Configuring SINAMICS G120 CU250S-2 HTL Speed Control with S7-1500
The SINAMICS G120 modular drive system paired with the CU250S-2 control unit and an HTL incremental encoder provides a deterministic, encoder-closed-loop speed-control platform for a continuously running conveyor driven by a SIMATIC S7-1500 PLC. The CU250S-2 supports universal vector control with encoder feedback, making it suitable for any G120 drive application with or without encoder feedback. This reference covers drive selection, Telegram 2/3 selection, encoder wiring, TIA Portal V13 SP1 configuration, and commissioning verification.
System Overview
The complete system comprises:
- SIMATIC S7-1500 CPU (e.g., CPU 1515-2 PN or CPU 1516-3 PN/DP)
- SINAMICS G120 power module (PM240-2, PM250, or PM330)
- CU250S-2 control unit (PROFINET or PROFIBUS variant)
- HTL incremental encoder on motor or load shaft (1024 PPR typical)
- Three-phase squirrel-cage induction motor
- STARTER or Startdrive commissioning tool
CU250S-2 Control Unit Variants and Ordering Data
The CU250S-2 control unit is available in two fieldbus variants. Both expose the same encoder interface, so the choice is driven by the fieldbus used for PLC integration.
| Variant | Order Number (MLFB) | Fieldbus | Encoder Interface | Typical Firmware |
|---|---|---|---|---|
| CU250S-2 PN | 6SL3246-0BA22-1FA0 | PROFINET / EtherNet/IP | HTL/TTL/SSI | V4.5 / V4.6 / V4.7 |
| CU250S-2 DP | 6SL3246-0BA22-1CA0 | PROFIBUS DP | HTL/TTL/SSI | V4.5 / V4.6 / V4.7 |
For PROFINET-based S7-1500 communication, select the PN variant. Common firmware versions deployed in 2020-2026 plants are V4.5, V4.6, and V4.7. Install the latest service pack (e.g., V4.7 SP10 or later) to obtain functional and security patches. The full ordering data and accessory list are documented in the SINAMICS G120 with CU250S-2 List Manual.
HTL Encoder Interface Specifications
The encoder interface is brought out on the 15-pin Sub-D connector X2100 on the front of the CU250S-2. The interface accepts single-ended or bipolar 24 V push-pull signals. Encoder type is selected with parameter p0400 (1 = HTL, 2 = TTL/SSI).
| Parameter | Specification |
|---|---|
| Signal level | HTL bipolar: high > 15 V, low < 5 V (24 V nominal) |
| Maximum input frequency | 500 kHz per channel (HTL) |
| Encoder supply | 24 V, max 350 mA, short-circuit proof |
| Minimum pulse count | 1 pulse per revolution |
| Maximum pulse count (HTL) | 20,000 pulses per revolution (bipolar recommended) |
| Direction detection | Yes (A/B quadrature, 4x evaluation) |
| Zero pulse | Yes (used for homing / reference) |
| Channels | A, A*, B, B*, N, N* |
Use 4x evaluation (p0430.13 = 1) to quadruple the effective resolution. For example, a 1024 PPR encoder yields 4096 counts per revolution at the drive level.
Startdrive vs STARTER: Commissioning Tool Selection
Startdrive is integrated into TIA Portal and is the recommended tool for new S7-1500 + G120 projects. STARTER remains supported for trace recordings, firmware updates on older control units, and projects with no S7-1500.
| Criterion | Startdrive (TIA Portal) | STARTER (Standalone) |
|---|---|---|
| Integration with PLC/HMI project | Yes, single project | No, separate project file |
| PROFINET device name assignment | Native, drag-and-drop | Manual via Topology Editor or PRONETA |
| Trace functionality | Yes (V15.1+) | Yes, more mature |
| Function generator | Limited | Full |
| Expert parameter list | Yes, with parameter view | Yes, with expert list |
| TIA Portal V13 SP1 support | Yes, with G120 HSP | Yes (STARTER V5.x) |
| Required additional package | Startdrive option in TIA Portal | None (free download) |
Recommendation: For this application, install Startdrive in TIA Portal V13 SP1 along with the matching Hardware Support Package (HSP) for SINAMICS G120 / CU250S-2. STARTER is only required if you need advanced trace functions or are updating firmware on a control unit that is not yet supported by the installed HSP.
PROFIdrive Telegram Selection
The PROFIdrive telegram defines the cyclic process data (PZD) layout exchanged between the S7-1500 and the drive. The choice of telegram is driven by the application requirements and whether S7-1500 Motion Control (MC_) blocks will be used.
| Telegram | PZD OUT (PLC → Drive) | PZD IN (Drive → PLC) | Function | MC_ Block Compatible |
|---|---|---|---|---|
| 1 | 2 words | 2 words | Speed control (basic) | No |
| 2 | 4 words | 4 words | Speed control with extended word (STW2/ZSW2) | No |
| 3 | 5 words | 5 words | Speed control with 32-bit position actual value (G1_XIST) | Yes |
| 5 | 9 words | 9 words | Speed control with DSC (Dynamic Servo Control) | Yes |
| 102 | 10 words | 10 words | Free mapping with speed and torque | Configurable |
| 103 | 10 words | 10 words | Speed/position with DSC, encoder 1 and 2 | Yes |
| 105 | 10 words | 10 words | Speed with DSC, 16-bit position | Yes |
| 110/111 | Configurable | Configurable | Free telegram (BICO-mapped PZD) | Configurable |
For a free-running conveyor with encoder-closed-loop speed control, Standard telegram 2 is the conventional choice. It provides:
- STW1 (control word 1): drive enable, OFF1/OFF2/OFF3, ramp-function generator control, fault acknowledge
- NSOLL_A (speed setpoint A): 16-bit normalized setpoint, range -16384 to +16384 (0x4000 hex = motor rated speed)
- ZSW1 (status word 1): drive ready, fault, run-up, setpoint-actual deviation within tolerance, actual speed reached
- NIST_A (actual speed A): 16-bit normalized actual speed
- STW2 / ZSW2: extended control and status (sign-of-life, additional status bits)
Use Telegram 3 or higher if:
- S7-1500 Motion Control (MC_) blocks such as MC_Power, MC_MoveVelocity, MC_Home are to be used.
- The application requires 32-bit encoder position feedback in the cyclic PZD (e.g., for synchronization of multiple drives).
- Dynamic Servo Control (DSC) is required for high-dynamic applications (less likely on a conveyor).
Why Telegram 2 Is the Correct Choice for a Free-Running Conveyor
Telegrams 3, 5, 103, 105, and 106 enable the drive-internal position controller. For a conveyor that never stops, the position controller is typically not desired because:
- Position-controlled telegrams are designed for positioning axes and may inject position corrections during steady-state speed operation.
- Telegram 2 keeps the drive in pure speed control (closed-loop vector control with encoder, p1300 = 21), which is the natural control mode for a continuously running conveyor.
- Position information can still be obtained via acyclic parameter access (r0480 encoder count, r0482 absolute position) or by mapping a free PZD word to the encoder count using a free telegram such as 110.
If the application needs MC_ blocks from the S7-1500, use Telegram 3 and configure the drive in TIA Portal as a positioning axis under Technology Objects > TO_Axis_PTO (with PROFIdrive) or TO_SynchronousAxis.
Telegram 2: PZD Layout and Bit Mapping
Output (PLC → Drive)
| Word | Name | Bit | Description |
|---|---|---|---|
| 1 | STW1 | 0 | ON / OFF1 (edge 0→1 enables drive; 0 = ramp stop) |
| 1 | STW1 | 1 | OFF2 (coast to stop) — 0 = coast |
| 1 | STW1 | 2 | OFF3 (quick stop) — 0 = quick ramp down |
| 1 | STW1 | 3 | Inverter enable (pulse enable) |
| 1 | STW1 | 4 | Ramp-function generator enable |
| 1 | STW1 | 5 | Start ramp-function generator (freeze setpoint) |
| 1 | STW1 | 6 | Setpoint enable |
| 1 | STW1 | 7 | Fault acknowledge (0→1 edge) |
| 1 | STW1 | 10 | Control by PLC (must be 1) |
| 2 | NSOLL_A | — | Speed setpoint A (16-bit normalized) |
| 3 | STW2 | 8-15 | Extended control word (sign of life, etc.) |
| 4 | (configurable) | — | Free PZD, default unused |
Input (Drive → PLC)
| Word | Name | Bit | Description |
|---|---|---|---|
| 1 | ZSW1 | 0 | Ready to switch on |
| 1 | ZSW1 | 1 | Ready to operate (DC bus charged) |
| 1 | ZSW1 | 2 | Operation enabled |
| 1 | ZSW1 | 3 | Fault present |
| 1 | ZSW1 | 4 | Coast stop active (OFF2) |
| 1 | ZSW1 | 5 | Quick stop active (OFF3) |
| 1 | ZSW1 | 6 | Switch-on inhibited |
| 1 | ZSW1 | 7 | Alarm present |
| 1 | ZSW1 | 8 | Speed setpoint/actual deviation within tolerance (n_set = n_act ± tolerance) |
| 1 | ZSW1 | 9 | Control requested (PLC has control) |
| 1 | ZSW1 | 10 | f or n reached (setpoint reached) |
| 1 | ZSW1 | 13 | No motor overtemperature alarm |
| 2 | NIST_A | — | Actual speed A (16-bit normalized) |
| 3 | ZSW2 | — | Extended status word |
| 4 | (configurable) | — | Free PZD, default unused |
Motion Control (MC_) Blocks and Telegram Compatibility
The S7-1500 motion control library (e.g., MC_Power, MC_MoveVelocity, MC_Home, MC_Reset, MC_ReadParameter) requires a PROFIdrive telegram that contains a position actual value (G1_XIST) and, for positioning, a position setpoint (G1_SOLL). Only telegrams 3, 5, 103, 105, and 106 expose these signals. Telegram 2 does not include any position data, so MC_ blocks cannot be used with it.
Decision matrix:
- If the application needs only speed control and the position can be derived by integrating the actual speed, integrate NIST_A in the PLC, or read the encoder raw value from r0480 via acyclic parameter access. Use Telegram 2.
- If S7-1500 MC_ blocks are required (e.g., for a synchronized line of multiple drives, or for S7-1500-based homing), use Telegram 3 or Telegram 5 with DSC for the highest dynamic response.
Step-by-Step Configuration in TIA Portal
Prerequisites
- TIA Portal V13 SP1 (or later) installed with the Startdrive option
- Hardware Support Package (HSP) for SINAMICS G120 / CU250S-2 installed (matching TIA Portal version)
- SIMATIC S7-1500 CPU with PROFINET interface (PN variant of CU250S-2 required for PROFINET)
- CU250S-2 PN control unit with firmware V4.5 or later
- HTL incremental encoder, 24 V bipolar, with shielded cable
Procedure
- Open TIA Portal and create a new project. Add the S7-1500 CPU under Devices & Networks.
- Open the Hardware Catalog and navigate to Drives > SINAMICS > G120 > Control Units > CU250S-2 PN. Drag the drive to the PROFINET network of the CPU. TIA Portal automatically assigns a device name and IP address (e.g., 192.168.0.10).
- Open the drive device configuration. Under Properties > PROFINET interface > Telegram configuration, select Standard telegram 2.
- Note the automatically assigned I/O addresses (e.g., PQW 256 to PQW 262 for output, PIW 256 to PIW 262 for input). These are the addresses used in the PLC program.
- Assign a PROFINET device name to the drive (e.g., "g120-conv1") via Online > Assign PROFINET device name. The device name must match the configured name in the TIA Portal project.
- Open the drive's parameter view and run the basic commissioning wizard: enter motor nameplate data, select encoder type = HTL, enter pulses-per-revolution (e.g., 1024), set the application class to "Speed control with encoder".
- Run motor identification (p1900 = 2 for static, p1900 = 1 for rotating) and speed controller auto-tuning (p1960 > 0).
- Compile and download the TIA Portal project to the S7-1500 CPU.
Key Drive Parameters for HTL Encoder Configuration
| Parameter | Default | Setting for HTL Application | Description |
|---|---|---|---|
| p0010 | 0 | 0 (Ready) | Commissioning parameter filter; 0 = normal operation |
| p0015 | 0 | Macro (e.g., 7 for HTL with no BICO) | Drive macro / I/O configuration preset |
| p0100 | 0 | 0 (Europe, 50 Hz, kW) | Motor standard / units |
| p0300 | 0 | 1 (induction motor) | Motor type selection |
| p0304 / p0305 / p0307 | — | Per motor nameplate | Rated voltage (V) / current (A) / power (kW) |
| p0310 / p0311 | — | Per motor nameplate | Rated frequency (Hz) / rated speed (rpm) |
| p0400 | 0 | 1 (HTL encoder) | Encoder type selection |
| p0408 | 2048 | Set to encoder PPR (e.g., 1024) | Encoder pulses per revolution |
| p0410 | 0 | 0 (no inversion) | Encoder inversion |
| p0430 | 0 | 0 | Encoder A/B track configuration |
| p0430.13 | 0 | 1 (recommended) | 4x evaluation (quadrature) |
| p1300 | 0 | 21 (vector control with encoder) | Open-loop / closed-loop control mode |
| p1120 / p1121 | 10 / 10 | 5-10 s typical | Ramp-up / ramp-down time |
| p1500 | 0 | 6 (PROFIdrive setpoint) | Setpoint source selection |
| p2000 | 1500 | Motor rated speed (e.g., 1450) | Reference speed for 0x4000 = rated |
| p2051 | — | Per telegram mapping | PROFIdrive PZD output (PLC→Drive) connector |
| p2053 | — | Per telegram mapping | PROFIdrive PZD input (Drive→PLC) connector |
| p8841 | — | Per telegram (DP only) | PZD output (PROFIBUS) |
PLC Programming: S7-1500 to G120 Communication
For Telegram 2, the S7-1500 exchanges 4 PZD words in each direction. Define a PLC data type (UDT) for clarity and use direct peripheral I/O writes/reads or the Siemens library block SINA_SPEED (FB 285).
UDT Definition (SCL)
TYPE UDT_G120_Telegram2 :
STRUCT
STW1 : WORD; // Output word 1: control word 1
NSOLL_A : INT; // Output word 2: speed setpoint (normalized)
STW2 : WORD; // Output word 3: extended control
unused : WORD; // Output word 4: not used in telegram 2
END_STRUCT;
END_TYPE;
TYPE UDT_G120_Telegram2_In :
STRUCT
ZSW1 : WORD; // Input word 1: status word 1
NIST_A : INT; // Input word 2: actual speed (normalized)
ZSW2 : WORD; // Input word 3: extended status
unused : WORD; // Input word 4: not used in telegram 2
END_STRUCT;
END_TYPE;
Setpoint Scaling
NSOLL_A is normalized such that 0x4000 (16384 decimal) corresponds to the reference speed p2000. To command 50% of rated speed, write 0x2000 (8192). To command full reverse, write 0xC000 (-16384). The sign and magnitude are defined in the PROFIdrive profile.
// SCL: enable drive and command 50% speed
"DB_Drive".STW1 := 16#047E; // OFF1, OFF2, OFF3 released; enable; ramp enable; no fault ack
"DB_Drive".NSOLL_A := 8192; // 50% of p2000
"DB_Drive".STW2 := 16#0000;
"DB_Drive".unused := 16#0000;
// After STW1 = 0x047E, set STW1 = 0x047F to latch ON (rising edge on bit 0)
// To command run: STW1 := 16#047F; (bits 0,1,2,3,4,5,6,10 = 1)
// To fault-ack: pulse STW1 bit 7 to 1 (0x04FF then 0x047F)
Using SINA_SPEED (FB 285)
Siemens provides a ready-made function block SINA_SPEED (FB 285, in the SINAMICS library) that wraps Telegram 2 and Telegram 3 control/status. For applications with multiple drives, using SINA_SPEED reduces programming effort and ensures consistent bit-level handling.
HTL Encoder Wiring (X2100)
Wire the HTL encoder to the 15-pin Sub-D connector X2100 on the front of the CU250S-2. Pin assignment (see SINAMICS G120 with CU250S-2 List Manual for the full pinout):
| Pin | Signal | Function |
|---|---|---|
| 1 | — | Reserved |
| 2 | — | Reserved |
| 3 | — | Reserved |
| 4 | P_Encoder | Encoder supply +24 V |
| 5 | M_Encoder | Encoder supply 0 V (ground) |
| 6 | Track A | Channel A (non-inverted) |
| 7 | Track A* | Channel A inverted (for bipolar HTL) |
| 8 | Track B | Channel B (non-inverted) |
| 9 | Track B* | Channel B inverted |
| 10 | Zero pulse N | Reference / index pulse |
| 11 | Zero pulse N* | Reference pulse inverted |
| 12-15 | — | Reserved / shield |
For a 3-wire single-ended HTL encoder, connect only A, B, N (and 24 V supply); leave the inverted channels (A*, B*, N*) open. For industrial environments with VFD-induced noise, use the bipolar (6-wire) connection with shielded twisted-pair cable (e.g., LiYCY 4x2x0.34).
Commissioning Procedure
- Apply 24 V control voltage and 400 V (or 480 V) main supply. Verify the CU250S-2 LED is solid green (RUN) and the PROFINET LEDs are flashing or solid green.
- In TIA Portal, go online to the drive and run the basic commissioning wizard in Startdrive: select application class = Standard Drive Control (Speed), enter motor nameplate data, select encoder type HTL (p0400 = 1), enter pulses per revolution (p0408).
- Set the application parameters: ramp-up time p1120, ramp-down time p1121, reference speed p2000, and speed setpoint source p1500 = 6 (PROFIdrive).
- Run the motor identification: p1900 = 2 (motor data identification, standstill) and p1960 > 0 (speed controller optimization, requires the motor to spin unloaded or in a safe state).
- Download the configuration to the S7-1500 and assign the PROFINET device name to the drive.
- From the PLC, set STW1 = 0x047E (basic enable) and NSOLL_A = 2000 (~12% speed). Confirm the drive accelerates to the setpoint. Verify ZSW1 bits 0, 1, 2 = 1 and bit 10 = 1 (f or n reached).
- Increment NSOLL_A in steps (e.g., 0x1000, 0x2000, 0x3000, 0x4000) and verify smooth ramp behavior and zero steady-state error.
- Trigger a fault simulation: disconnect the encoder, command a setpoint, and verify that the drive generates an encoder fault (F3xxxx) and that ZSW1 bit 3 = 1 in the PLC.
Verification Checklist
| Check | Expected |
|---|---|
| PROFINET connection between S7-1500 and CU250S-2 PN | LEDs green on both devices; Online status in TIA Portal; no PROFINET diagnostics |
| Drive ready after enable command | ZSW1 bits 0, 1, 2 = 1 (ready, ready to operate, operation enabled) |
| Setpoint-actual tracking | Deviation between NSOLL_A and NIST_A < 2% at constant setpoint |
| Encoder feedback active | r0061 (actual speed) matches r0021 (motor speed); r0061 source = encoder |
| Ramp behavior | p1120 ramp-up time matches configured value (e.g., 5 s from 0 to 1500 rpm) |
| Fault-free operation | No active F-codes in r0945 / r2122; no A-codes blocking operation |
| Fault propagation to PLC | ZSW1 bit 3 = 1 on drive fault; PLC fault handling activated within 1 cycle |
Troubleshooting Matrix
| Symptom | Probable Cause | Diagnostic Step | Resolution |
|---|---|---|---|
| Drive does not enable (ZSW1 bit 0 = 0) | STW1 bit 0 not edge-triggered, OFF2/OFF3 active, or STW1 bit 10 = 0 | Inspect STW1 bits 0-3 and bit 10 in the watch table | Set STW1 = 0x047E first, then 0x047F to latch ON; ensure bit 10 = 1 |
| F31117 (encoder signal level A/B out of tolerance) | HTL signal voltage low, cable too long, EMI | Measure A/B signal amplitude with oscilloscope at X2100; check encoder supply voltage at pins 4/5 | Use bipolar HTL connection; shorten cable; route away from VFD power cables; check shield termination |
| F3x015 (encoder fault) after motor ID | p0400 not set to HTL, p0408 wrong, or wiring error | Verify p0400 = 1, p0408 = encoder PPR; inspect X2100 wiring; check r0459 for encoder status | Set p0400 = 1; set p0408 to encoder PPR; rewire per pinout; re-run motor ID |
| Actual speed oscillates or hunts | Speed controller gain too high (p1470) or integral time too small (p1472) | Run Startdrive trace on r0061; observe oscillation frequency and amplitude | Reduce p1470 (gain) by 30%; increase p1472 (integral time) by 50%; re-run auto-tuning (p1960) |
| Drive ready but motor does not turn when setpoint written | NSOLL_A scaled incorrectly, or p2000 not set, or STW1 bit 6 = 0 | Verify p2000 = motor rated speed; check NSOLL_A value in trace; check STW1 bit 6 (setpoint enable) | Set p2000 = motor rated speed; ensure STW1 bit 6 = 1; scale NSOLL_A to 0x4000 = p2000 |
| PROFINET communication error (F08501 or PROFINET alarm) | Telegram mismatch, watchdog timeout, wrong device name | Check r2050/r2053 for PZD mapping; verify PROFINET device name; check TIA Portal topology | Reset telegram to 2 (p0922 = 2); re-assign PROFINET device name; check for duplicate IP addresses |
| Drive immediately faults on enable | Motor data incorrect, encoder PPR wrong, or p1300 mismatch | Read r0947 for the active fault code; verify p0304-p0311, p0400, p0408, p1300 | Re-run basic commissioning; correct motor nameplate data; set p1300 = 21 for closed-loop vector with encoder |
| Direction of rotation reversed | Encoder channels A and B swapped, or p0410 = 1 required | Verify X2100 pinout; check p0410 (encoder inversion) | Swap A and B at X2100; alternatively set p0410 = 1 to invert the encoder |
| Encoder error after long cable runs | Voltage drop on 24 V supply; signal attenuation | Measure encoder supply voltage at the encoder terminals (not at X2100) | Use larger cable gauge for supply; install a 24 V local power supply at the encoder; max cable length 100 m for HTL bipolar |
Position Feedback Without Telegram 3
If Telegram 2 is used and the application needs to know the conveyor position, several approaches are available:
- Read the encoder actual count via acyclic parameter access: r0480[0] returns the raw encoder count. Use RDREC/WRREC or the SINA_PARA block from the SINAMICS library.
- Read the absolute position after homing: r0482[0] returns the absolute position in LU (length units) once a homing procedure has been performed.
- Configure a free telegram (102, 103, 110, or 111) and map the encoder count to a free PZD word for cyclic transmission. For example, configure Telegram 110 and set p2051[x] = r0480[0] for the 32-bit encoder value to be transmitted in PZD words 3 and 4 of the input.
- Integrate NIST_A in the PLC over time. NIST_A is a 16-bit normalized value; sample it at a fixed PLC cycle time (e.g., 10 ms) and accumulate. This approach is less precise but avoids acyclic parameter access.
Typical Application Class and Control Mode
Startdrive's basic commissioning wizard offers several application classes. For a free-running conveyor with HTL encoder, select:
- Application class: Standard Drive Control
- Control mode: Speed control with encoder (p1300 = 21, encoderless = 0)
- Setpoint source: PROFIdrive telegram 2 (p1500 = 6)
This configuration yields a closed-loop vector speed control with a torque limit (p1520, p1521) and a ramp-function generator at the drive. The S7-1500 controls enable, setpoint, and fault acknowledge via the PROFIdrive cyclic data, while the drive handles torque limiting, ramp generation, and current control locally.
Safety Integration (STO)
The CU250S-2 includes Safe Torque Off (STO) as a standard safety function. STO is hardwired via terminals on the control unit and can be used independent of the PROFIdrive communication. For applications requiring a higher safety level (SS1, SS2, SLS, SDI), use the CU250S-2 with a fail-safe PLC (e.g., CPU 1515F-2 PN) and configure PROFIsafe telegrams on a separate slot.
| Safety Function | Required CU250S-2 Variant | Integration |
|---|---|---|
| STO (Safe Torque Off) | Standard CU250S-2 | Hardwired terminals |
| SS1, SS2, SLS, SDI | CU250S-2 with PROFIsafe license | PROFIsafe telegram + F-CPU |
Standards and PROFIdrive Profile
The PROFIdrive profile is maintained by PROFIBUS & PROFINET International (PI) and is implemented by Siemens in all SINAMICS drives. The current profile version (V4.2 as of 2024) defines standard telegrams 1-106 and the BICO interconnection rules. The conformance classes CC1-CC4 are relevant for different drive types:
- CC1: standard drives (G120 with CU250S-2 fits here)
- CC3: single-axis positioning (telegram 3, 5, 103, 105)
- CC4: synchronized axes with DSC (telegram 5, 105, 106)
Refer to the SINAMICS G120 with CU250S-2 Operating Instructions and the PROFIdrive Profile (PI) for normative details.
FAQ
Can I use Startdrive in TIA Portal V13 SP1 to commission a G120 with CU250S-2?
Yes. Startdrive is available in TIA Portal V13 SP1 and later, but you must install the matching Hardware Support Package (HSP) for SINAMICS G120 / CU250S-2. Verify the HSP version supports your drive firmware. For G120 firmware V4.7 SP3 or later, TIA Portal V15.1 or newer is recommended.
Which PROFIdrive telegram should I use for speed control with an HTL encoder on a conveyor?
For a free-running conveyor with closed-loop speed control only, use Standard telegram 2 (PZD 2/2, 4 words in and out). It provides control word 1, status word 1, speed setpoint, and actual speed. Telegram 3 or 5 is required only when S7-1500 Motion Control (MC_) blocks are used, because those require a 32-bit position actual value (G1_XIST) in the cyclic PZD.
Can I use MC_ blocks from the S7-1500 with Telegram 2?
No. The S7-1500 motion control library requires a PROFIdrive telegram that includes a position actual value. Only telegrams 3, 5, 103, 105, and 106 expose G1_XIST. For a pure speed-control conveyor, integrate the actual speed (NIST_A) in the PLC or read the encoder count via acyclic parameter access (r0480) instead of using MC_ blocks.
Does the CU250S-2 support HTL encoders directly?
Yes. The CU250S-2 includes a built-in HTL/TTL/SSI encoder interface on the 15-pin Sub-D connector X2100. Configure p0400 = 1 for HTL and p0408 to the encoder's pulses per revolution. The interface accepts bipolar 24 V push-pull signals with a maximum input frequency of 500 kHz per channel and supports 4x quadrature evaluation for 4x effective resolution.
How do I scale the speed setpoint NSOLL_A?
NSOLL_A is a 16-bit normalized value where 0x4000 (16384 decimal) corresponds to the reference speed p2000. Set p2000 to the motor rated speed. To command 50% of rated speed, write 0x2000 (8192). Negative values rotate in the opposite direction. The drive scales NSOLL_A to internal rpm according to p2000 and the active ramp-function generator.
What happens if the encoder cable is disconnected at runtime?
The drive generates an encoder fault (F3xxxx, e.g., F31117) within one speed-controller cycle, removes the inverter pulse enable, and reports ZSW1 bit 3 (fault) to the S7-1500. The drive enters OFF2 (coast stop) by default. To recover, clear the fault from the PLC (pulse STW1 bit 7) once the encoder cable is reconnected and the fault is acknowledged.