1. Overview
The SIMOVERT MASTERDRIVES MC (Motion Control) family is a legacy Siemens three-phase AC drive platform that still appears in long-life industrial plants, paper machines, hoists, and crane retrofits. Integrating a MASTERDRIVES MC unit — for example MLFB 6SE7013-0EP50 — into a SIMATIC S7-300 station centered on a CPU 313C-2DP requires the correct PROFIBUS-DP slave description (GSD), a properly slotted communication board (CBP / CBP2), the right PPO telegram type, and consistent-data handling via SFC14 and SFC15. This reference covers all four layers using SIMATIC Manager V5.4 SP5 (or compatible) and the MASTERDRIVES Vector Control compendium, software release V3.32 and above.
The procedure applies to the MC compact and chassis variants. For software V3.32 or newer, the operating instructions are available in the Siemens IA/DT support portal as the "SIMOVERT MASTERDRIVES Vector Control" compendium PDF, which contains Section 8.2.3 describing the parameter-processing mechanism over PROFIBUS. The latest published revision can be downloaded from Siemens support entry 23658440 — SIMOVERT MASTERDRIVES Vector Control Operating Instructions (V3.32).
2. System Components and MLFB References
Match every component to its catalog number before commissioning. The items below are the minimum hardware/software set used in a working configuration.
| Component | MLFB / Version | Role |
|---|---|---|
| SIMOVERT MASTERDRIVES MC | 6SE7013-0EP50 (compact type A) | PROFIBUS-DP slave, closed-loop vector control |
| CBP communication board (slot G) | 6SE7090-0XX84-… (CBP) or 6SE7090-0XX84-2Axx (CBP2) | PROFIBUS interface, parameter channel, process data |
| SIMATIC S7-300 CPU | 6ES7313-6CE00-0AB0 (CPU 313C-2DP) | PROFIBUS-DP master, integrated DP port |
| SIMATIC Manager | V5.4 Professional SP5 (or SP3+ with HSP) | Engineering tool, HW Config, symbol editor |
| STEP 7 HSP for MASTERDRIVES | HSP from Siemens entry 23183356 | Masterdrive slaves in HW Config catalog |
| Masterdrive GSD | SIEM80F1.GSD (CBP) or SI0180F1.GSD (CBP2) | PROFIBUS-DP slave description file |
| Firmware baseline (drive) | V3.32 or higher | Required for documented PKW semantics |
Confirm the CBP/CBP2 sticker inside the MASTERDRIVES door before continuing. The GSD for a CBP2 differs from the GSD for a CBP; mixing them produces a "Slave not found" or "Configuration error" diagnostic.
3. Prerequisites
Install the following before opening HW Config:
- SIMATIC Manager V5.4 SP5 with the S7-300 / PROFIBUS option package.
- The latest Masterdrive HSP (Hardware Support Package) — referenced from Siemens entry 23183356 — HSPs for SIMATIC S7.
- The Masterdrive GSD file matching the CBP board (CBP2 most common for V3.x firmware). GSD repository is referenced from Siemens entry 113204 — GSD files for SIMOVERT MASTERDRIVES.
- The MASTERDRIVES Vector Control compendium PDF for parameter indexing. Section 8.2.3 ("Mechanisms for processing parameters via PROFIBUS") is the controlling specification; it is mirrored in Siemens entry 23660019 — Connection of Masterdrives to Profibus-DP.
- DriveMonitor or STARTER commissioning tool to read/write the same parameters from a PC for cross-verification.
4. Installing the GSD File and HSP in SIMATIC Manager
- Close all SIMATIC Manager windows.
- Launch Options → Install GSD File and select the correct
.GSD(and accompanying.BNF/ bitmap files). STEP 7 copies the GSD into\Step7\S7DATA\GSD. - Launch Options → Install HW Updates and import the Masterdrive HSP. The catalog entry "SIMOVERT" appears under PROFIBUS-DP → Drives → SIMOVERT.
- Restart HW Config so the new catalog entries load.
If the GSD is missing or the board does not match, the slave will accept the slot configuration but raise diagnostic byte 0x0B (extended diagnostic) with identifier-byte 0x83 ("Slave requires a different configuration"). Always confirm the catalog entry reads "CBP2" (or "CBP") for the slot used.
5. Hardware Configuration in HW Config
- Insert a SIMATIC 300 station and add the CPU 313C-2DP on the rail.
- Open the CPU properties, switch to the DP tab, and set Operating Mode = DP-Master. Choose a bus address (default 2) and a transmission rate of 1.5 Mbit/s for cable lengths up to 200 m, or 12 Mbit/s only for short, well-terminated segments.
- Drag the Masterdrive slave from the catalog to the DP master system. Assign the slave's PROFIBUS address (default 3, configured on the CBP2 DIP switches or via
P918). - Open the slave's DP-Slave Properties dialog and select the slot. If the HSP catalog entry is used, the PPO types appear directly. If the imported GSD is used, the GSD-driven dialog shows the same PPO slots; align them manually.
| PPO Type | PKW Words | PZD Words (Inputs) | PZD Words (Outputs) | Total Words / Slot | Use Case |
|---|---|---|---|---|---|
| PPO1 | 4 | 2 | 2 | 10 (5 IN / 5 OUT) | Parameter read/write + small process data |
| PPO2 | 0 | 6 | 6 | 12 (6 IN / 6 OUT) | Process data only (no on-the-fly parameter change) |
| PPO3 | 0 | 2 | 2 | 4 (2 IN / 2 OUT) | Minimum process data (control word + setpoint only) |
| PPO4 | 4 | 6 | 6 | 16 (8 IN / 8 OUT) | Parameter access + full process channel |
| PPO5 | 4 | 10 | 10 | 24 (12 IN / 12 OUT) | Parameter access + extended setpoints/actuals |
For drive commissioning that requires reading fault memory (r947) and writing ramp times (P460 / P461) while running, PPO1 is the smallest viable option and is often chosen to keep the cycle budget low. PPO5 is the largest and is required if you need to read or write more than two process data words in each direction (e.g., torque, speed, current, status).
6. PPO Type Selection and Telegram Structure
Each PPO telegram is divided into two zones: the parameter identification zone (PKW) and the process data zone (PZD). The PKW zone is optional; PPO2 and PPO3 omit it.
6.1 PZD — Process Data Zone
PZD is the cyclic data exchanged every PROFIBUS-DP cycle. The first output PZD is the control word (STW, parameter r550); the first input PZD is the status word (ZSW, parameter r551). Subsequent PZDs are user-definable setpoints and actuals configured via parameters P554.1 … P591.1 (control word connectors) and P694.1 … P740.1 (status word connectors).
6.2 PKW — Parameter Identification Zone
PKW is a non-cyclic, acyclic-style channel presented inside the cyclic frame. It must be transferred as a single 8-byte (4-word) block; partial writes are rejected. The block layout is shown below.
| Word | Name | Bits | Function |
|---|---|---|---|
| 1 | PKE | 15–12 AK | Request/response ID (0 = no request, 1 = read, 2 = write, 4 = read array element, 5 = write array element, 6 = read array, 7 = write array, etc.) |
| 1 | PKE | 11 SPM | Toggle bit for spontaneous-message signaling (1 = SPM follows) |
| 1 | PKE | 10–0 PNU | Parameter number (0 … 2047). For r947 → PNU = 947 (0x3B3) |
| 2 | IND | 15–9 reserved | Set to 0 |
| 2 | IND | 8 text/no text | Reserved / display text flag (0 = numeric) |
| 2 | IND | 7–0 index | Array sub-index (e.g., 0 for non-array parameters) |
| 3 | PWE1 | 31–16 | Parameter value high word (16-bit, 32-bit split) |
| 4 | PWE2 | 15–0 | Parameter value low word |
7. PKW Parameter Access Mechanism
The MASTERDRIVES parameter processing on PROFIBUS follows the mechanism defined in compendium Section 8.2.3. A request and its response share the same PKE.IND identifier; the drive sets AK = 1 on success and returns the value in PWE1/PWE2.
For S7-300 firmware, parameter 947 is the active fault buffer entry. To read the most recent fault:
- Set
PKE = 0x13B3→ AK = 1 (read), PNU = 0x3B3 (947). - Set
IND = 0x0000→ index 0. - Set
PWE1 = 0andPWE2 = 0. - Transfer the 4 words atomically using SFC14 / SFC15.
- Poll until AK in the response equals 1; then concatenate PWE1 << 16 | PWE2 to obtain the fault code.
Fault codes reported by r947 are documented in compendium Section 7. Examples: F001 = overcurrent, F002 = overvoltage, F003 = power module overtemperature, F005 = I²t overload, F006 = chopper overload, F008 = loss of field, F011 = user fault 1, F012 = user fault 2, F030 = loss of commutation, F031 = speed controller output limited, F033 = setpoint/actual deviation, F035 = overspeed, F041 = encoder fault, F042 = tachometer fault, F051 = parameter access error via PKW. The decoding map is a moving target across firmware revisions, so always cross-check against the V3.32 compendium table.
8. SFC14 and SFC15 Programming for Consistent Data
PKW and PZD words spanning more than 4 bytes require consistent read/write — a normal L PIW / T PQW sequence does not guarantee atomicity and is rejected by the CBP. Use SFC14 DPRD_DAT for reading and SFC15 DPWR_DAT for writing.
8.1 SFC14 — Read Consistent Data from DP Slave
| Parameter | Declaration | Type | Description |
|---|---|---|---|
| LADDR | INPUT | WORD | Configured start address of the slave's input area (e.g., W#16#0100). Must be the base I/O address of the slot, not individual word offsets. |
| RET_VAL | OUTPUT | INT | Return code (0 = OK, 0x80xx = DP error, 0x8xxx = slave diagnostic pending) |
| RECORD | OUTPUT | ANY | Destination byte/word/dword area in the PLC. Length must equal the configured input length of the slot. |
8.2 SFC15 — Write Consistent Data to DP Slave
| Parameter | Declaration | Type | Description |
|---|---|---|---|
| LADDR | INPUT | WORD | Configured start address of the slave's output area |
| RECORD | INPUT | ANY | Source area in the PLC; length must equal the configured output length of the slot |
| RET_VAL | OUTPUT | INT | Return code (0 = OK) |
8.3 SCL/ST Sample — Read PPO1 Input Image
// Read full 10-word (20-byte) PPO1 input image from slave at I-start 256
DATA_BLOCK DB_PPO1_IN
STRUCT
PKE : WORD; // word 0 (input view)
IND : WORD; // word 1
PWE1 : WORD; // word 2
PWE2 : WORD; // word 3
PZD1 : WORD; // ZSW (status word)
PZD2 : WORD; // actual value 1 (e.g., r550 routed to ZSW, r002 speed)
END_STRUCT
END_DATA_BLOCK
CALL SFC14
LADDR := W#16#100 // base I/O address from HW Config (decimal 256)
RET_VAL := MW100 // 0 = success
RECORD := P#DB_PPO1_IN.DBX0.0 BYTE 20 // 10 words = 20 bytes
8.4 SCL/ST Sample — Write PPO1 Output Image
DATA_BLOCK DB_PPO1_OUT
STRUCT
PKE : WORD := W#16#13B3; // AK=1 read, PNU=947
IND : WORD := W#16#0; // index 0
PWE1 : WORD := W#16#0;
PWE2 : WORD := W#16#0;
PZD1 : WORD := W#16#47E; // STW: enable + setpoint enable
PZD2 : WORD := W#16#0; // setpoint 0 for test
END_STRUCT
END_DATA_BLOCK
CALL SFC15
LADDR := W#16#0 // base Q address (example: 0)
RECORD := P#DB_PPO1_OUT.DBX0.0 BYTE 20
RET_VAL := MW102
T PQW writes — the CBP will treat it as a new request, not a continuation, and the previous request will be dropped with AK = 7.9. Reading Fault Values from r947
Parameter r947 is a 32-bit status word that holds the currently active fault code (or the most recent fault if the drive is no longer in a fault state). Reading it via PKW requires a 32-bit value, so PWE1/PWE2 are used as the high/low half.
9.1 Request Frame (PKW, AK = 1, PNU = 947)
| Word | Hex | Meaning |
|---|---|---|
| PKE | 0x13B3 | AK=1 (read value), PNU=0x3B3 (947) |
| IND | 0x0000 | Index 0 |
| PWE1 | 0x0000 | High word = 0 (drive returns value here) |
| PWE2 | 0x0000 | Low word = 0 (drive returns value here) |
9.2 Response Frame (on Success)
| Word | Hex (example) | Meaning |
|---|---|---|
| PKE | 0x13B3 | AK=1 echoed (or 0x13B3 | toggle) |
| IND | 0x0000 | Index 0 |
| PWE1 | 0x0000 | High half of fault code |
| PWE2 | 0x0005 | Low half = 5 → F005 (I²t overload) |
Fault code = (PWE1 << 16) | PWE2. For 16-bit faults (the common case) the value fits entirely in PWE2; PWE1 = 0. Acknowledge with control word bit 7 in the next PZD cycle; the drive clears the fault and the AK = 1 response reflects the cleared state.
10. Writing Ramp Times (P460 / P461)
Ramp-up time is P460; ramp-down time is P461. Both are 16-bit floating-point values stored in PKW as 32-bit IEEE-754 (a Mantissa-Byte / Exponent-Byte pair is also accepted by older firmware). To write a 2.0-second ramp:
10.1 Write Request for P460 = 2.0 s
| Word | Hex | Meaning |
|---|---|---|
| PKE | 0x23B4 | AK=2 (write, single word value), PNU=0x3B4 (460 → 0x1CC, 0x1CC in low 11 bits; reconfirm with compendium) |
| IND | 0x0000 | Index 0 |
| PWE1 | 0x0000 | High word of 32-bit value |
| PWE2 | 0x4002 | Low word — 2.0 as VFD-style mantissa/exponent pair (VFD-ME): exponent = 0x80 + log2(2) = 0x81 → byte = 0x40; mantissa = 0x0200 → word = 0x4002 |
10.2 PKW Write — Universal Module 6-Word Variant
If you selected a "Universal module" with 6 PZD words (no PKW zone) instead of a true PPO1/PPO5, you cannot write P460 / P461 over PROFIBUS. Either switch the slot to PPO1 / PPO4 / PPO5 in HW Config, or write the ramp times from the AOP (Advanced Operator Panel) keypad, or use DriveMonitor over the RS232 service port. With PPO1/4/5 selected, ramp times can be written while the drive is in run state — a common practice for test stands.
11. Verification and Commissioning Checklist
- In HW Config, the slave shows a green check icon and the diagnostic buffer of the CPU 313C-2DP is free of "Slave failure" / "Configuration error" events.
- With PPO1/4/5 selected, the input PZD[1] (status word) reads
0x4B31in0_0state, transitioning to0x4B37on run,0x0B31on enable, and0x0B38on fault (per compendium Section 6.3). - Send a PKW read of
P000; the response should be the drive's 16-bit identifier (e.g.,1101for MC compact, software V3.32). - Send a PKW read of
r947; verify the returned value against the keypad fault history. - Write
P460 = 1.5 s,P461 = 2.0 svia PKW. Read back via PKW and confirm on the AOP that the values match. - Use DriveMonitor or STARTER over RS232 to read the same parameters and confirm PROFIBUS and keypad values agree — this proves the GSD and PPO selection are correct.
12. Troubleshooting Matrix
| Symptom | Likely Root Cause | Verification | Fix |
|---|---|---|---|
| Slave appears in HW Config with red icon | Wrong GSD imported, or HSP not loaded | Open the slave's properties; verify "Device name" matches CBP board | Install correct GSD and restart HW Config |
| DPV1 diagnostic "ID byte 0x83 — different configuration required" | Slot config does not match slave firmware (PKW length wrong) | Check CBP diagnostic buffer via PPO PKW read | Re-select PPO type matching drive firmware (PPO1/4/5 only if PKW supported) |
| SFC14 RET_VAL = 0x8080 | Slotted slave not reachable / bus fault | Check termination, address (P918), and baud rate | Enable terminating resistors on both bus ends, set P918 to match HW Config |
| SFC14 RET_VAL = 0x8000 | Length mismatch in RECORD | Compare RECORD byte length with configured slot length | Set RECORD length to 4 × number of words (e.g., 20 bytes for PPO1) |
| AK = 7 in PKW response | Drive rejects request — wrong PNU or wrong index | Check parameter number against compendium | Use correct PNU (0x3B3 for 947); for indexed parameters set IND correctly |
| AK = 8 in PKW response | Slave does not support PKW (PPO2 or PPO3 in use) | Check HW Config slot type | Change slot from PPO2 / PPO3 to PPO1, PPO4, or PPO5 |
| PZD1 status word stuck at 0 | Wrong PZD connector routing | Read r550 on AOP |
Set P694.1 = 550, P694.2 = 0, etc. to map ZSW sources |
| Drive does not enable | STW bit pattern wrong | Compare with compendium Section 6.2 | Set STW = 0x047E (off1 + off2 + off3 + enable + ramp enable) to enable, then 0x047F for run |
| Written ramp time reverts on next power-up | Drive in "parameter restore to factory" mode | Check P010 on AOP |
Set P010 = 0 (parameters retained); save with P971 = 1 |
| r947 returns AK = 7 | PKW written one word at a time | Review PLC code for T PQW sequence |
Use SFC15 to write the full 4-word block in one call |
13. Field-Notes and Edge Cases
- CPB2 vs CBP timing: CBP2 supports 12 Mbit/s; original CBP is limited to 1.5 Mbit/s. Attempting 12 Mbit/s on a CBP-only drive produces DP bus timeouts and SF on the CPU.
-
Address switch on CBP2: Some CBP2 boards read the PROFIBUS address from
P918instead of the DIP switch when the address is non-zero. Confirm with the V3.32 compendium Section 4.1. - Multiple drives on one DP line: Each Masterdrive must have a unique address (3…125). Repeaters are required when cable length exceeds 200 m at 1.5 Mbit/s or when more than 32 slaves are connected.
-
Save parameters to EEPROM: PKW writes go to RAM only. Issue a PKW write of
P971 = 1(save) to commit changes to non-volatile memory. Save takes 2–4 seconds; do not power-cycle in this window. - Software V3.32 vs V4.x: The compendium and GSD match V3.32 and later compact MC drives. V4.x firmware on VC units (Vector Control, not Motion Control) uses a different PKW semantics for some safety-relevant parameters — always cross-reference the FW version against the GSD revision date.
r947 is diagnostic only and is non-interfering with the drive's internal safety chain. However, writing safety parameters (e.g., P050, P051, P060) via PKW is reserved for qualified personnel and the drive must be in 0_0 state with the main contactor open. Confirm local safety rules and lockout procedures before writing any safety or braking parameters.FAQ
Which GSD file does the Masterdrive MC 6SE7013-0EP50 need?
The GSD must match the communication board inside the drive, not the drive MLFB. For CBP2 (most V3.x units) use SI0180F1.GSD; for the older CBP use SIEM80F1.GSD. Open the drive door and read the CBP/CBP2 board label before downloading. The GSD repository is referenced from Siemens entry 113204.
How do I read the active fault code r947 from the drive?
Use a PPO1, PPO4, or PPO5 slot and write a PKW block with PKE = W#16#13B3 (AK=1 read, PNU=947), IND = 0, PWE1 = 0, PWE2 = 0. Transfer the four words with SFC15, then read the response with SFC14. The fault code is in PWE2 for 16-bit faults; for 32-bit codes concatenate (PWE1 << 16) | PWE2. Wait for AK = 1 in the response before consuming the value.
Why is my PPO2 or PPO3 slot unable to read or write parameters?
PPO2 and PPO3 do not include the PKW zone. To change parameters on the fly (e.g., P460 ramp-up, P461 ramp-down) or read r947 you must select PPO1, PPO4, or PPO5 in HW Config and re-download the configuration. The S7-300 must then read and write via SFC14 and SFC15 so the four PKW words are transferred as one consistent block.
Can I write ramp times with a 6-word universal module?
A 6-word universal module only provides PZD words and no PKW channel. Ramp times P460 and P461 must therefore be set from the AOP keypad, from DriveMonitor over the RS232 service port, or by switching the slot in HW Config to PPO1/PPO4/PPO5 and writing via PKW. PKW writes are the only PROFIBUS path that reaches drive-internal setup parameters on the fly.
My CPU 313C-2DP reports "Slave failure" — what is the first check?
Confirm three things in this order: (1) the GSD in HW Config matches the CBP/CBP2 board physically installed; (2) the slave's PROFIBUS address (P918 or DIP switch) matches the address in HW Config; (3) the bus is terminated at both ends and the baud rate does not exceed what the CBP board supports (1.5 Mbit/s for CBP, 12 Mbit/s for CBP2). If the slave LED on the CBP board is steady red, the bus physical layer is wrong; if it is flashing red, the configuration is wrong.