Problem Overview: TRCV_C #80C3 on S7-1500 Open User Communication
The TRCV_C and TSEND_C instructions implement open user communication (OUC) over the integrated PROFINET interface of the SIMATIC S7-1200 and S7-1500 CPU families. Both blocks combine three legacy functions: TSEND_C wraps TCON, TDISCON, and TSEND; TRCV_C wraps TCON, TDISCON, and TRCV. The combined design lets a single FB own the entire connection lifecycle while exposing a compact status interface (DONE, BUSY, ERROR, STATUS, NDR, RCVD_LEN).
When TRCV_C reports STATUS = 16#80C3, the embedded TCON sub-function has failed. The S7-1200/S7-1500 communication manual defines this status as "All connection resources are in use." In practice the failure mode splits into two distinct causes: a duplicate local CONN_OUC ID, or a fully populated connection resource table. The original report — a CPU 1515F2-PN driving 4 PCs each with 3 telegrams (12 simultaneous OUC connections) — is on the edge of the published resource budget for the F-class 1500, and the path to #80C3 is dominated by resource accounting, not by network quality. See the official block description at TSEND_C and TRCV_C — Send and receive data using Ethernet.
Where #80C3 Originates in the Block
Inside the combined FB, the TCON sub-function performs the connection resource allocation. TCON is invoked on the rising edge of CONT or when the instance DB has just been (re)initialized. If the CPU's kernel-side connection table already holds an entry for the requested ConnId, or if the table is full for the protocol/interface pair requested (TCP, ISO-on-TCP, UDP, or others), TCON returns 0x80C3 to the user block. TRCV_C mirrors that status on the STATUS output and the ERROR/STATUS pair at the rising edge of NDR.
The TIA Portal "Connections" editor view is a logical, configuration-time representation of the connection topology. It does not reflect the kernel's runtime state. A mismatch is normal during a startup race and during TIA Portal download sequences. Always trust the block's online STATUS over the editor's view.
| STATUS (hex) | Siemens manual description | Field interpretation |
|---|---|---|
0x80C3 |
All connection resources are in use | Duplicate CONN_OUC ID, or kernel resource table exhausted |
0x80C4 |
Connection terminated by remote | Peer closed the socket; check partner application |
0x80C7 |
Timeout on send/receive | Network latency, partner not responding, ADHOC mode mismatch |
0x80C1 |
Connection parameters invalid |
TCON_Parms mismatch, IP/port/protocol typo |
0x80C2 |
Local endpoint in use | Local port already bound by another block |
Full error tables are published in the S7-1200 communication manual: Legacy TSEND_C and TRCV_C — Send and receive data using Ethernet.
CPU 1515F2-PN Connection Resource Accounting
The 1515F2-PN shares a fixed pool of connection resources among PROFINET IO, S7 communication, OUC, Web server, OPC UA server, HMI panels, and the engineering/TIA Portal online channel. The F-class variant additionally reserves slots for PROFIsafe. The exact published maximum depends on the firmware version and is documented in the device manual. With 4 partner PCs and 3 telegrams per PC you are asking the kernel to manage 12 active OUC connections from a single program — every connection needs a unique ConnId in the local connection table, and a matching unique identifier at the partner.
TRCV_C/TSEND_C blocks in the same S7 program point at the same CONN_OUC ID, the second TCON attempt always fails with #80C3 because the first block still owns the resource slot. This is the single most common production cause of #80C3.Symptom Matrix
| Symptom | Most likely cause | First check |
|---|---|---|
| Error appears after every TIA Portal download | Instance DB reinit triggers a new TCON while the old TCON is still in the kernel table |
CONT edge behaviour; initial values of the instance DB |
| One of 12 connections hangs intermittently; only power cycle clears it | Duplicate CONN_OUC ID between two blocks |
Audit TCON_Parms in every block |
| TIA "Connections" view shows all 12 established, yet blocks still error | Connections view is a logical, configuration-time representation, not the kernel's runtime state | Read block STATUS outputs from a watch table |
| Error appears once, never clears, even after STOP/RUN | Instance DB retains CONT=TRUE; TCON never re-attempts cleanly |
Toggle CONT in OB100 startup |
| Block recovers after STOP→MRES→RUN, but not after STOP→RUN | Stale resource slot retained across a warm restart | MRES clears the connection table; warm restart does not |
Diagnostic Procedure
- Open TIA Portal and navigate to Devices & Networks → Connections. List every
TSEND_C/TRCV_Cblock and its configuredConnId(also calledCONN_OUCID). Highlight any duplicate IDs. - Open each
TRCV_Cinstance DB (for exampleDB2100) in online mode. Confirm theSTARTUPbit in theSTATICsection isFALSEafter a download. ATRUEvalue indicates the DB was reinitialized. - Create a watch table that includes the
STATUSandERRORoutputs of every block. Force the CPU toRUN. Watch for the first instance that reportsERROR=TRUE STATUS=16#80C3. - From the same watch table, monitor the CPU's online connection list via Online & Diagnostics → PROFINET interface → Connection list. Cross-reference every connection shown against the configured
ConnIdvalues. - If the online connection list shows fewer entries than configured IDs, the missing entries are the ones that failed
TCON— those are the blocks that reported#80C3. - From the project tree, right-click the CPU → Online & Diagnostics → Diagnostic buffer. Look for the
Communication errorevents. TheModefield shows the event class; theEvent IDfor OUC resource exhaustion is the same as theSTATUScode returned by the block.
Connection Topology Reference
Solution 1 — Eliminate Duplicate CONN_OUC IDs
The TCON_Parms structure inside the TSEND_C/TRCV_C data block contains a ConnId field. In TIA Portal this is exposed as the Connection ID (also called CONN_OUC ID) property on the block's configuration dialog. Every active OUC connection — TSEND_C, TRCV_C, TCON, or the legacy TCP/ISO-on-TCP variants — must use a unique ConnId. The ID space is local to the CPU; PCs at the other end of the cable do not need to match.
For a 1515F2-PN with 12 OUC connections, the recommended practice is to allocate a 16-wide block per protocol direction. The ConnId values 1..15 are reserved by TIA Portal for system connections; start at 100 to leave a generous gap.
| Block | Peer | ConnId | Direction | Protocol |
|---|---|---|---|---|
| TSEND_C_PC1_T1 | PC1 | 100 | PLC→PC1, telegram 1 | TCP |
| TRCV_C_PC1_T1 | PC1 | 101 | PC1→PLC, telegram 1 | TCP |
| TSEND_C_PC1_T2 | PC1 | 102 | PLC→PC1, telegram 2 | TCP |
| TRCV_C_PC1_T2 | PC1 | 103 | PC1→PLC, telegram 2 | TCP |
| TSEND_C_PC1_T3 | PC1 | 104 | PLC→PC1, telegram 3 | TCP |
| TRCV_C_PC1_T3 | PC1 | 105 | PC1→PLC, telegram 3 | TCP |
| TSEND_C_PC2_T1 | PC2 | 106 | PLC→PC2, telegram 1 | TCP |
| TRCV_C_PC2_T1 | PC2 | 107 | PC2→PLC, telegram 1 | TCP |
| … | … | … | … | … |
| TRCV_C_PC4_T3 | PC4 | 123 | PC4→PLC, telegram 3 | TCP |
Reserve ConnId 124..127 as sentinels. If a code review spots one of those IDs in a user program, an earlier developer misallocated the ID space.
Solution 2 — CONT Reset Pattern (Field-Proven)
When the kernel refuses to release a connection slot and the only documented recovery is a power cycle, a forced CONT = FALSE → CONT = TRUE toggle at the block input forces TDISCON followed by TCON. The pattern below runs in OB1 and self-heals any TRCV_C/TSEND_C that reports ERROR with a recoverable status (including 0x80C3).
// ST / SCL — TRCV_C self-healing wrapper
// iDB_TRCV is the instance DB of TRCV_C (e.g. DB2100)
// tReset is a TON timer instance
// bResetLatch is a static BOOL
IF iDB_TRCV.ERROR
AND (iDB_TRCV.STATUS = 16#80C3
OR iDB_TRCV.STATUS = 16#80C4
OR iDB_TRCV.STATUS = 16#80C7) THEN
tReset(IN := TRUE, PT := T#200ms);
END_IF;
IF tReset.Q THEN
iDB_TRCV.CONT := FALSE; // forces TDISCON
bResetLatch := TRUE;
END_IF;
iDB_TRCV(); // call block
IF bResetLatch AND NOT iDB_TRCV.BUSY THEN
iDB_TRCV.CONT := TRUE; // re-arm TCON on next cycle
bResetLatch := FALSE;
tReset(IN := FALSE);
END_IF;
The same pattern scales to a function block that wraps a single TRCV_C plus the reset logic, instantiated 12 times. Variants observed in production code include a watchdog timer that cycles CONT low for 200 ms then high, and an HMI tag that drives CONT to allow operator-initiated reset without a STOP/RUN download.
TRUE on CONT is acceptable for steady-state operation. Toggling CONT to FALSE for one OB1 cycle is the documented way to disconnect without changing the program. The block will not release its resource slot until CONT goes low.Solution 3 — Instance DB Reinitialization on Download
Every TIA Portal download can reinitialize the TRCV_C/TSEND_C instance DB if the block's interface signature has changed (added STATIC, changed TEMP, recompiled). When the DB is reinitialized, the internal "connection already established" flag is cleared, the block issues a new TCON, and that new TCON collides with the still-open kernel connection — resulting in #80C3 for one scan. The TIA "Connections" view will momentarily show 13 entries until the old one times out.
To prevent the post-download collision:
- Open the instance DB properties → Download tab. Uncheck Reinitialize instance DB on download if the project policy allows it.
- Wrap every
TRCV_C/TSEND_Ccall with theCONTreset pattern (Solution 2). A reinitialized DB hasCONT=FALSEon its first scan, so the block will re-TCONcleanly. - For the first download after a program change, perform a
STOP → MRES → RUNon the CPU to flush the kernel's connection table before the user program starts.MRESresets the connection table; a warm restart (STOP → RUN) does not.
Firmware Considerations
The original report references firmware V2.0 on the CPU 1515F2-PN. V2.0 is early for the F-generation 1500; later firmware versions (V2.6, V2.9, and the V3.x line introduced with TIA Portal V18/V19) fix several open-user-communication defects observed in earlier branches:
- Improved handling of the
CONTedge after aTCONfailure — blocks no longer leave a partially-allocated resource slot in the table. - Additional resource headroom for OUC on PROFINET interface
X1andX2(where present on the CPU variant). - Fixes for a TRCV_C leak in which a
#80C3on the first call would not release the resource until the next STOP/RUN. - Hardened handling of ISO-on-TCP partner TCON collisions during partner restart storms.
Before applying any firmware update, capture the current project, perform a full backup using the SIMATIC Automation Tool, and review the release notes for breaking changes in TCON_Parms structure layout. TIA Portal must be the matching version: V2.6 → TIA V15.1, V2.9 → TIA V16 Update 4 or later, V3.0 → TIA V17, V3.1 → TIA V18/V19. The full compatibility matrix is in the Siemens online support entry 67196808 — How do you program the TSEND_C and TRCV_C instructions for open user communication over the integrated PROFINET interface of the S7-1200/S7-1500 CPU?
Worked Example: 1515F2-PN with 4 PCs × 3 Telegrams
Assume the application needs three unidirectional data exchanges per PC:
- Telegram 1: PLC → PC, 256 bytes, every 100 ms (control setpoints).
- Telegram 2: PC → PLC, 512 bytes, event-driven (acknowledgements).
- Telegram 3: bidirectional, 1024 bytes, every 1 s (diagnostic block).
TRCV_C supports a maximum payload of 8192 bytes per the S7-1200 manual. All three telegrams fit comfortably. The total OUC connection count is 4 PCs × 3 = 12, each occupying one slot in the kernel's connection table. Add PROFINET IO, the HMI connection, and the engineering connection, and the CPU is operating near its published resource limit. If the limit is exceeded, the kernel refuses TCON with #80C3 even though the project compiles cleanly.
Two engineering choices reduce the load: (a) collapse two unidirectional telegrams into a single bidirectional exchange (1 connection instead of 2), or (b) move lower-priority exchanges to a single multiplexed connection with a length-prefixed protocol. Either approach halves the OUC count and provides headroom for future expansion.
Verification Procedure
- Download the corrected program. Force the CPU to
STOP, thenRUN. - Open a watch table with
STATUSof all 12 blocks. All must show16#0000(no error pending) within 5 s ofRUN. - From TIA Portal Online & Diagnostics, navigate to PROFINET interface → Connections. Confirm exactly 12 OUC entries plus the engineering connection.
- Disconnect one PC's Ethernet cable. The corresponding
TRCV_Cshould report16#80C7(timeout) andTSEND_Cshould report16#80C4(connection terminated). All other 11 connections must remain unaffected. - Reconnect the cable. The
CONTreset pattern (Solution 2) must restore the connection without a STOP/RUN of the CPU. - Trigger a TIA Portal download of a non-communication-related block. All 12 connections must survive the download (the instance DBs are not reinitialized, the kernel does not release the resources).
- Read the diagnostic buffer. No
Communication errorevents with ID0x80C3should appear during the test sequence.
Troubleshooting Matrix
| Observed STATUS | Probable cause | Fix |
|---|---|---|
16#80C3 on first call after download |
Instance DB reinitialized; TCON collision |
Disable "Reinit on download" or implement CONT reset |
16#80C3 on one block, others fine |
Duplicate CONN_OUC ID |
Reassign unique ConnId
|
16#80C3 on all blocks simultaneously |
Kernel resource table exhausted | Reduce the number of concurrent OUC; check the CPU connection budget |
16#80C3, but block recovers after STOP/RUN |
Stale resource slot held by a previous TCON
|
CONT reset pattern or MRES before RUN
|
16#80C4 |
Remote peer closed socket | Verify partner application; check firewall/keep-alive |
16#80C7 |
Send/receive timeout | Check ADHOC mode, polling time, partner TSEND_C
|
16#80C1, 16#80C2
|
Protocol mismatch, partner not in correct state | Match TCP vs ISO-on-TCP; verify partner TCON complete |
Preventive Best Practices
- Maintain a centralized
ConnIdallocation table in the project documentation. Review it at every code review. - Always wrap
TSEND_C/TRCV_Cin a self-healing FB that togglesCONTon#80C3or#80C7. - Enable the Block consistency check during TIA Portal download so that unintended reinitialization of instance DBs is reported.
- Use distinct PROFINET interface
X1/X2(if available on the CPU) to spread OUC and PROFINET IO across separate MAC tables. - Schedule firmware updates through the Siemens release cycle. Subscribe to the firmware RSS feed for the 1515F2-PN to be notified of OUC bug fixes.
- Avoid
TCON/TDISCONraw blocks in the same program asTSEND_C/TRCV_C. Mixing the two families on the sameConnIdis a known recipe for resource table corruption. - Document the maximum expected OUC count per CPU in the network architecture diagram. Add a 20% headroom margin; never operate at the published maximum.
FAQ
What does TRCV_C error 80C3 mean on an S7-1500 CPU?
STATUS 16#80C3 means the embedded TCON sub-function inside TRCV_C could not allocate a connection resource — either because the connection table is full or because the requested CONN_OUC ID is already in use by another active block. The full Siemens description is "All connection resources are in use."
Can duplicate CONN_OUC IDs cause 80C3 even when the TIA Connections view shows all links established?
Yes. The TIA Connections view reflects the configured topology, not the kernel's runtime state. Two blocks pointing at the same ConnId cause the second TCON to fail with 80C3, while the first block keeps the connection alive in the kernel table and in the view.
How do I reset a TRCV_C connection without powering down the CPU?
Drive the block's CONT input low for one OB1 cycle, then high. The block will issue a TDISCON followed by a TCON on the rising edge, releasing and re-allocating the resource. A watchdog timer or operator-controlled HMI tag can implement the same pattern in a self-healing FB.
Does downloading the TIA Portal program always reinitialize the TRCV_C instance DB?
Only if the block interface signature changed (new STATIC, removed TEMP, recompiled) or the Reinitialize instance DB on download option is checked in the DB properties. A pure code change to a different FB does not reinitialize the TRCV_C instance DB.
Is a firmware update a valid fix for 80C3 on CPU 1515F2-PN V2.0?
Yes. V2.0 is an early firmware branch for the 1515F2-PN; later V2.6/V2.9/V3.x firmware ships bug fixes for open user communication, including resource-leak conditions that contributed to 80C3. Coordinate the firmware update with the matching TIA Portal version per the Siemens compatibility matrix (support entry 67196808).