  := 0.0E+00;        // engineering lower value
      BIPOLAR := FALSE;          // 4–20 mA is unipolar
      RET_VAL := MD100;          // scaled result, REAL
      OUT     := MD104;          // duplicate output

  // Equivalent ladder: call FC105 with the same parameters.

If the HART module is being used to read the PV (level) directly in engineering units, the HART driver block (FB81 "HART_PV" for the older 6ES7331-7TF01, or the integrated HART driver in TIA Portal) returns the PV as a REAL. In that case FC105 is not required for the HART variable — but it remains correct for the analog count.

Step 4 — Verify Wiring Polarity and Loop Voltage

  1. With the CPU in RUN, force the Probe LU output to a fixed value using the local push buttons (menu 1.4 "Loop Test") to 4 mA, 12 mA, and 20 mA.
  2. At each setpoint, observe the PIW value in the STEP 7 Monitor/Modify table. PIW should step from 0 → 13824 → 27648 within ±2 counts.
  3. If the PIW is off by more than 1 %, check for a ground loop, swapped polarity, or a 250 Ω resistor in the loop that wasn't there before.

Verification: A Field Commissioning Checklist

Table 2. Commissioning verification for SITRANS Probe LU on a HART SM331
Step Action Expected Result Pass/Fail
1 Power on Probe LU, wait 30 s for echo acquisition LCD shows current level in m, mA output = 4–20 mA scaled to level —
2 Apply HART communicator (475/FMR) at the Probe LU terminals Communicates on PV, SV, TV, QV; serial number matches nameplate —
3 Set Probe LU loop test = 4.000 mA PIW = 0 ±2 —
4 Set Probe LU loop test = 12.000 mA PIW = 13824 ±2 —
5 Set Probe LU loop test = 20.000 mA PIW = 27648 ±2 —
6 FC105 output at 20 mA RET_VAL = HI_LIM —
7 FC105 output at 4 mA RET_VAL = LO_LIM —
8 Move level to 50 % of range by physical means PIW = 13824 ±0.5 %, FC105 RET_VAL = 50 % of HI_LIM —
9 Trigger HART burst mode from Probe LU Analog count unchanged; HART driver receives PV at 4 Hz —
10 Disconnect one wire at the Probe LU Module flags wire break (SF LED + diagnostic OB82) —

Parameter Reference: SITRANS Probe LU Output Settings

Table 3. Probe LU transmitter parameters relevant to the PLC interface
Menu Item Setting Effect on PLC Reading
1.1 Units m, cm, mm, ft, in, % Sets engineering unit; the loop current scaling must match this unit
1.2 Empty (0 %) Distance to surface at 4 mA Sets LO_LIM in FC105
1.3 Full (100 %) Distance to surface at 20 mA Sets HI_LIM in FC105
1.4 Loop Test 4, 12, 20 mA selectable Allows verification of PIW without changing level
2.1 Volume Units m³, L, gal, ft³ When on PV/SV/TV mapping, selects volume variable
2.2 Vessel Shape Linear, cylindrical, parabolic, custom Drives volume conversion; ensure PLC receives volume, not level
3.1 HART Polling Address 0 (default, point-to-point) 0 = analog + HART, 1–15 = multidrop, current fixed to 4 mA
3.2 Burst Mode Off / On If On, the HART SM331 must be in "4DMU HART" mode
5.1 Bluetooth Off / On (LU240 only) No effect on loop current; commissioning tool only

Important — Volume vs. Level mapping: When the SITRANS Probe LU is configured for volume, the loop current is still scaled to level (0 % empty, 100 % full). The volume conversion is performed internally and exposed on TV (tertiary variable) in HART. A user who wants volume in the PLC can either:

  1. Recompute the volume in the PLC from the linear level using the same vessel curve; or
  2. Read the HART TV (volume) directly through the 6ES7331-7TF01-0AB0 with FB81/FB101.

The local LCD on the Probe LU shows the configured primary variable, which can be level or volume depending on which is mapped to PV. Mismatches between LCD and PLC often originate here, not in the analog path.

Troubleshooting Matrix for SITRANS Probe LU + S7-300

Table 4. Symptom → Likely cause → corrective action
Symptom in PLC Likely Cause Corrective Action
Reading is 0.5–1.5 mA low Non-HART SM331 attenuates HART carrier and offsets DC level Replace with 6ES7331-7TF01-0AB0 or add HART isolator
Reading oscillates 2–4 % at 4 Hz Burst mode on, but module is not HART-capable Disable burst mode or upgrade to HART SM331
Reading is correct at 4 mA, wrong at 20 mA FC105 HI_LIM/LO_LIM does not match Probe LU range Re-enter HI_LIM/LO_LIM from menus 1.2/1.3
Reading is constant at 4 mA, full value Probe LU is in HART multidrop (address 1–15), current fixed to 4 mA Reset HART polling address to 0 via handheld
Reading is −27648 (underflow) Wire break or polarity reversed Check wiring; re-verify loop voltage ≥ 12 V at Probe LU
Reading is +27648 (overflow) Loop current > 22 mA, or short in field Disconnect field; measure mA at module input
Reading drifts with ambient temperature Cold-junction compensation or shield grounded at both ends Ground shield at module end only
Cannot reach Probe LU with 475 handheld No 250 Ω termination; SM331 input impedance too high Add 250 Ω resistor in series with loop; or use HART module
PIW reads 32767 (overflow diagnostic) Module configured for voltage; Probe LU provides current Change HW Config to "2-wire current 4–20 mA"
FC105 RET_VAL is always 0.0 BIPOLAR input set TRUE; integer underflow Set BIPOLAR := FALSE for 4–20 mA

Special Case: ET 200M vs. Central S7-300 Rack

The 6ES7331-7TF01-0AB0 HART module is mechanically a standard SM331 and can be installed in either a central S7-300 rack or an ET 200M distributed rack. The functionality is identical, but the diagnostic and configuration path differs:

  • Central S7-300: Configuration is in HW Config of the CPU; HART PDM uses the CPU's MPI/PROFINET interface.
  • ET 200M (IM153-1/-2): Configuration is in the same way, but HART PDM can be routed through the PROFIBUS or PROFINET interface module; multiple HART field devices can be serviced from a single PDM station.

For brown-field installations, the ET 200M option is the least disruptive: a new IM 153 plus a 7TF01 slot can be added next to the existing non-HART rack without changing the rest of the I/O.

Special Case: TIA Portal Migration

For users migrating from STEP 7 V5.x to TIA Portal, the 6ES7331-7TF01-0AB0 HART module is supported in TIA Portal V14 SP1 and later. The HART driver library "HART_PV" is replaced by the system block "HART_4AI" or "HART_8AI" depending on the firmware version. FC105 remains available as the scale block, or the user can use the TIA Portal "NORM_X" instruction. Scaling limits (HI_LIM, LO_LIM) and the analog PIW limits (0–27648 unipolar) are identical.

Safety and Functional Notes

Warning: In safety-instrumented systems (SIL 1/2/3) the SITRANS Probe LU is not the primary element; it is only suitable for non-SIL level indication. Do not place the PLC's reading of the Probe LU on a safety function. Use a dedicated safety transmitter such as SITRANS Probe LU240 with a separate safety PLC.
Caution: When connecting a HART handheld to a 4–20 mA loop that is also wired to an active SM331, the loop is powered from one source only. The HART handheld draws a small amount of current and will not affect the SM331 reading if the loop supply is 24 V and the SM331 input impedance is 250 Ω or less. With non-HART SM331 modules the loop impedance can be as high as 600 Ω, which causes additional 0.6 V drop; the Probe LU still operates above 12 V but the headroom for the handheld is reduced.

Summary of Recommended Module Mapping

Table 5. Quick reference: which S7-300 AI module to use for SITRANS Probe LU
Probe LU Mode Required SM331 MLFB HART Communicator Compatible?
HART (point-to-point, address 0) AI8 HART, ET 200M 6ES7331-7TF01-0AB0 Yes, full PV/SV/TV/QV
HART with external barrier Any SM331 (e.g. 6ES7331-1KF02-0AB0) Multiple Yes, across the barrier
4–20 mA only, HART disabled Any SM331, 2-wire current 4DMU Multiple No (HART disabled)
HART multidrop (address 1–15) AI8 HART, ET 200M 6ES7331-7TF01-0AB0 Yes, but analog current is fixed at 4 mA

FAQ

Why does the SITRANS Probe LU LCD show the correct volume but the S7-300 SM331 AI8*13 bit reads wrong through FC105?

The Probe LU scales the 4–20 mA loop to level (0 % empty, 100 % full) and performs the volume conversion internally for the LCD and for the HART TV variable. A standard non-HART SM331 such as 6ES7331-1KF02-0AB0 does not provide a HART-compliant loop interface, so the analog current the module sees is attenuated or shifted by the HART carrier. FC105 (or the equivalent NORM_X in TIA Portal) is not the cause — it faithfully scales whatever the input word delivers. Replace the module with the HART SM331 6ES7331-7TF01-0AB0 in an ET 200M station, add an external HART isolator, or disable HART in the Probe LU (menu 3.1, set polling address 0 and burst off, then the HART carrier stops).

Which S7-300 SM331 MLFB supports HART for the SITRANS Probe LU?

Use 6ES7331-7TF01-0AB0 (SM331 AI8 HART, 16/31 bit) installed in an ET 200M station. This module provides transparent HART pass-through and channel-level diagnostics, and is documented in the Siemens Industry Online Support entry 22063748.

Can I keep my existing non-HART SM331 and still read the Probe LU with a handheld programmer?

Yes, but only if you add a 250 Ω HART termination resistor in series with the loop and the Probe LU is configured for point-to-point (HART address 0). The handheld will communicate at the resistor terminals, but the analog reading at the SM331 will still be slightly offset because the module does not isolate the HART bandpass. For clean analog and HART reading simultaneously, the 6ES7331-7TF01-0AB0 is required.

What PIW value should FC105 expect at 4 mA, 12 mA, and 20 mA on a HART SM331?

Standard S7-300 unipolar scaling is 0 = 4 mA, 13824 = 12 mA, 27648 = 20 mA. Use FC105 with BIPOLAR := FALSE, LO_LIM := 0 (or the engineering value at 4 mA), HI_LIM := 100 (or the engineering value at 20 mA). For bipolar ranges (e.g., ±10 V or ±20 mA) the input count is -27648 to +27648 and BIPOLAR := TRUE.

Does the SITRANS Probe LU240 with Bluetooth option change the PLC wiring?

No. The Bluetooth option (Probe LU240 only) is a wireless commissioning interface. The 2-wire 4–20 mA/HART loop, terminals, voltage (12–30 V DC), and SM331 interface requirements are identical to the original SITRANS Probe LU. Follow the same module-selection and FC105 procedures described above.

Back to blog