1. Overview
The Siemens 1PH7 288-2NF050AA3-Z is a member of the SIMOTICS M family of squirrel-cage induction motors (asynchronous three-phase motors) typically deployed as main spindle or feed drives in machine tools. Although cataloged as a motor, the electromagnetic principle of a three-phase induction machine is fully reversible: when the rotor is driven above synchronous speed by an external mechanical prime mover, the machine becomes an induction generator and delivers real power to its stator terminals. When paired with a Sinamics S120 drive line-up built around an Active Line Module (ALM), the regenerated energy is inverted and fed back into the line supply (grid feedback), so the 1PH7 can be operated continuously as a generator/alternator in industrial test benches, dynamometer stands, kinetic energy recovery systems, and hydro/wind micro-generation packages.
This reference walks through the system identification, control architecture, software commissioning with STARTER, parameterization for generator/regenerative operation, and verification checks for the following equipment stack:
- 1PH7 288-2NF050AA3-Z induction motor (frame size 288, forced-ventilated)
- 6SL3300-7TE35-0AA0 Active Interface Module (AIM)
- 6SL3335-7TE35-0AA0 Active Line Module (ALM)
- 6SL3325-1TE36-1AA0 Sinamics S120 Motor Module (booksize/chassis variant)
- CU320-2 Control Unit (implicit to the S120 line-up)
All commissioning steps assume STARTER V5.x or the TIA Portal equivalent SINAMICS Startdrive, communicating with the drive over PROFIBUS, PROFINET, or Ethernet service interface.
2. Decoding the 1PH7 288-2NF050AA3-Z Part Number
The Siemens SIMOTICS M type designation follows a structured code. Confirm the exact data on the motor rating plate against the order documents before relying on any inferred value.
| Position | Code | Meaning (per Siemens D81.1 catalog convention) |
|---|---|---|
| 1-4 | 1PH7 | SIMOTICS M induction motor, water- or air-cooled |
| 5-7 | 288 | Shaft height 288 mm (frame size) |
| 8 | 2 | Cooling method 2 = forced ventilation (separately driven fan) |
| 9 | N | Speed/pole-pair variant (N-class speed range) |
| 10 | F | Length/core-build code (frame length F within the 288 shaft height) |
| 11-13 | 050 | Winding/power code (rated power bracket) |
| 14-15 | AA | Encoder / feedback variant (typically DRIVE-CLiQ absolute encoder, e.g. AM22DQN) |
| 16 | 3 | Mounting / construction option |
| 17 | Z | Special variant (custom option suffix, must be checked against drawing) |
3. Drive Line-up Topology
The Sinamics S120 is a modular drive system. The line-up recommended for a high-power 1PH7 (frame 288 typically corresponds to >100 kW continuous) is the Chassis format with an active front end, because chassis Active Line Modules are bidirectional and can return energy to the line. The interconnection is:
3-phase line supply → line reactor (typically integrated in AIM) → Active Interface Module 6SL3300-7TE35-0AA0 (LC filtering, pre-charge, voltage sensing) → DC link → Active Line Module 6SL3335-7TE35-0AA0 (IGBT inverter, line-side) → shared DC bus → Motor Module 6SL3325-1TE36-1AA0 (motor-side inverter) → 1PH7 motor stator.
The Active Line Module is the key component that enables regeneration. Unlike a Basic Line Module (diode rectifier) or Smart Line Module (transistor rectifier with brake chopper only), the ALM uses IGBTs in an active front-end topology and a clean-up filter (AIM) to draw nearly sinusoidal current and to allow bidirectional power flow. When the DC link voltage rises above the rectified line peak (controlled threshold, typically around 1.5-1.6 × Vline,LL,RMS), the ALM transitions seamlessly into inverter mode and exports the surplus energy to the grid.
The Motor Module 6SL3325-1TE36-1AA0 in the user's stack is sized for high motor current. In motoring mode it converts DC to variable-frequency, variable-voltage AC for the stator. In generator mode the same inverter operates as a synchronous rectifier, converting the stator's variable-frequency, variable-voltage AC into DC for the DC link. The ALM then ships that energy to the line.
4. Generator Mode Operating Principle
An induction machine delivers mechanical power Pmech = T · ωm when the rotor turns faster than the synchronous speed set by the stator frequency. The slip s = (ns - nm) / ns becomes negative, the air-gap torque reverses, and energy flows from the shaft to the stator. The Sinamics S120 uses field-oriented control (vector control) to maintain a defined flux in the machine even when the rotor is being driven by an external load, so the same control structure used for high-dynamic spindle operation also works for generator operation.
Three conditions must be satisfied:
- The stator must be excited with controllable voltage/frequency (the Motor Module does this).
- External mechanical energy must drive the shaft above synchronous speed (a prime mover - turbine, engine, flywheel, dynamometer motor - is required).
- The DC link must accept the energy and the ALM must feed it back to a stiff, in-tolerance line supply.
If the line is lost or distorted, the ALM will inhibit regen and the DC link will rise. The drive's integrated braking chopper (if equipped) or an external brake resistor will clamp the DC bus, and the drive will trip with F30002 (DC link overvoltage) or F07900 (Line failure detected by ALM) as a safety response.
5. Prerequisites
Before recommissioning the stack in generating mode, verify the following:
| Item | Requirement |
|---|---|
| Line supply | 3-phase 380-480 V, 50/60 Hz, TN/TT grounded, with a transformer impedance of at least 1 % uk for proper ALM operation |
| Wiring | Stator cables shielded, symmetrical, length observed per S120 manual; PE bonded at both ends with 360° EMC glands |
| Encoder | DRIVE-CLiQ encoder on the motor, connected to a Sensor Module Cabinet (SMC) - typically SMC20 for incremental encoders or SMC40 for absolute EnDat/SSI |
| Cooling | Forced-ventilation fan powered (the 1PH7 288 "2" cooling code), air flow clear, intake filters clean, ambient ≤ 40 °C |
| Mechanical | Shaft grounded to avoid bearing currents; coupling aligned, key removed or captured, rotor free to spin without obstruction |
| Commissioning PC | STARTER installed (free download from SIOS) and a working Ethernet or PROFIBUS connection to the CU320-2 |
| Documentation | Order-specific datasheet, S120 Function Manual, S120 List Manual, Active Line Module Manual on hand |
6. Software: STARTER Setup
STARTER (Startdrive commissioning tool) is the recommended commissioning suite for legacy Sinamics S120 systems and is still distributed free of charge. The official entry point is the SIOS article STARTER commissioning tool download and overview (SIOS 26233208). Newer TIA Portal users can also commission the S120 with SINAMICS Startdrive, but the parameter numbers are identical.
General commissioning flow inside STARTER:
- Create a new project: Project → New → Create new project, give it a meaningful name, and insert the drive unit at the correct topology level.
- Set the PG/PC interface: Options → Set PG/PC interface. Select the Ethernet adapter bound to the S120 service access (default IP 169.254.11.22 on the CU320-2 X120, or the PROFINET name configured for the project).
- Connect online: highlight the drive and click Connect to target system. Use Accessible nodes if the IP is unknown.
- Automatic configuration: in the configuration tree, right-click the drive and choose Automatic configuration. STARTER will read out the topology from the DRIVE-CLiQ ports, identify the AIM, ALM, Motor Module, and encoder, and populate the device list.
- Motor identification: enter the motor data from the 1PH7 nameplate (rated voltage, current, power, power factor, speed, torque) into the motor wizard. The values flow into parameters p0304, p0305, p0307, p0308, p0310, p0311, p0314, p0335.
- Encoder selection: confirm the encoder type matches what STARTER autodetected. Adjust p0400 family if a non-DRIVE-CLiQ encoder is wired through an SMC.
- Control mode: choose vector control with speed controller (p1300 = 21) for the most stable generator behavior. Sensorless vector control (p1300 = 22) can be used above a minimum speed (typically 10-20 % of rated) if encoder feedback is unavailable, but for a grid-tied generator operation with a stiff prime mover, encoder-based vector control is preferred.
- Download: Target system → Load to target device (with copy RAM to ROM) to push the project to the CU320-2.
7. Step-by-Step Commissioning in Generator Mode
Use the S120 List Manual and the S120 Function Manual as the authoritative reference. The full manuals are linked at the end of this article. The procedure below assumes the project is online and the topology has been read out successfully.
- Power up the line, then the 24 V Control Unit supply. The CU320-2 boots and the AIM/ALM pre-charge the DC link. Wait for the "Ready" LED on the ALM.
- Run motor data identification (motoring): p1910 = 1, then issue ON to spin the shaft. The drive measures stator resistance, leakage reactance, and magnetizing curve. Wait for the routine to complete, then acknowledge any F0793x alarm.
- Run rotating measurement: p1960 = 1, then ON. The drive accelerates to a set speed, measures the moment of inertia and friction, and updates p1115, p1121, p0341, p0342. Allow the routine to finish without external torque disturbance.
- Configure the speed controller: p1460 (Kp_n) and p1470 (Tn_n) can be left at the STARTER autotuning default; tighten only if the generator shows sustained oscillation when the prime mover applies step changes in torque.
- Configure the torque limits: p1520 = +rated motor torque, p1521 = -rated motor torque. Set p1530 (motoring power limit) and p1531 (regenerative power limit) to the rated motor power (p0307). For generator-only operation, increase p1531 up to the value the mechanical system can absorb at overspeed, but do not exceed the Motor Module's rated I (p0205).
- Enable ramp-function generator: p1120 (ramp-up) and p1121 (ramp-down) should be configured for the prime mover's safe acceleration. A slow ramp prevents inrush at the moment the line is paralleled.
- Configure the signal sources for control words: in generator mode the speed setpoint typically comes from a fixed value (p1001, p1002, ...) or from a higher-level controller. Wire the source to p1070 (main setpoint) and the ON/OFF1 commands per your PLC/control strategy.
- Decide on droop / grid-parallel vs. island: for true grid-parallel operation with closed-loop active and reactive power control, you must use the ALM's Line droop (p5401) and active power controller (p5402) and a separate synchronization check. The S120 ALM is normally a line-follower (it locks to the grid); it does not black-start. For islanded generator operation an upstream controller (e.g. SIMATIC S7 with SINAMICS blocks) regulates the setpoint.
- Save the project: Target system → Copy RAM to ROM, then back up the project file on the engineering station and on a CF card inserted in the CU320-2 (if used).
- First run in generator mode: with the prime mover at rest, give the drive ON. Bring the prime mover up to rated speed slowly. Watch the ALM display: the line-side power readout (r0032, r0080) should swing negative as soon as the rotor exceeds synchronous speed. Check r0046.29 (ALM in regen) and r0082.3 (line feed-in active) in STARTER's trace.
8. Key Parameters for Generator Operation
The numbers below are the S120 standard indexing. Always cross-check with the active firmware version's List Manual, because parameter numbers and ranges change between firmware releases. The values shown are conservative defaults; actual commissioning must use the project's real motor data.
| Parameter | Name | Generator-Mode Relevance |
|---|---|---|
| p0300 / p0301 | Motor type / selection | Select 1PH7 induction motor (code per List Manual) |
| p0304-p0314 | Rated V / I / P / cosφ / n / T / f | Entered from the 1PH7 nameplate; defines the operating envelope |
| p0320 / p0321 | Rated magnetizing current / flux | Used by the field-weakening model; important at overspeed |
| p1082 | Maximum speed | Set to the maximum safe overspeed of the prime mover, not above the motor's mechanical limit |
| p1300 | Open/closed-loop control mode | 21 = speed-controlled vector control with encoder (recommended) |
| p1500 | Torque setpoint source | Wire to the higher-level controller for power-limiting generator mode |
| p1520 / p1521 | Torque limit upper / lower | Define the motoring and generating torque envelopes |
| p1530 / p1531 | Power limit motoring / regenerative | Set p1531 to the desired maximum regen power |
| p1610 / p1611 | Torque limit static / dynamic | Use to cap transient torque during line disturbances |
| p1900 | Motor data identification | Trigger stationary + rotating measurement for an accurate model |
| p5401 | Line droop activation (ALM) | Enables ALM droop control for parallel operation with other sources |
| p5402 / p5403 | Active / reactive power setpoint (ALM) | Used in grid-parallel generator operation |
| r0032 / r0080 | Active power smoothed / actual | Negative value indicates regen (export to grid) |
| r0046.29 | ALM status: regenerating | Boolean status flag for trace recording |
| r0082.3 | Line feed-in active | Boolean status flag for trace recording |
9. Active Line Module - Line-Side Configuration
Because the regenerated energy is exported through the ALM, the line-side parameterization is as important as the motor-side parameterization.
- Line voltage (p0210): enter the actual line-to-line RMS voltage at the AIM terminals, not the nominal grid voltage. Voltages of 380 V, 400 V, 415 V, 440 V, 460 V, and 480 V are common and each shifts the DC link setpoint.
- Line frequency (p0211): 50 Hz or 60 Hz, with the appropriate PLL bandwidth (p3400).
- Pre-charge and line monitoring: keep p0278 (line monitoring time) at the default 2 s. The ALM performs a phase, voltage, and frequency check on every line connection; if the check fails the drive trips with F07900/F07901.
- DC link setpoint: p3510 controls the ALM's DC voltage target. The default is derived from p0210 and is typically 1.5 × Vline,LL,peak / √2. Do not reduce it below the motor's rectified EMF at maximum speed, or the Motor Module will pull the DC link down and stall in regen.
- Reactive power / cosφ: by default the ALM is set to cosφ = 1 (no reactive current). For grid code compliance, adjust p5420 (reactive current setpoint) and configure the droop characteristic (p5421) per the utility requirements.
10. Encoder, SMC, and Speed Feedback
The 1PH7 288-2NF050AA3-Z typically ships with a DRIVE-CLiQ encoder (e.g. AM22DQN) connected through a Sensor Module. Verify the Sensor Module's DRIVE-CLiQ port lights up green. If the drive reports F3x051 (encoder fault), check the DRIVE-CLiQ cable for damage and confirm p0430, p0431, and p0432 (encoder word/bit configuration) match the encoder data sheet. After replacing an encoder, always re-run p0440 = 1 (accept encoder) and p1990 = 1 (encoder tuning) so the commutation offset is relearned.
11. Cooling and Thermal Limits
The 1PH7 288 has a frame-size thermal envelope that the drive monitors via KTY84/PTC inputs wired through a Terminal Module (TM31/TM120). The Motor Module's I2t model (p0290-p0299) and the motor's thermal model (p0610-p0613) must both be enabled to protect against:
- Sustained regen at low speed (poor self-ventilation on the 1PH7 with separate fan only - the fan is independent of rotor speed).
- Repeated overcurrent transients during grid faults (the ALM will momentarily block regen, raising DC link and forcing the motor into field-weakening; this can overheat the rotor).
Configure the overtemperature responses (p0610 = 1 = warning + fault) and verify with the trace tool that the motor temperature model stays below 100 % during a full power regen cycle.
12. Verification and Acceptance Test
Use the STARTER trace recorder to capture the following quantities during a controlled no-load regen ramp:
- r0021 (motor speed) - should track the setpoint with no oscillation.
- r0027 (output current amplitude) - should be smooth, no DC offset.
- r0030 (torque actual) - should be slightly negative (generator torque).
- r0032 / r0080 (active power) - should go negative when the prime mover crosses synchronous speed.
- r0082 (ALM status word) - bit 3 (line feed-in) should set.
- ZSW1 (status word 1) from the Motor Module - bit 14 (regen active in vector control) should set.
Acceptance criteria:
| Check | Pass Criterion |
|---|---|
| Steady-state speed error | ≤ 0.5 % of rated speed at full regen power |
| Active power export | Equals the mechanical input power minus losses (target ≥ 92 % electrical efficiency at rated load) |
| Line current THD | ≤ 5 % at full regen (the AIM filter caps the harmonics; verify with a power analyzer) |
| Cosφ at PCC | 0.95-1.0 leading or as required by the grid code |
| Motor temperature | Stays within the thermal model below 100 % duty cycle |
| Fault-free runtime | 8 h continuous at rated regen power with no F-class faults |
13. Troubleshooting Matrix
| Symptom | Likely Cause | Action |
|---|---|---|
| F07900 line failure | Phase loss, frequency outside 47-63 Hz, voltage ±10 % | Measure line, adjust p0210 / p0211, inspect fuses |
| F30002 DC link overvoltage | ALM not absorbing regen energy, brake chopper missing or undersized | Verify ALM enable, check brake chopper threshold (p1360) |
| F07802 drive Ready, no regen | Torque/power limit set to 0, or motoring direction blocked | Check p1521 and p1531; verify control word bit for regen direction |
| F3x051 encoder fault | Damaged cable, mis-wired SMC, or wrong encoder configured | Replace DRIVE-CLiQ cable, verify p0400/p0430 |
| Speed oscillation | Speed controller gain too high, encoder noise | Reduce p1460 by 30 %, increase p1470 by 50 % |
| ALM does not feed in | Droop / power controller disabled, or setpoint clamps to 0 | Enable p5401, set r5402/5403 to desired active/reactive power |
| Motor overtemperature in regen | Self-vent fan not running, thermal model not enabled | Power the forced-vent fan, enable p0610 = 1 |
| F7452 / F7453 line PLL | Distorted supply, weak transformer | Check uk ≥ 1 %, install line reactor if needed |
14. Safety and Grid-Code Notes
Using a 1PH7 plus Sinamics S120 ALM as a grid-tied generator falls under the same local grid code (e.g. VDE-AR-N 4105 in Germany, IEEE 1547 in the US, AS/NZS 4777 in Australia/New Zealand) as any other inverter-based generation. Typical requirements include:
- Anti-islanding detection (the ALM implements passive methods but may need an external RoCoF relay).
- Frequency-dependent active power reduction (P(f) curve).
- Voltage-dependent reactive power (Q(U) curve).
- LVRT/HVRT behavior during grid faults.
Verify the project-specific protection settings with the local utility operator before energizing. The S120 supports many of these features through the ALM's free-function blocks, but the engineering effort is not trivial.
15. References for Further Reading
Authoritative Siemens documentation for this stack:
Can the Siemens 1PH7 288-2NF050AA3-Z induction motor be operated as a generator?
Yes. The 1PH7 is a squirrel-cage induction motor, and an induction machine is inherently reversible. When the rotor is driven above synchronous speed by a prime mover and the stator is excited by the Sinamics S120 Motor Module, the machine develops negative slip and exports electrical power to the DC link. With an Active Line Module (ALM) the energy is then inverted and returned to the supply grid.
Which Sinamics S120 Line Module is required for regenerative operation?
Use an Active Line Module (ALM) together with the matching Active Interface Module (AIM). Basic Line Modules cannot export energy to the line; Smart Line Modules can only brake via a chopper and a resistor. The ALM's IGBT-based active front end enables true bidirectional power flow with controlled DC link voltage and low line harmonics.
Which software is used to commission the 1PH7 in generator mode?
STARTER is the standard commissioning tool, available free of charge from the SIOS article 26233208. SINAMICS Startdrive inside TIA Portal is an alternative. Both use the same parameter numbers; for example p1300 = 21 selects sensor-based vector control, p1520/p1521 set the torque limits, and p1531 caps the regenerative power.
Does the ALM support black-start (islanded generator operation)?
No. The ALM is a line-follower: it requires an existing energized, in-tolerance grid at the line-side terminals to establish the DC link. For true black-start capability you need a separate voltage-source inverter or a controlled prime mover that brings the system up to nominal speed before the ALM is connected to the line.
What is the difference between 6SL3300-7TE35-0AA0 (AIM) and 6SL3335-7TE35-0AA0 (ALM)?
The AIM (Active Interface Module) contains the line-side filter components, pre-charge circuit, and voltage sensing hardware; it sits in series with the line ahead of the ALM. The ALM (Active Line Module) is the IGBT inverter module that performs the actual rectification/regeneration. Both are required for a clean, bidirectional, low-harmonic connection to the grid.
How is generated power observed in STARTER?
Monitor r0032 and r0080 (active power) - they go negative when the drive is exporting energy. The status word r0046 bit 29 indicates the ALM is in regen, and r0082 bit 3 confirms line feed-in is active. STARTER's trace tool can record all of these simultaneously during an acceptance test.