Configuring Modbus TCP/IP Communication on S7-300 PLC Systems

David Krause12 min read
S7-300SiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview: Modbus/TCP on a SIMATIC S7-300

Modbus/TCP is an open, Ethernet-based variant of the Modbus protocol (IANA assigned TCP port 502) that lets a SIMATIC S7-300 exchange process data with third-party devices such as drives, instruments, RTUs, and SCADA servers without a proprietary gateway. On the S7-300 platform, Modbus/TCP is implemented through one of two architectural paths:

  • Path A — CP-based (recommended): A communications processor (CP 343-1 or CP 343-1 Lean/Advanced/EX) terminates the TCP connection and runs the Modbus/TCP server or client. The CPU exchanges data with the CP through the backplane using standard S7 PUT/GET or via the MODBUSCP function block.
  • Path B — CPU PN/IE integrated port: For S7-300 CPUs with an integrated PROFINET interface (e.g., CPU 315-2 PN/DP, CPU 317-2 PN/DP, CPU 319-3 PN/DP), Modbus/TCP can run directly on the CPU's Ethernet port when the optional Modbus/TCP license and blocks are loaded. This eliminates the CP hardware but requires an additional software package.

Siemens' official entry 22660304 in the Siemens Industry Online Support describes both options and points to the matching manuals, sample projects, and library deliverables. Use that entry as the canonical index whenever a firmware or library version question arises.

Engineering rule of thumb: If the application already has a CP 343-1, run Modbus/TCP on the CP. The CPU retains deterministic cycle time for the user program because the TCP stack and Modbus state machine run on the CP's own processor. Reserve the CPU PN port approach for smaller machines where adding a CP is not economical.

Hardware Prerequisites

Before any software configuration, confirm the physical layer is complete and the catalog numbers match the firmware you intend to load.

Component Catalog Number (MLFB) Function Notes
S7-300 CPU (any) 6ES731x-xxxxx-xxxx Application program, owns DBs Firmware ≥ V2.x recommended for CP-based path
CP 343-1 Lean 6GK7343-1CX10-0XE0 10/100 Mbit, up to 4 TCP connections Modbus/TCP supported from firmware V2.0
CP 343-1 6GK7343-1EX30-0XE0 10/100 Mbit, up to 8 TCP connections Most common choice for Modbus/TCP
CP 343-1 Advanced 6GK7343-1GX31-0XE0 Adds IP routing, security Use when Modbus traffic crosses subnets
Power supply PS 307 6ES7307-1xxxx-0AA0 24 V backplane power ≥ 5 A recommended when CP is loaded
Modbus/TCP PN CPU block package 2XV9450-1MB11 Enables Modbus/TCP on CPU PN/IE port Required for Path B only; pairs with a license key on the SIMATIC Memory Card

Verify the hardware list against the S7-300 module spectrum manual (entry 8859629) before ordering. Field-replacement with a CP of a different article number is one of the most common causes of a "TCP connection refused" fault on first commissioning.

Software Prerequisites and Licensing

Tool / Package Version Purpose
STEP 7 (Classic) V5.5 SP4 / SP5 Hardware config, NetPro connection table, FB source code import
TIA Portal V15.1 or newer for S7-300 CP support Optional alternative editor; required for newer CPs
Modbus/TCP CP block library (S7-300/400) See 22660304 Provides FB MODBUSCP (V1/V2 variants)
Modbus/TCP PN CPU blocks Delivered with 2XV9450-1MB11 Path B; ships FBs MB_CPCLI, MB_CPSRV, MB_REDCL, MB_REDSV
Automation License Manager V6.0+ Activate Modbus/TCP license when using Path B

For Path A (CP-based), no license is required on the CP itself. The CP firmware handles the Modbus/TCP framing and the CPU simply reads/writes data tags. For Path B (CPU-based), the Modbus/TCP PN CPU package 2XV9450-1MB11 must be installed and a valid license transferred to the SIMATIC Memory Card; without it the Modbus FB will return error code 0x8600 ("license missing").

Network Topology and IP Planning

Plan IP addresses before you touch TIA Portal or STEP 7. Modbus/TCP does not perform any discovery, so an addressing mismatch between CP and partner device is the single most common commissioning fault.

  1. Reserve a static IPv4 address for the CP 343-1 in the same subnet as the Modbus partner. Example for an isolated machine network: 192.168.10.10 / 255.255.255.0.
  2. Reserve a static IPv4 address for each Modbus partner (PLC, VFD, SCADA node). Avoid DHCP for industrial Modbus/TCP nodes.
  3. Place the CP and the partner on the same physical switch or VLAN. Cross-subnet Modbus/TCP requires the CP 343-1 Advanced or a router; a Lean or standard CP cannot route.
  4. Confirm TCP port 502 is not blocked by any managed switch ACL, firewall, or Windows Firewall rule on the SCADA host.
  5. If the project uses PROFINET and Modbus/TCP on the same physical port of the CP, verify the CP variant supports both simultaneously (CP 343-1 EX30 and Advanced do; Lean limits concurrent PROFINET IO + open TCP).
Watch-out: Two S7-300 CPs on the same backplane share one Ethernet MAC domain per slot. If you install two CP 343-1 modules, both must be in different IP subnets or you will get intermittent ARP conflicts that masquerade as Modbus timeouts.

Configuration in STEP 7 (Classic) — Path A (CP 343-1)

Step 1: Insert the CP in HW Config

  1. Open the SIMATIC Manager and the S7 project.
  2. In HW Config, drag the CP 343-1 (6GK7343-1EX30-0XE0) from the hardware catalog onto slot 4–11 of the S7-300 rack.
  3. Double-click the CP to open its properties dialog. Assign the static IP address, subnet mask, and (optionally) a router address.

Step 2: Enable the Modbus/TCP connection in NetPro

  1. Open NetPro from the SIMATIC Manager.
  2. Right-click the CP 343-1 and choose Insert New Connection.
  3. Connection type: TCP connection (not ISO-on-TCP, not S7 connection).
  4. Set Active connection establishment on the side that initiates (usually the S7-300 for a client role; the partner for a server role).
  5. Specify the partner IP address and confirm local port 502 is used for the Modbus/TCP server.

Step 3: Load the MODBUSCP function block

Import the Modbus/TCP CP block library obtained from Siemens entry 22660304. The library contains:

  • FB MODBUSCP (background DB instance per logical connection)
  • UDT MODBUS_PARAM for connection parameters
  • Example project with a sample S7 program

Copy FB MODBUSCP into the S7 program blocks container. Open OB1 and instantiate the FB once per active Modbus/TCP connection.

Programming the MODBUSCP Function Block

The TIA Portal documentation for MODBUSCP describes the block interface for S7-300/S7-400. Key parameters:

Input Type Meaning
EN BOOL Enable the call (typical: call unconditionally in OB1)
ID WORD Local connection ID from NetPro (hex, e.g., W#16#0001)
START BOOL Rising edge triggers a single read/write request
REQ_FUNC BYTE Modbus function code: 1=Read Coils, 2=Read Discrete, 3=Read Holding Reg, 4=Read Input Reg, 5=Write Single Coil, 6=Write Single Reg, 15=Write Multiple Coils, 16=Write Multiple Regs
START_ADDR WORD Modbus starting address (0-based)
QUANTITY INT Number of coils/registers (1–125 for registers)
DATA_PTR ANY Pointer to the source/destination DB area in the CPU
Output Type Meaning
DONE BOOL One-shot pulse on successful completion
BUSY BOOL TRUE while the request is in progress
ERROR BOOL TRUE if the request terminated with an error
STATUS WORD Hex status word; see error table below

Minimal ST call pattern (SCL or STL) to read 10 holding registers starting at Modbus address 40001 from partner 192.168.10.50:

// OB1 — cyclic call
CALL FB 100, DB100   // FB MODBUSCP, instance DB
     ID       := W#16#0001
     START    := TRUE                  // single-shot; latch off in OB1 logic
     REQ_FUNC := B#16#03               // Read Holding Registers
     START_ADDR:= W#16#0000             // address 40001
     QUANTITY := 10
     DATA_PTR := P#DB200.DBX0.0 BYTE 20
     DONE     := M100.0
     BUSY     := M100.1
     ERROR    := M100.2
     STATUS   := MW102

The 20-byte DATA_PTR area in DB200 receives ten 16-bit Modbus registers in big-endian order (high byte first). If the CPU is little-endian, byte-swap each word with TAW / manual rotation before any further integer arithmetic.

Configuration in TIA Portal — Path B (CPU PN/IE direct)

When the project uses an S7-300 CPU with an integrated PN port and the optional Modbus/TCP PN CPU package 2XV9450-1MB11 is installed:

  1. In the TIA Portal device view, select the CPU and open Properties > Communication > Modbus/TCP.
  2. Add a new Modbus connection; specify role (server/client), partner IP, port (default 502), and the Modbus register area mapping.
  3. Transfer the Modbus/TCP license to the SIMATIC Memory Card via Online > Licensing.
  4. Use the supplied FBs MB_CPCLI / MB_CPSRV in OB1 instead of MODBUSCP.
Path B blocks and Path A blocks are not interchangeable. Mixing them produces status 0x8085 ("block ID mismatch"). Confirm which library was loaded by checking the FB version in the block properties.

Data Areas and Modbus Register Mapping

Modbus addressing is 0-based in the protocol and 1-based in many tools. Translate consistently to avoid off-by-one faults.

Modbus Function Modbus Address Range (protocol) Typical UI Label PLC Data Type
Read Coils (FC 1) 00001–09999 0xxxxx BOOL array
Read Discrete Inputs (FC 2) 10001–19999 1xxxxx BOOL array
Read Holding Registers (FC 3) 40001–49999 4xxxxx INT / WORD array
Read Input Registers (FC 4) 30001–39999 3xxxxx INT / WORD array
Write Single Coil (FC 5) 00001–09999 0xxxxx BOOL
Write Single Register (FC 6) 40001–49999 4xxxxx INT / WORD
Write Multiple Coils (FC 15) 00001–09999 0xxxxx BOOL array
Write Multiple Registers (FC 16) 40001–49999 4xxxxx INT / WORD array

When the SCADA configuration tool asks for register 40001, set START_ADDR := W#16#0000 in the FB. When the tool asks for register 40100, set START_ADDR := W#16#0063 (decimal 99 → 0-based offset). Document the mapping in a cross-reference table so commissioning engineers can verify quickly.

Diagnostics and Status Codes

Read the CP's diagnostic buffer via Online > Accessible Nodes or via the RDREC / WRREC SFBs. The MODBUSCP STATUS output returns a hex word that combines a class byte and a detail byte.

STATUS (hex) Class Meaning Recommended Action
0x0000 — No error None
0x8085 Configuration Block ID / version mismatch Reload the correct library; check Path A vs Path B
0x80A1 Resource Connection not configured in NetPro Re-create the TCP connection and download
0x80A3 Resource Connection ID in use Use a unique ID per connection
0x80B1 Resource QUANTITY exceeds 125 registers or 2000 coils Reduce quantity or split request
0x80C3 Resource Temporary resource shortage on CP Reduce polling rate; check CP load
0x80D0 Resource Partner not reachable (TCP timeout) Ping partner; check IP, subnet, VLAN, firewall on port 502
0x8600 License Modbus/TCP PN CPU license missing (Path B) Transfer license to SIMATIC Memory Card
0x86A2 Modbus Modbus exception code 02 (illegal data address) Verify partner supports the requested address range
0x86A3 Modbus Modbus exception code 03 (illegal data value) Verify QUANTITY is within partner's limits
0x86A4 Modbus Modbus exception code 04 (slave device failure) Check partner device health

The CP 343-1 also writes its own diagnostic entries with identifiers in the format Modbus: TCP xyz. Filter the diagnostic buffer on the string "Modbus" to retrieve only relevant entries.

Verification and Commissioning Checklist

  1. From the TIA Portal / STEP 7 engineering station, ping the CP 343-1 IP address; expect < 5 ms RTT on a healthy switched network.
  2. Open a Telnet or netcat session to partner-ip 502; the connection should complete silently (no banner).
  3. In Online & Diagnostics, view the CP's connection list; the Modbus/TCP entry should appear with state ESTABLISHED.
  4. Force a single read of holding register 40001 from the FB and observe DONE = TRUE, ERROR = FALSE, and a non-zero STATUS = 0x0000.
  5. From the SCADA side, perform a Modbus poll of the same register; values must match within one poll cycle.
  6. Capture a Wireshark trace filtered on tcp.port == 502; verify request/response pairs and MBAP (Modbus Application) header transaction IDs increment monotonically.
  7. Disconnect the partner cable; STATUS should change to 0x80D0 within the configured keep-alive time (default 10 s).
  8. Reconnect and confirm the FB recovers without CPU restart (no STOP needed).

Troubleshooting Matrix

Symptom Likely Root Cause Diagnostic Step Fix
ERROR = TRUE, STATUS 0x80D0 immediately Wrong partner IP or subnet Ping from CPU's Ethernet port using ping via TIA Portal Re-assign partner IP in NetPro / TIA Portal
STATUS 0x8085 on first call Wrong FB variant Compare FB version with library Replace FB with matching library version
STATUS 0x8600 (Path B) Modbus/TCP PN CPU license missing Online > Licensing Install 2XV9450-1MB11 license
STATUS 0x86A2 Partner rejects address range Read partner's Modbus map Use supported address range
Register values swapped bytes Endianness mismatch Inspect bytes in DB monitor Apply byte swap in PLC program
Intermittent timeouts during PROFINET IO comms CP Lean overload Check CP connection count and PROFINET IO count Upgrade to CP 343-1 (EX30) or Advanced
SCADA receives exception 0x0B (gateway target failed) CP backplane busy Check CP diagnostic buffer Reduce poll rate to ≤ 200 ms
No Modbus traffic on Wireshark Wrong TCP port or VLAN ACL Inspect switch port config Open TCP/502 between VLANs

Performance and Polling Recommendations

  • Keep poll cycles ≥ 100 ms per connection to leave CPU scan time for the user program.
  • Batch reads into multi-register requests (FC 3 / FC 16) instead of single-register polling to cut TCP overhead.
  • For more than 4 simultaneous Modbus/TCP partners, choose CP 343-1 (8 connections) or CP 343-1 Advanced (up to 32 connections).
  • Place Modbus/TCP on a dedicated VLAN when shared with PROFINET to keep both deterministic.
  • Use BUSY for hand-shake: do not retrigger START until BUSY = FALSE; retriggering during a pending transaction returns STATUS 0x80A3.

Related Siemens Documentation

FAQ

Which CP 343-1 firmware supports Modbus/TCP?

CP 343-1 Lean (6GK7343-1CX10-0XE0) and CP 343-1 (6GK7343-1EX30-0XE0) support Modbus/TCP from firmware V2.0. The Advanced variant (6GK7343-1GX31-0XE0) supports it on all shipped firmware versions. Verify the firmware level with Online > Accessible Nodes > Module Information before commissioning.

Do I need a separate Modbus/TCP license on the CP 343-1?

No. Running Modbus/TCP on a CP 343-1 does not require any additional license. A license is only required when running Modbus/TCP on the integrated PROFINET port of an S7-300 CPU (Path B), in which case the package 2XV9450-1MB11 must be activated on the SIMATIC Memory Card.

What TCP port does Modbus/TCP use, and can it be changed?

Modbus/TCP uses IANA-assigned TCP port 502. On a CP 343-1 acting as a server, the local port is fixed to 502. On a CP acting as a client, the remote port of the partner is normally 502 but can be changed in NetPro to reach non-standard servers (some vendors use 5020 or 5030 for routing gateways).

Why does STATUS return 0x80D0 even though ping succeeds?

Ping only confirms IP reachability; STATUS 0x80D0 indicates the TCP connection was actively refused or timed out at the application layer. The most common causes are a firewall blocking TCP/502, the partner Modbus server not running, or the partner bound to a different IP than the CP is targeting. Verify with telnet <partner-ip> 502 from the engineering station.

Can the CP 343-1 and the CPU PN port both run Modbus/TCP simultaneously?

Yes, but each interface runs its own FB instance and license model. The CP uses MODBUSCP with no license; the CPU PN port uses the Path B blocks (MB_CPCLI / MB_CPSRV) and the 2XV9450-1MB11 license. Keep the two Modbus address spaces distinct to avoid SCADA confusion.

Back to blog