Configuring Selective Retentive Memory on S7-300 in TIA Portal

David Krause12 min read
SiemensTIA PortalTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Overview

The S7-300 CPU family (including the CPU 313C, order number 6ES7 313-5BF03-0AB0) does not support the granular, per-symbol retentive memory model introduced with the S7-1500 generation. In the CPU properties dialog of TIA Portal (or legacy STEP 7), retentivity is configured as a single contiguous range: Number of retentive memory bytes starting with MB0. The user can only specify how many bytes from the start of the bit-memory (M) area survive power OFF, STOP→RUN, and unbuffered RESTART — there is no way to flag individual words such as MW16, MW22, MD54, or MD200 as retentive while leaving MW0MW14 non-retentive.

This limitation causes three field problems:

  1. Marking the entire range MB0…MB203 as retentive consumes backup capacity on the MMC and risks retaining intermediate scratch values that should be initialised on every restart.
  2. WinCC 7.3 HMI tags bound directly to MW/MD addresses lose their last value when the CPU is switched off, which corrupts operator faceplates and recipe views.
  3. Code becomes non-portable: when the same logic is migrated to an S7-1500 the retentive attribute is lost unless a separate download is performed, creating a maintenance hazard.

The recommended solution is to replace the volatile MW/MD operands with a global Data Block (DB) whose instance-DB area is flagged with the RETAIN attribute. Each individual tag inside the DB inherits the retentive behaviour, regardless of its address, while all other flags remain volatile. The same pattern is documented in the Siemens functional description of S7-1500 CPUs under Retentive memory areas (S7-1500); the principle (DB-scoped retain) is identical on the S7-300 and S7-400 lines.

2. Why S7-300 Retentive Memory Is Range-Based

The S7-300 architecture separates the retentive configuration of three operand areas:

Operand Area Configuration Parameter CPU 313C (6ES7 313-5BF03-0AB0) Maximum Granularity
Bit memory (M / MB) Number of retentive MBs starting at MB0 0 … 2048 bytes 1-byte boundary, always from MB0
S7 timers (T) Number of retentive timers starting at T0 0 … 256 (T0…T255) 1-timer boundary, always from T0
S7 counters (C) Number of retentive counters starting at C0 0 … 256 (C0…C255) 1-counter boundary, always from C0
DB instance area SET (RETAIN) attribute on the DB Limited by load memory / MMC Per-tag, address-independent

Hardware Configuration → CPU 313C → Properties → Retentive Memory exposes the three numeric spin boxes. There is no symbolic selector: if you want MW200 retained, you must also retain everything from MW0 to MW199. The CPU firmware stores the configured length in the system data block SDB 0 and applies it to the warm-restart OB (OB100) and to the backup/restore procedure triggered by the MMC.

Operational consequence: the S7-300 backup battery (or MMC remanence) must hold the entire retentive range. A 128-byte setting is therefore not just a programming convenience — it directly determines the energy budget required to bridge a power loss. Use the smallest range that still satisfies the process, and push selective retention into a DB.

3. Prerequisites

  • Siemens STEP 7 / TIA Portal V13 SP1 (Update 9 minimum) — older V13 without SP fails to upload the SDB into a project that contains optimised blocks.
  • CPU 313C, 6ES7 313-5BF03-0AB0, firmware V3.3 or later (earlier V3.0/V3.1 are functionally identical for retain but lack some diagnostic OBs).
  • MMC of at least 64 KB; the retentive DB will be downloaded as part of the active program.
  • Source project compiled without errors — DB retain cannot be set on blocks that contain unresolved symbols or mixed instance / global declarations.
  • WinCC Explorer 7.3 (or WinCC flexible 2008 SP5) with an active HMI connection of type S7ONLINE pointing at the same MPI/Profibus subnet.

4. The Data Block RETAIN Method — Concept

DB-based retain works on every S7-300/400/1500 CPU because the retain flag is stored in the DB header (attribute byte in the block interface, S7-matic ATTR_RET bit). When the CPU performs a power-OFF/power-ON sequence, the load image of every RETAIN DB is preserved by the operating system; volatile DBs are zeroed. The mechanism is independent of the bit-memory retentive range, so it does not consume any of the configured MB backup budget.

Three structural rules must be observed:

  1. The DB must be a global DB (DB type = Shared DB). Instance DBs attached to FBs inherit the retain setting of the FB interface; this is harder to audit.
  2. The DB must be non-optimised on S7-300 (TIA Portal option “Accessible from S7-300/400”). The S7-300 firmware does not understand the optimised-block container introduced with S7-1500.
  3. Absolute addressing in the program must change from MW16 to DB_RETAIN.DBW16 (or fully symbolic "dbRetain".SetpointRPM). The original MW16 becomes a scratch flag and is no longer retained.

5. Step-by-Step — Create the Retentive Data Block

  1. In the project tree, right-click Program blocks → Add new block → Data block (DB).
  2. Name the DB DB_Retain (number 100 is conventional; avoid 0–5 which are reserved for system and SFB/SFC instance work areas).
  3. Open the DB properties: uncheck “Optimised block access”, leave “Instance of a…” unchecked (Shared DB), and tick “Set” (RETAIN) under Attributes. The block interface should now show the green RETAIN indicator on every declared tag.
  4. Declare the tags that previously lived in M-memory, e.g.:
    STRUCT
        SetpointRPM   : INT;       // formerly MW16  (WORD aligned to MW16)
        AuxTimer      : WORD;      // formerly MW22
        RecipeIndex   : WORD;      // formerly MW28
        Position_mm   : DINT;      // formerly MD54  (DINT, 4 bytes)
        CycleCounter  : DWORD;     // formerly MD112
        Totaliser     : LREAL;     // formerly MD200 (use 8 bytes for REAL/LREAL)
    END_STRUCT
  5. Confirm the declaration is free of overlap. The S7-300 compiler aligns tags on a WORD boundary; the offsets above will land at DBW16, DBW22, DBW28, DBD54, DBD112 and DBD200 — matching the original M-addresses one-to-one, which simplifies the search-and-replace step in the program.
  6. Compile the block (Ctrl+B) and verify in the inspector that the “Retain” column reads SET for every tag.

6. Step-by-Step — Migrate the User Program

  1. Open Project → Cross-references and filter for MW16, MW22, MW28, MD54, MD112, MD200. Record every call site in OB1, OB35, OB100, FCs and FBs.
  2. For each occurrence, perform Replace → Operand with the corresponding DB operand:
    Old operand New operand (absolute) New operand (symbolic)
    MW 16 DB100.DBW 16 "dbRetain".SetpointRPM
    MW 22 DB100.DBW 22 "dbRetain".AuxTimer
    MW 28 DB100.DBW 28 "dbRetain".RecipeIndex
    MD 54 DB100.DBD 54 "dbRetain".Position_mm
    MD 112 DB100.DBD 112 "dbRetain".CycleCounter
    MD 200 DB100.DBD 200 "dbRetain".Totaliser
  3. Because the offsets are preserved, the conversion can be scripted with a Replace in project regular expression. TIA Portal V13 supports a limited regex flavour; use plain text replacement for each pattern.
  4. Re-run Compile → Software (rebuild all blocks). The compiler will flag any tag that conflicts with the DB interface (e.g. an indirect read that previously pointed inside the M area but now lands in undefined DB offset space).
  5. Open the Watch table and add both the old MW/MD addresses and the new DB tags side by side; verify that writes to the new symbols mirror into the watch window.

7. Step-by-Step — Update the WinCC 7.3 HMI Tags

WinCC 7.3 cannot read DBx.DBW tags directly through the OPC channel of a third-party PLC; it goes through the S7ONLINE / SIMATIC S7 PROTOCOL SUITE. Two integration paths are commonly used:

7.1 SIMATIC S7 Protocol Suite — direct DB tag

  1. In WinCC Explorer open Tag Management → SIMATIC S7 Protocol Suite → MPI (or PROFIBUS)New Tag.
  2. Set Data area = DB, DB number = 100, Offset = the absolute byte offset of the desired tag (16, 22, 28, 54, 112, 200).
  3. For MD200 (DWORD / LREAL) select the appropriate data length: 4 bytes for DWORD, 8 bytes for LREAL. WinCC will treat the LREAL as a 64-bit float.
  4. Assign the new tag to every HMI element that previously referenced the M flag. The HMI faceplate should now read the retained value after a CPU power cycle.

7.2 Symbolic HMI tag through TIA Portal integration

  1. In the TIA Portal HMI project, navigate to HMI tags → Show HMI tags of the S7 connection. TIA Portal V13 will surface the DB tags as selectable symbolic names.
  2. Drag dbRetain.SetpointRPM onto the HMI tag list; the connection editor resolves DB100.DBW16 automatically.
  3. Download the HMI station; WinCC Runtime will read/write the symbolic address through the same MPI/Profibus.
Diagnostic tip: if a WinCC tag stays at 0 after a power cycle even though the DB tag is correctly declared with RETAIN, check the WinCC Update cycle. A 1-second update combined with a 2-second acquisition cycle can mask the restoration; reduce the acquisition to 250 ms for verification, then restore the production value.

8. Verification & Commissioning Procedure

  1. Download the project (hardware + software) to the CPU 313C. Accept the prompt to delete all blocks; the SDB must be re-generated with the new DB structure.
  2. Switch the CPU to RUN. Open a watch table containing DB100.DBW16, DB100.DBW22, DB100.DBW28, DB100.DBD54, DB100.DBD112 and DB100.DBD200. Write distinctive values: 16#1234, 16#5678, 16#9ABC, 1234567, 9876543 and 3.14159E+0.
  3. Force a power OFF / power ON at the 24 V supply (or trigger an MRES). Allow at least 30 s for the MMC remanence to elapse before re-energising.
  4. Re-open the same watch table. All six values must reappear unchanged. The volatile M flags (e.g. MW0) must be 0.
  5. Trigger a STOP → RUN transition via the mode selector. The DB tags must remain unchanged. A RUN → STOP transition is also valid; STOP clears only the PAE/PAA, not the retentive DB.
  6. On the HMI faceplate, navigate to the screens bound to the migrated tags and confirm the values match the watch table.
  7. Archive the verification log — most plant quality systems require a screenshot of the watch table before and after the power cycle.

9. Alternative Methods and When to Use Them

Method Granularity MMC budget Migration effort Recommended use
DB with RETAIN (covered above) Per-tag Minimal (only used tags) Medium — touch all references Default choice for ≤ a few hundred retentive words
Range-based MB retain Byte-aligned range from MB0 Full range × byte count Zero — no code change Legacy code where every flag is meant to be retained
PLC tag table with “Retain” attribute (S7-1500 only) Per-tag Per-tag Low Not available on S7-300
Set/Reset flag → recipe DB on shutdown OB80 Per-tag via custom code None High Brown-out bridge with a UPS; avoids MMC wear
Store to MMC recipe on every change (SFC 213/214) Per-recipe Recipe file size Medium Process data that must survive MMC removal (e.g. batch IDs)

If the application must withstand MMC removal (operator swaps the card while the line is down), combine the DB-retain method with a Recipe function: the in-RAM retain is the first line of defence, and a periodic save to the MMC via SFC 213 (WR_REC) or WinCC recipe view is the second. Remember that DB retain alone does not survive a card pull — only the MMC-resident recipe does.

10. Memory Architecture — Why the DB Outlives the M-Byte

The CPU 313C has three physical memories, all of which contribute to retentivity:

Memory Volatile? Backed by Holds
Load memory (Flash on MMC) No MMC flash cells Project blocks, comments, recipes
Work memory (RAM) Yes Optional backup capacitor / battery Active OB/FB/FC/DB code & data
System memory (RAM) Partially Optional backup M flags, T timers, C counters, I/O process image

When the configured MB retentive range is N bytes, the operating system allocates an N-byte buffer in the system memory and refreshes it on every STOP/RESTART. The DB retain, in contrast, lives in the work memory and is restored from the load image during the start-up phase. The two mechanisms are independent: a project that marks MB0…MB31 as retentive and DB100 as RETAIN uses 32 bytes of system memory for the first range plus the full DB footprint in work memory for the second.

Capacity planning: the CPU 313C ships with 32 KB of work memory and 8 MB of load memory (MMC). A retentive DB of 256 bytes is negligible; a retentive DB of 32 KB will starve the active blocks and trigger the diagnostic “Insufficient work memory” with SF LED on. Always check CPU → Information → Memory usage after a build.

11. Troubleshooting Matrix

Symptom Most likely cause Diagnostic step Fix
DB tags reset to 0 after power cycle RETAIN attribute not set, or block is an instance DB Open DB properties → Attributes Tick Set (RETAIN) and recompile
Compile error: “Optimised block access not supported on S7-300” Optimised block enabled DB properties → General Uncheck Optimised block access
WinCC tag shows quality “bad” HMI tag points to absolute M address, not the DB WinCC tag list Re-point to DB100 / change offset
Watch table shows DBW16 = 16#0000 even though program writes to it Different DB number / overlay with a different tag in the same STRUCT Cross-reference, DB structure view Renumber DB or restructure the STRUCT
SF LED on, diagnostic buffer: “DB has been deleted” CPU restarted with MMC missing or new project downloaded without the DB Online → Accessible nodes Insert the MMC containing the original project, perform MRES, re-download
M flags between MB0 and MB31 stay retained even though only the DB was meant to be Legacy retentive range still configured Hardware configuration → CPU → Retentive memory Set Number of retentive MBs from MB0 to 0 (or to the smallest accepted value, e.g. 16)
Retentive value drifts by 1 LSB after several days MMC write wear on a recipe that is being updated too often Online → MMC diagnostics Move the high-frequency update out of the recipe and into the RAM DB

12. Frequently Asked Questions

Why does TIA Portal V13 only let me enter the start and end of retentive memory on the S7-300?

The S7-300 firmware (CPU 313C included) stores retentivity as a single numeric range in SDB 0. The properties dialog is a direct representation of that limitation. For tag-level granularity, declare a Shared DB with the RETAIN attribute and replace the M operands with DB operands.

Is the DB retain attribute preserved when the same project is migrated to a S7-1500?

Yes. The RETAIN attribute is part of the DB interface and is round-tripped by TIA Portal. The S7-1500 firmware additionally exposes per-tag retentive control in the PLC tag table, but the DB-level attribute continues to work identically.

Do I still need a backup battery on the CPU 313C if I use DB retain?

Yes, if you also use retentive MBs, S7 timers, or S7 counters. The battery backs the system memory; the MMC backs the load memory but only preserves DB retain while the card remains in the slot. Without a battery or capacitor, a power loss longer than the MMC remanence time (~ 1 s to a few seconds) will zero the retentive DB.

How many bytes can a single retentive DB hold on the CPU 313C?

The upper limit is the work memory available after the active blocks are loaded. With the standard 32 KB work memory, a project that occupies 18 KB for code leaves roughly 14 KB for data. In practice, 4 KB retentive DBs are routine; anything above 16 KB will trigger a warning during download.

Can WinCC 7.3 read a symbolic HMI tag from TIA Portal V13, or must I use absolute DB addresses?

Both are supported. The TIA-integrated WinCC configuration in TIA Portal V13 (or WinCC Professional V13) creates symbolic HMI tags that point to the DB. In a standalone WinCC 7.3 project, configure the connection manually with Data area = DB, DB number = 100, and the absolute byte offset; the symbolic name is purely a TIA Portal convenience.

Back to blog