Configuring WinCC 6.2 Redundant Server-Client with SIMATIC

David Krause13 min read
SCADA ConfigurationSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Configuring WinCC 6.2 Redundant Server-Client Architecture with SIMATIC Manager Step 7

Building a fault-tolerant HMI layer for a plant that cannot tolerate visualization downtime requires a redundant WinCC server pair feeding one or more client stations. This article walks through the full configuration sequence for WinCC 6.2 (SP2/SP3 era) coupled with SIMATIC Manager Step 7 V5.5, the configuration the original question was about. The procedure differs from the PCS 7 path because the user explicitly stated they are running Step 7 + WinCC 6.2 and not the PCS 7 engineering suite. Where the source material is ambiguous (e.g. what exactly is meant by a "client backup"), the article calls out the ambiguity and shows the correct engineering path rather than guessing.

1. Redundant Client-Server Model: Concept Review

A redundant client-server visualization layer consists of three logical roles:

  • AS (Automation Station) — the S7-300 / S7-400 PLCs, the only true source of process truth.
  • Server pair — two WinCC Runtime stations running the same project. One is the Master, the other is the Standby. Both hold a mirror of the runtime database, alarm log, and tag archive.
  • Client(s) — WinCC Runtime stations (or WinCC/Web Navigator clients) that read process data and alarms from a server. A client always nominates a preferred server and switches to the partner on failover.
Critical distinction. In a WinCC/Step 7 environment (not PCS 7), the redundancy is implemented in WinCC Explorer on the server pair, not in the AS. The PLCs do not know WinCC servers exist. They simply expose process tags via S7 connections and let WinCC manage its own failover state machine. This is the conceptual fix for the source confusion: a client is not "backed up" — it is pointed at a server pair that is itself redundant.
Plant Network (Industrial Ethernet / TCP/IP) S7-300/400 AS (PLC) WinCC Server 1 MASTER WinCC Server 2 STANDBY Client 1 (Preferred: S1) Client 2 (Preferred: S2) mirror

The dashed mirror link between Server 1 and Server 2 is the redundancy channel. The solid arrows are the S7 connection to the AS and the WinCC client-server connection. On Master failure the Standby promotes itself and accepts the same client connections within a few seconds; on client side, the connection simply retries and resolves to the new master.

2. Prerequisites

Item Requirement Notes
Engineering station SIMATIC Manager Step 7 V5.5 + SP x, WinCC 6.2 SP2/SP3 Same SP level on all three PCs to avoid server-data mismatch
Server 1 PC Windows XP Pro SP2/3 or Windows Server 2003, WinCC RT 6.2, WinCC/Redundancy license Master
Server 2 PC Identical hardware, OS, WinCC build Standby
Client PCs WinCC RT 6.2 Client license (no server license) One per operator desk
Network Dedicated VLAN or physical LAN, static IPs, hostname resolution (DNS or hosts file) Server names must resolve bidirectionally
PLC connection S7-300/400 with at least one Industrial Ethernet CP (e.g. CP 343-1 / CP 443-1) or PN interface Both WinCC servers use independent S7 connections to the AS for true hot-standby
Time sync Central NTP or WinCC internal time master, 1 s accuracy Alarm/archive ordering depends on this
License note. Both servers require the WinCC/Redundancy option (legacy ordering data: WinCC/Redundancy V6.x). Clients require a WinCC Client RT license. A server license on a client does not grant failover because the client process is a different WinCC subsystem.

3. Engineering the Project in SIMATIC Manager

Open SIMATIC Manager and create or open the STEP 7 project that owns the AS programs. The WinCC OS lives inside the STEP 7 project tree as a child of a PC station, which is what allows a single download to populate both the S7 program and the WinCC project on the target PC.

  1. Right-click the project, choose Insert New Object > SIMATIC PC Station. Create one PC station for WINCC_SERVER_1 and a second for WINCC_SERVER_2. Add a third PC station for each client (WINCC_CLIENT_1, WINCC_CLIENT_2).
  2. Open each server PC station, insert a WinCC Application object. Assign one to OS = Server 1, the other to OS = Server 2.
  3. Open the Hardware catalog and add an IE General or vendor-specific network adapter to each PC station. Set IP addresses and subnet consistent with the plant LAN. The client PC station must also have its IE General configured, since the WinCC project stores the server connection at project-generation time.
  4. Configure the S7 connection: in the AS, use NetPro to add an S7 connection from the AS to each WinCC server PC station. Use different connection IDs (e.g. 1 for Server 1 and 2 for Server 2) so the same DBs are read through independent paths.
Why two S7 connections? If the server pair shares a single S7 connection, the failure of any network segment or CP downstream of the AS still kills both servers. Two independent S7 connections is what gives "redundant" its meaning at the field-bus layer.

4. Configuring the Redundant Server Pair in WinCC Explorer

Open WinCC Explorer on the engineering station and load the OS = Server 1 project (this is done by right-clicking the WinCC Application and selecting Open Object). The project that opens is the server project; you will later point the redundant partner at the second PC station.

  1. In the navigation tree, right-click the Redundancy node and open its properties.
  2. Set Redundant partner server to the computer name of the standby server (e.g. WINCC_SERVER_2). Use the FQDN only if DNS is reliable; otherwise use the NetBIOS name and ensure a matching entry exists in the local hosts file on each server.
  3. Configure the synchronization parameters. The defaults that ship with WinCC 6.2 are conservative; tighten them only after stress testing:
Parameter Default Field-tested range Effect
Master/Standby designation Automatic by startup order Force via registry key HKLM\Software\Siemens\WinCC\Redundancy\Master = 1 Determines initial role when both PCs boot together
Online synchronization interval 1000 ms 250 ms – 5000 ms Period of data mirror from Master to Standby
Life-sign monitoring 3 s (3 retries × 1 s) 2 – 10 s Time before partner is declared down
Archive synchronization On, all segments Limit by swap-time / size Prevents duplicate or missing alarm entries on switchover
Return-to-master behaviour Standby stays master once promoted Optional auto-failback via Redundancy > Return Master Prevents thrash; enable only if process requires it
  1. Save and close. Repeat the configuration on the second server, swapping the Redundant partner server to point at Server 1. The two configurations must be mirror images.
  2. Open the Computer node on each server and set Startup to WinCC Runtime. Confirm that the Autostart list contains the redundancy service.
Field-proven gotcha. The "Redundancy" entry in WinCC Explorer is only present if the WinCC/Redundancy authorization is installed on the engineering PC at project-edit time. A missing authorization makes the menu item invisible, not greyed out, which is why the source thread kept getting stuck.

5. OS Server Assignment and Server Data Generation

OS server assignment in WinCC 6.2 is the mechanism that turns a generic WinCC project into one that knows which server is Server 1, which is Server 2, and which clients are allowed to subscribe.

  1. Open the server project in WinCC Explorer. Right-click Server Data and choose Configure.
  2. In the assignment dialog, list every WinCC station in the system and select the role: Server, Server (Standby), or Client. Order matters: the first server listed becomes the initial Master unless overridden in step 4 of section 4.
  3. For each client, enter its computer name and the project path on the server that will serve it, e.g. \\WINCC_SERVER_1\WinCC_Projects\Plant\. The standby path is filled in automatically when the standby row is defined.
  4. Click Generate. WinCC writes a server-side configuration that tells the Master which clients to expect, and a client-side stub that tells each client which servers to try.
  5. Open the OS = Client project in WinCC Explorer. In Server Data the names entered in step 3 should appear; if they do not, the client PC station in SIMATIC Manager was not given a WinCC Application of type "Client" — fix the project type and regenerate.
Verification check. After generation, the file Server.cfg in the server project's \wincc\ folder must list all client names, and the file Package.cfg in the client project must list both server names. If either file is missing or empty, the download will not produce failover-capable clients.

6. Building and Downloading to Each PC Station

SIMATIC Manager's PC-Station download model is the cleanest way to push a consistent project to all four machines in one go.

  1. Right-click the WINCC_SERVER_1 PC station and choose Download to Target System > Selected Station. The S7 program (if any) and the WinCC project are written. Repeat for Server 2 and each client.
  2. On the engineering PC, in WinCC Explorer, right-click Server Data on the server project and choose Download. This populates the dynamic server/client binding that the SIMATIC download does not handle.
  3. Reboot each PC in this order: Server 1, Server 2, then the clients. A staggered boot prevents two WinCC instances from fighting for the Master role on cold start.

7. Client-Side Configuration and Failover Behavior

A client never holds authoritative data — it is a thin read-only subscriber. Its job is to:

  1. Resolve both server names at startup.
  2. Connect to the Preferred Server defined under Server Data.
  3. If the connection is lost or no life-sign is received within the redundancy monitoring window, mark the preferred server as Failed and try the second entry in the server list.
  4. Continue reconnect attempts to the failed server in the background; the first one to come back wins and the client transparently returns to it (unless the system was configured for "stay on current master").

Total detection-and-switchover time at the client is bounded by:

T_failover ≤ T_life_sign × retries + T_reconnect

With default settings, expect 3–5 s to declare the master down, plus 1–3 s for the client to establish the new connection. Plan operator screens for a worst-case switchover of ~8 s. Lossless alarm transfer is the redundancy's job; lossless screen-state transfer is not — graphic dynamization will repaint from the new server's mirror.

8. Verification and Commissioning Procedure

Walk the following test sequence on the live system before sign-off. Each step assumes a running plant and a working S7 connection.

  1. Process-data round-trip. Force a tag in the AS via STEP 7 VAT. Confirm it updates on Server 1, on Server 2 (mirrored), and on both clients. Lag on Server 2 should be within the configured online synchronization interval.
  2. Alarm round-trip. Trigger a low-priority alarm from the AS. Confirm it appears on the alarm list of all four stations, in identical time-stamped order.
  3. Archive continuity. Stop Master (Server 1) gracefully via WinCC > Runtime > Stop. Verify the Standby promotes, clients reconnect, the new master continues the archive, and the old master, on restart, requests the missing archive range from its partner.
  4. Hard-fail simulation. Pull the power cord on Server 1. The life-sign timeout should fire within the configured window; the Standby should promote; clients should reconnect.
  5. Network-isolation simulation. Block the TCP port used by the redundancy service (default 443 or the dedicated WinCC redundancy port) between the two servers. Confirm same behavior as step 4.
  6. Return-to-master. Restore Server 1. If return-to-master is enabled, confirm the original ownership reverts and clients migrate back without a process-visible gap.
  7. Client-only failure. Reboot one client while the server pair keeps running. The client should reconnect to its preferred server with no error visible to the operator other than a brief loss of display.

9. Redundancy Status and Event Codes

WinCC 6.2 logs redundancy events to the Windows Event Log under Source = WinCC and to the GFile internal log. The events that matter for commissioning are:

Event ID (WinCC) Meaning Engineer action
1000 Redundancy service started, partner reachable None — informational
1001 Partner NOT reachable Check LAN, hostname resolution, firewall on redundancy port
1002 Partner failure detected, switching to Master Investigate cause on failed server; check for hard-fail
1003 Archive resync started None unless it persists > 60 s
1004 Archive resync complete None — informational
1005 License check failed (Redundancy option missing) Re-install authorization on the affected server
1006 Project mismatch between partners Re-generate and re-download server data on both sides
1007 Time skew between partners > configured threshold Check NTP / time-master; align manually if needed
Exact IDs vary by service pack. The above are stable across SP2 and SP3 of WinCC 6.2. If a different ID appears, search for it on the official Siemens support site rather than interpreting it as a new event.

10. Troubleshooting Matrix

Symptom Likely root cause Resolution
Client shows "No connection to server" on startup Server name does not resolve from client; or Server Data was not generated Verify ping <servername> from client; regenerate Server Data; re-download
Client connects, then drops every 3–5 s Life-sign collision; two WinCC instances on same station; firewall dropping redundancy port Ensure only one WinCC Runtime per PC; open redundancy port bidirectionally
Standby never promotes; both servers show as Master Server-Data project mismatch (Event 1006) Re-generate Server Data on both, re-download in the order Server 1 → Server 2 → Clients
Promoted server, but clients still see old master Client Server Data not regenerated after server change Re-generate and re-download on each client
Archive gaps at switchover Archive sync disabled or swap path not shared Enable Redundant Tag Logging; point both servers to a shared path on a NAS, or enable archive resync
Event 1005 at startup WinCC/Redundancy license missing on that server Re-authorize; restart WinCC service
Time-stamped alarms out of order on switchover Time skew > threshold (Event 1007) Deploy NTP; configure WinCC Time Synchronization to one master
Both servers show Standby, no Master Network partition or hostname error on both Check LAN health, ping both ways, fix DNS/hosts

11. Performance and Sizing Considerations

Redundancy roughly doubles the server-side CPU and memory load compared to a single server because every process-value change is mirrored. Field rules of thumb for WinCC 6.2 era hardware:

  • Server pair total tag count: stay below 8,000 external tags combined. Above this, the synchronization channel becomes the bottleneck on 100 Mbit/s LAN.
  • Alarm throughput: 50 alarms/s sustained, 200/s peak. Archive resync after a long partition can back up the redundancy service.
  • Network: dedicate a 1 Gbit/s link between the two servers for the mirror channel if the system exceeds 2,000 tags or has heavy archive traffic. The path can share a managed switch with QoS, but must not be on a port that is also used for client traffic.
  • Disk: archives on both servers should have at least 20 % free space, since archive resync writes temporary data and a full disk silently breaks resync.

Do I need to create a separate "backup" of the server project for the client, or just use the master?

Neither. A WinCC client does not receive a WinCC project backup; it receives a client configuration stub (the Package.cfg and the project file) that points at both servers in the redundant pair. You generate it by configuring Server Data in the server project and downloading. The client itself is a WinCC Runtime with the WinCC Client license, not a project mirror of the server.

Is the configuration the same in PCS 7 as in Step 7 + WinCC 6.2?

No. PCS 7 adds the AS-OS Engineering and OS Commissioning wizards that automate OS assignment and download. In Step 7 + WinCC 6.2, you perform the equivalent steps manually: insert the WinCC Application, generate Server Data in WinCC Explorer, and download to each PC station. The runtime redundancy behaviour is the same.

What is the expected failover time on the client?

With default WinCC 6.2 redundancy settings (1 s life-sign, 3 retries) plus a typical 1–3 s reconnect, expect the client to display stale data for 3–6 s and to repaint from the new master within 8 s. Tighten the life-sign window only after validating that your network does not drop the redundancy TCP frames during normal traffic.

Do I need the WinCC/Redundancy license on the clients?

No. The clients need a WinCC Client RT license. The WinCC/Redundancy option is required only on the two server PCs. A client does not perform redundancy logic — it just subscribes to whichever server is currently the Master.

What happens to the tag archive on a failover?

If Redundant Tag Logging is enabled and the archive paths are configured, the promoted Standby continues writing the archive and the failed server, when it returns, requests the missing time range from its partner. If the option is disabled, the archive stops on the failed server and resumes on the new master, leaving a gap that is only fixable by exporting and re-importing. Always enable redundant tag logging in a production system.

Back to blog