Configuring Sinamics G110 for Cyclic Timer Operation via DIN0

David Krause11 min read
SiemensTutorial / How-toVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Siemens SINAMICS G110 is a sub-3 kW single-phase/three-phase 230 V or 400 V inverter from the SINAMICS V20/G110/G120 family of modular drives. In small motor applications (pumps, fans, vibrators, conveyor feeders, vibratory bowl feeders, agitators), it is common to drive a load on a repetitive duty cycle rather than a continuously running setpoint. A typical field requirement is to run a small 45 W vibration motor at a fixed 50 Hz for ten seconds, then coast for fifty minutes, repeating each hour indefinitely without an operator pressing start after every power cycle.

The G110 supports this requirement natively through terminal control with a fixed frequency setpoint. The trick is to decouple the Start/Stop command (controlled by a cyclic timer's volt-free contact into DIN0) from the frequency reference (held at a fixed internal value). Once configured, the inverter self-runs whenever DIN0 is high, stops when DIN0 is low, and restarts automatically when the timer next closes its contact — no operator pushbutton required.

Safety: The mains input, DC-link and motor terminals of the SINAMICS G110 carry dangerous voltages even when the inverter is inoperative. After removing supply power, always wait a minimum of 5 minutes to allow the internal DC bus capacitors to discharge below 50 V before touching any terminal. Reference: SINAMICS G110 Operating Instructions (Compendium).

Prerequisites

  • Drive: SINAMICS G110 (any frame size appropriate to the motor; for a 45 W motor the smallest 0.12 kW / 120 W unit is mechanically adequate, although frame selection is usually based on input current and supply type).
  • Motor: 45 W three-phase or single-phase induction vibration motor rated for inverter operation (insulation class F, VFD-rated windings).
  • Supply: 1 AC 230 V or 3 AC 400 V per the inverter's nameplate.
  • Cyclic timer: A digital timer with a volt-free normally-open (NO) contact, for example the Grasslin talento 471 pro, Finder 88 series, or equivalent DIN-rail digital timer rated ≥ 24 V DC, 0.5 A minimum contact rating.
  • Commissioning tool: Basic Operator Panel (BOP) or the PC-based STARTER commissioning software via USS on the G110's RS485 port (optional but recommended for backup parameter storage).
  • Wiring: 0.5–1.5 mm² control cable, ferrules, and a 24 V DC source (the G110 supplies an internal +24 V on terminal 9 referenced to terminal 7 for digital inputs).

Hardware Topology

The cyclic timer is the master controller. It toggles a single volt-free contact. The G110's DIN0 reads the contact state as an ON/OFF1 command. The frequency is supplied internally by the inverter's fixed-frequency block so no analog wiring is required.

Cyclic Timer Talento 471 pro L N volt-free NO T = 60 min t_on = 10 s SINAMICS G110 9 (+24V) 7 (GND) 8 (DIN0) P0700=2 P0701=1 P1000=3 P1001=50.00 ramp: P1120/P1121 U-V-W output Vibration Motor 45 W 3 ~ 50 Hz U V W +24 V U V W

Wiring the Control Circuit

  1. Confirm discharge state. With supply isolated for >5 minutes, verify zero potential between L1 and PE using a CAT-III rated meter.
  2. Connect the +24 V source. The G110 provides an internal +24 V on terminal 9 referenced to terminal 7 (digital common). Do not apply an external 24 V unless the manufacturer's instructions explicitly permit it on the chosen variant.
  3. Wire the timer's NO contact. Route one side of the timer's volt-free NO contact to terminal 9 (+24 V). Route the other side of the contact to terminal 8 (DIN0). This is the digital input that will be assigned the ON/OFF1 function.
  4. Leave DIN1–DINn open. Do not strap them to +24 V; doing so may assign unintended functions (e.g. reverse, OFF2, fault acknowledge) per P0702, P0703, ... and prevent the drive from running.
  5. Connect the motor. Wire the 45 W vibration motor's U-V-W leads to the inverter's output terminals. Observe rotation direction; the SINAMICS G110 supports direction reversal only when commanded; here the direction is set by wiring phase sequence.
  6. Connect the supply. Apply L1/L2/L3 (or L/N for single-phase units) and PE to the input terminals. Torque per the label side-plate values.

Parameter Configuration

All parameters below are accessed from the BOP via the parameter number (e.g. P0700). Press P, arrow to the index, press P, edit, press P to confirm. The complete parameter list is documented in the SINAMICS G110 Operating Instructions (Compendium).

Parameter Factory Default Set Value Meaning
P0700[0] 1 2 Command source = digital inputs (terminals). Required so the timer contact drives Start/Stop.
P0701[0] 1 1 Function of DIN0 = ON/OFF1 (Run forward when high, remove when low).
P0702[0] 12 0 Disable DIN1 to avoid stray functions.
P0703[0] 0 0 Disable DIN2.
P0704[0] 0 0 Disable DIN3 (if present).
P1000[0] 2 3 Frequency setpoint source = Fixed frequency (no analog wiring needed).
P1001[0] 0.00 Hz 50.00 Fixed frequency 1 = 50 Hz.
P1011[0] 0 0 Fixed freq 1 active when no selection bits = 1 (i.e. always selected when P1000 = 3).
P1080[0] 0.00 Hz 0.00 Minimum frequency (leave at 0 unless low-speed operation is undesirable).
P1082[0] 50.00 Hz 50.00 Maximum frequency (clamp to 50 Hz for 50 Hz motor).
P1120[0] 10 s 0.5–2 s Ramp-up time. Shorten so the motor reaches 50 Hz within the 10 s window; vibration motors tolerate fast ramps.
P1121[0] 10 s 0.5–2 s Ramp-down time.
P1300[0] 0 0 Control mode = V/f linear (suitable for small induction motors without encoder).
P2000[0] 50.00 50.00 Reference frequency for serial scaling (keep at 50 Hz to match P1001).
Why P1000 = 3 (Fixed frequency) and not P1000 = 1 (MOP)? With the Motor Potentiometer (MOP) setpoint, the drive still requires the operator to raise the setpoint via DIN keys. After a power loss the MOP value defaults to the saved setpoint on some firmware revisions, but the safer choice for unattended cyclic operation is a fixed internal setpoint that is bound to the rated motor frequency by construction.

Configuring the Cyclic Timer

Set the Grasslin talento 471 pro (or equivalent) for an asymmetric repeating cycle with period T = 60 min and on-time ton = 10 s:

  1. Enter timer programming mode; select cycle rather than one-shot.
  2. Set T = 01:00:00 (h:mm:ss).
  3. Set ton = 00:00:10.
  4. Assign the output channel that drives the G110; confirm the contact type (NO).
  5. Power the timer from the same single-phase supply feeding the G110 so a supply loss resets both devices together.

The output contact is therefore closed for the first 10 s of every hour. While closed, +24 V is presented to terminal 8 (DIN0). The drive runs the motor at 50 Hz, decelerates over P1121, and waits. The next hour the contact closes again and the cycle repeats.

Verification & Commissioning

  1. Manual override test (BOP): With the timer contact open, set P0700 = 1 temporarily. Press the green Run key on the BOP. The motor should ramp to 50 Hz and run continuously. Press the red Stop key. The motor should coast or ramp down per P1121. This proves the power and motor wiring are correct before any timer logic is enabled.
  2. Restore terminal control: Set P0700 = 2. Confirm P0701 = 1.
  3. Short-cycle test: On the timer, temporarily set T = 30 s and ton = 10 s so the cycle is observable.
  4. Observe: The BOP should show r0002 = frequency in Hz. At 10 s after the timer closes the contact, the displayed frequency should rise from 0 to 50 Hz over P1120, hold at 50 Hz briefly, then ramp to 0 over P1121 as the contact opens.
  5. Verify 5+ cycles without faults. Check the fault buffer (r0947[0..7]) for any F-coded faults.
  6. Restore production timing: Set T = 60 min, ton = 10 s.

Fault Code Matrix & Troubleshooting

Symptom Likely Cause Diagnostic Remediation
Motor does not run when timer contact closes DIN0 not configured as ON/OFF1 BOP: P0701 = 1; check r0722 (DI status) Set P0701 = 1; re-verify wiring at terminal 8
Motor runs once after power-on then stops and never restarts Timer does not deliver a sustained signal, or command source still defaults to USS/Modbus Check P0700; measure voltage at terminal 8 with meter Set P0700 = 2; replace timer battery if applicable
Motor runs but at wrong speed P1000 not set to fixed, or analog input selected Check r0024 (output freq), P1000 Set P1000 = 3, P1001 = 50.00
Drive trips F0001 (overcurrent) at start Ramp too short for locked-rotor vibration motor Read r0947 Lengthen P1120 to 2–5 s
Drive trips F0002 (overvoltage) at stop Regenerative energy from decelerating inertia Read r0947 Lengthen P1121 to 3–5 s, or fit a brake resistor
Drive trips F0035 (auto restart failed) Wiring re-arrangement during auto-restart attempts Read r0947 Disable auto-restart (P1210 = 0) for unattended operation
Contact chatters or rapid ON/OFF Timer relay bounce Scope DIN0 vs. +24 V Add 100 ms debounce via P0724; use gold-contact timer relay

Advanced Topics

Running at a different fixed speed

To change the operating speed without editing P1001, wire an additional timer contact to DIN1 (terminal 9 on the BOP-side terminal block varies by frame — consult the wiring diagram in the SINAMICS G110 Operating Instructions). Set P0702 = 15 (fixed-frequency select bit 0) and program a second fixed frequency in P1002. Toggle DIN1 to choose between 50 Hz and an alternative setpoint.

Multiple fixed speeds via binary coding

Up to seven fixed frequencies are accessible via binary coding of DI inputs. Set P0701=15, P0702=16, P0703=17 to assign bit 0, bit 1 and bit 2 of fixed-frequency selection. Populate P1001..P1007 with the desired frequencies and P1011..P1015 with the binary activation pattern (e.g. P1012=1, P1013=2, P1014=4).

Override / inhibit via hardware enable

For a service-interlock or maintenance inhibit, wire a normally-closed pushbutton in series with the timer contact. While pressed, DIN0 is held low and the drive will not run, even if the timer is in its ON window. This is preferred to setting P0701 = 0 at runtime because it does not require parameter writes.

Battery-backed timer

If supply power to the timer is interrupted, the ciclo must resume after power restore. The Grasslin talento 471 pro retains its programmed timing parameters for up to ~3 years on its internal battery; on power restore it begins a fresh cycle. If the cycle phase is critical, consider a timer with EEPROM retention (e.g. Siemens Sirius 3RP25 or Finder 88.92).

Field-Commissioning Notes

  • Don't use the BOP Run key as a substitute for wiring DIN0. Pressing Run on the BOP requires P0700 = 1. The user complaint — “still have to push the start button after every power off” — is almost always traceable to P0700 being left at the factory default of 1 instead of being changed to 2.
  • Don't pulse DIN0 with 24 V at every power-on with a one-shot RC network. The G110 latches ON only while DIN0 is high; removing the signal triggers a controlled stop. A one-shot circuit will start the drive for one cycle then leave it disabled indefinitely.
  • Avoid USS or Modbus command source for this application. A cyclic timer cannot easily produce a serial frame; the terminal interface is the right physical layer.
  • Confirm motor insulation class. Inverter-fed vibration motors generate a higher dv/dt than direct-on-line starting. Class B insulation is generally acceptable for short cables (<10 m); Class F is recommended for longer runs or for switching frequencies above 4 kHz.
  • Mechanical considerations. Vibration motors draw 5–7× rated current during startup. The 0.12 kW G110 can deliver 150 % rated current for 60 s per the standard overload profile; verify that this is sufficient for the vibration motor's starting transient by observing r0026 during the first 1 s.

Safety & Standards Reference

  • EN 61800-5-1 — Adjustable speed electrical power drive systems: safety requirements. Verify clearances and creepage distances after field wiring.
  • EN 60204-1 — Safety of machinery: electrical equipment of machines. The drive must be integrated into the machine's emergency-stop category per this standard.
  • UL 508C — Power conversion equipment. Relevant for North American installations.

Always cross-reference the parameter numbers above against the specific G110 firmware version installed on the unit. The SINAMICS G110 Operating Instructions contains the master list and is the authoritative reference for parameter ranges and defaults.

FAQ

Why does my G110 require a manual start push after every power cycle?

The factory default P0700 = 1 enables BOP control. When the BOP Run key is pressed the drive latches ON, but a supply power loss clears the latch. Setting P0700 = 2 and P0701 = 1 makes the drive follow the DIN0 input directly, so a closed timer contact (with +24 V on terminal 9) will start the motor without any BOP action.

Can I drive DIN0 directly from an Arduino output pin?

Yes, but only if the Arduino GND is commoned with the G110's digital common (terminal 7) and the Arduino's high-level output is within 5–24 V. Driving an optocoupler or a small 24 V relay from the Arduino and using the relay's contact to bridge terminal 9 to terminal 8 is the field-proven isolation method.

How do I change the fixed run frequency from 50 Hz to 40 Hz?

Edit P1001 from the BOP, set it to 40.00, and press P to confirm. No re-wiring is needed because the frequency setpoint source is fixed, not analog.

What is the difference between ON/OFF1 (value 1) and ON reverse/OFF1 (value 2) on DIN0?

ON/OFF1 starts the motor in the positive direction. ON reverse/OFF1 starts the motor in the negative direction. For a vibration motor where direction is fixed, use ON/OFF1. Avoid ON reverse unless you have explicitly verified that the vibration motor's bearings and unbalanced mass tolerate reverse rotation.

How long must I wait after powering off before touching the terminals?

Per the SINAMICS G110 manual, wait a minimum of 5 minutes after removing supply power before touching any terminals. This allows the internal DC-link capacitors to discharge to a safe level. Always measure between L1 and PE with a CAT-III multimeter before contact.

Can I use a mechanical mains timer (synchronous clock motor) instead of a digital cyclic timer?

Yes, provided the timer's output contact rating is sufficient (at least 24 V DC, 0.5 A) and the contact is volt-free. The advantage of a digital cyclic timer is exact ON-time resolution; a 24-hour mechanical timer typically has a 15-minute minimum resolution and is not ideal for 10-second pulses.