Configuring WinCC Communication to Siemens CP 443-1 via NetPro PC Station
This technical reference explains how to bring a WinCC SCADA station online with a SIMATIC S7-400 PLC through the CP 443-1 Industrial Ethernet communications processor using the legacy SIMATIC NetPro PC Station configuration. It covers IP address assignment rules, the OPC vs. TCP/IP driver decision, download semantics that prevent unintended CPU STOP transitions, and the OPC UA capability introduced on newer CP 443-1 firmware. Field engineers configuring STEP 7 V5.x projects against S7-400 will find the parameter tables, NetPro configuration steps, and verification checks needed to bring a WinCC channel into productive operation.
1. CP 443-1 Hardware Overview and Catalog Numbers
The CP 443-1 is the SIMATIC S7-400 module that terminates the PROFINET / Industrial Ethernet side of an AS-400 station. From a WinCC standpoint it is the IP endpoint where the SCADA station opens S7 connections (port 102 / ISO-TSAP) or — with newer firmware — OPC UA sessions (port 4840).
| Catalog Number | Ports | Typical FW | Notes for WinCC |
|---|---|---|---|
| 6GK7 443-1EX20-0XE0 | 1 × IE (RJ45) | V2.x / V3.x | Classic CP 443-1; supports S7 / PROFINET; no integrated OPC UA server in early FW |
| 6GK7 443-1EX30-0XE0 | 1 × IE (RJ45) | V3.x | CP 443-1 Advanced; supports OPC UA from firmware V3.0.10+ |
| 6GK7 443-1GX20-0XE0 | 4-port switch | V2.x / V3.x | Line / ring topologies; S7-400 and WinCC share the same switch |
| 6GK7 443-1GX30-0XE0 | 4-port switch | V3.x | Same as GX20 with OPC UA capability in later FW |
| 6GK7 443-1UX00-0XE0 | 1 × IE | V3.2+ | Variants explicitly featuring OPC UA server, ISO-on-TCP, and S7 routing |
The WinCC side does not care which CP 443-1 sub-variant is used as long as the IP layer is reachable. The differences surface when OPC UA is required: an OPC UA server inside the CP 443-1 became available with the introduction of the 6GK7 443-1UX00 variant and was back-ported to many EX/GX modules with firmware V3.2.x or later.
2. Architecture: PC Station, CP 443-1, and WinCC Relationship
In a STEP 7 V5.x project the SCADA computer is represented by a PC Station. The PC Station contains three types of objects:
- WinCC Application (the HMI/SCADA runtime)
- OPC Server (SIMATIC NET OPC server, used by WinCC's OPC channel and by external OPC clients)
- IE General — a software-only representation of an Industrial Ethernet interface such as the CP 1613 / CP 1623 PCI/PCIe card or the Softnet IE software interface used by standard onboard NICs
The PC Station does not download configuration into the S7-400 CPU. It downloads into the OPC Server and IE General configuration database on the SCADA PC. This is the single most important conceptual point when troubleshooting the "is this safe to download?" concern.
3. Prerequisites
- STEP 7 V5.5 (or later V5.x) with SIMATIC NetPro installed on the engineering station
- SIMATIC NET PC software on the SCADA PC matching the IE interface in use (Softnet IE for onboard NICs, Hardnet IE for CP 1613 / CP 1623)
- WinCC V7.0 SP3 or later (covers WinCC V7.2, V7.3, V7.4, V7.5)
- One free IP address in the same subnet as the CP 443-1 (for the SCADA PC NIC / IE General)
- CP 443-1 firmware loaded; for OPC UA capability, V3.2.x or the corresponding firmware per release notes
- Station Configuration Editor on the SCADA PC importing the same PC Station name as configured in NetPro
4. IP Address Assignment Rules
The rules below are derived directly from the SIMATIC NET manuals referenced by Siemens support entry "SIMATIC NET Communication Manual":
- Unique address. Each IE endpoint on the subnet must carry a unique IPv4 address. The IE General in the PC Station and the CP 443-1 must not share an IP.
- Same subnet. Both addresses must lie in the same subnet mask. With a /24 mask (255.255.255.0), 192.168.0.1 (CP 443-1) and 192.168.0.2 (WinCC PC) communicate directly. 192.168.0.1 and 192.168.1.2 would require routing and almost always fail silently in PC Station startup.
- PC NIC vs. IE General. The IP configured in the Windows network adapter for the SCADA PC must match the IP configured under Properties → IE General → IP Address in NetPro. Mismatches are the single most common cause of "Partner not reachable" faults from the OPC server.
- CP 443-1 default IP. Out of the box a CP 443-1 ships with no IP and is discovered via DCP / STEP 7 — do not assume a "default CP-443-1 PN/IO address" of any specific value. The address you read in STEP 7 Hardware Configuration under CP 443-1 Properties → Ethernet Interface is the authoritative value.
| Device | Address | Subnet Mask | Gateway |
|---|---|---|---|
| CP 443-1 (S7-400) | 192.168.0.1 | 255.255.255.0 | — |
| WinCC PC — NIC / IE General | 192.168.0.2 | 255.255.255.0 | — |
| Engineering PG (optional) | 192.168.0.3 | 255.255.255.0 | — |
| Other HMI / spare | 192.168.0.4 … .10 | 255.255.255.0 | — |
5. Step-by-Step: Configuring the PC Station in NetPro
The procedure below covers the legacy STEP 7 V5.x / NetPro flow. The TIA Portal equivalent is noted at the end of the section.
5.1 Add the PC Station
- Open the STEP 7 project containing the S7-400 station.
- Right-click the project → Insert New Object → SIMATIC PC Station.
- Rename the PC Station to match the Windows computer name of the SCADA PC (this is what the Station Configuration Editor on the PC will look for).
5.2 Insert WinCC Application
- In the PC Station hardware catalog, drag WinCC Application onto slot 1 (or the next free application slot).
- Open its properties and note the application name — this is the slot the running WinCC RT will occupy.
5.3 Insert OPC Server
- Drag OPC Server to the next application slot.
- This is the server WinCC's OPC channel talks to, and the one external SCADA clients connect to when sharing the OPC namespace.
5.4 Insert IE General and Assign IP
- Drag IE General to slot 4 or higher (depending on version) — that is where SIMATIC NET expects PC-side Ethernet interfaces.
- Double-click IE General → Properties → enter the IP Address, Subnet Mask, and (if needed) Router.
- Select the Network dropdown — choose Ethernet (1) to bind the IE General into the same subnet you will later connect with the CP 443-1.
5.5 Insert CP 443-1 in the S7-400 Station
- Open the SIMATIC 400 Station → Hardware.
- From the catalog, insert the correct CP 443-1 variant matching the module on the rack.
- Open its properties → assign IP, subnet mask, and select Ethernet (1) as the connected network.
- Confirm the rack and slot number match the physical placement in the S7-400.
5.6 Create S7 Connection in NetPro
- Right-click OPC Server in the PC Station → Insert New Connection → S7 Connection.
- Choose the CP 443-1 of the S7-400 as the connection partner.
- Set the local ID (e.g.
S7_Connection_1) — this is the name WinCC's TCP/IP driver or OPC channel will reference. - For each connection, NetPro assigns a slot-based TSAP (Transport Service Access Point) on both ends:
| Field | Typical value |
|---|---|
| Local TSAP (WinCC PC) | 01.01 (rack 0, slot 4 — OPC server) |
| Partner TSAP (CP 443-1) | 01.01 (rack 0, slot 3 — CPU) — confirm in CP 443-1 Properties → S7 Connection |
| Transport | ISO-on-TCP (RFC 1006), port 102 |
5.7 Compile and Download the PC Station
- In NetPro, click PC Station → Save and Compile (or Network → Save and Compile All).
- Right-click the PC Station → Download to Target System.
- In the "Select Target Station" dialog, enter the SCADA PC's IP address (it is the address bound to IE General, not the address of the CP 443-1).
- Confirm the download. This pushes the configuration into the Station Configuration Editor and SIMATIC NET on the SCADA PC only.
C:\Program Files\Siemens\Automation\SIMATIC_NET\). The PLC remains in RUN.
6. Selecting the WinCC Channel: TCP/IP, OPC, or OPC UA
WinCC V7.x ships with multiple channel DLLs in SIMATIC S7 Protocol Suite:
| Channel | Uses | Configuration item referenced | Strengths |
|---|---|---|---|
| TCP/IP | Native Softnet IE / IE General | Connection name from NetPro (e.g. S7_Connection_1), CP 443-1 IP, Rack/Slot |
Lowest runtime overhead; recommended when no external OPC clients are needed |
| Named Connections | STEP 7 symbolic names via PC Station OPC server | WinCC symbol export through STEP 7 → WinCC symbol table | Reuse of STEP 7 variable names; transparent for service |
| OPC DA (WinCC OPC channel) | SIMATIC NET OPC server (configured in step 5) | OPC item names | External clients can simultaneously read the same tags |
| OPC UA (WinCC OPC UA channel) | CP 443-1 OPC UA server (FW V3.2+) or external OPC UA server | OPC UA endpoint URL, security policy | Future-proof, vendor-neutral, supports S7-1200/1500 and S7-400 in parallel |
For most CP 443-1 deployments, the TCP/IP channel with WinCC's SIMATIC S7 Protocol Suite is the simplest and most direct path. Named Connections are functionally similar but route everything via the OPC server, which is convenient when you also want OPC DA for third-party MES clients. OPC UA is reserved for new plants or retrofits where you want to drop the S7 Protocol Suite dependency and rely on the OPC UA server embedded in the CP 443-1 or in the WinCC station itself.
6.1 OPC UA on CP 443-1 — When to Choose It
Per the Siemens release notes (referenced by the "Siemens releases CP 443-1 OPC UA communications processor" coverage), the CP 443-1 OPC UA variant exposes an embedded UA server on port 4840 according to OPC UA specification IEC 62541. Choose OPC UA on CP 443-1 when:
- The WinCC station is multi-vendor and needs to read from S7-400, S7-1500, and third-party controllers over a single stack.
- Network policy requires authenticated / encrypted transport (Basic256Sha256 security policies).
- You want to minimize SCADA-side S7 Protocol Suite licensing and rely on standard OPC UA client channels inside WinCC Professional.
7. WinCC Variable Configuration for CP 443-1 Connections
For each logical driver selection, the WinCC tag manager then binds tags to the connection:
| Channel | WinCC tag address example | Meaning |
|---|---|---|
| TCP/IP |
DB1,INT0 via connection S7_Connection_1
|
Data block 1, integer at offset 0 |
| Named Connections |
Motor1_Speed (symbol name from STEP 7) |
STEP 7 symbol alias, transparently resolved via OPC |
| OPC DA | S7:[S7_Connection_1]DB1,INT0 |
OPC DA item path |
| OPC UA |
ns=1;s=DB1,INT0 on endpoint opc.tcp://192.168.0.1:4840
|
OPC UA address space per IEC 62541 |
8. PC Station Download — Detailed Behavior
The question "is this download safe, or will it stop the PLC?" comes up regularly when commissioning engineers first encounter the PC Station. The answer is unambiguous:
- Target of the download: The PC Station download writes to Station Configuration Editor database and to the OPC server directory on the SCADA PC. It does not communicate with the S7-400 at all.
- Network path used: TCP/IP, port 102 is not opened for the PC Station download itself; NetPro uses the configured Ethernet path to the PC's SIMATIC NET Config API on a local service port (typically 102 or the Config service depending on SIMATIC NET version). It does not cross a router to the CPU.
- Effects on RUN/STOP: None. The CPU remains in its current operating mode.
- Restart required? Often yes: OPC server and IE General are services that reread configuration on service restart. After a PC Station download, restart the SIMATIC NET Configuration service (or reboot the SCADA PC) before commissioning.
9. Verification Checklist
Use the following checks in order to confirm the data path is up before going into runtime:
-
Ping from SCADA PC to CP 443-1.
ping 192.168.0.1must reply. - Station Configuration Editor. Open it on the SCADA PC; the WinCC Application and OPC Server components must show the configured slot numbers and a green status.
- NetPro consistency check. Network → Check Consistency for the entire station must report 0 errors.
- OPC Scout (S7 / OPC DA test). Launch SIMATIC NET OPC Scout and browse; the CP 443-1's connection partner must appear under the configured S7 connection.
- WinCC Channel Diagnostics. In the WinCC Explorer, open Channel Diagnostics → SIMATIC S7 Protocol Suite → TCP/IP → Connection and confirm status "Connected / OK".
-
Tag test. Create one tag in WinCC, link it to
DB1,INT0or to a STEP 7 variable, and confirm a value change appears at 1000 ms update rate. -
OPC UA (if used). Use the UaExpert client to browse
opc.tcp://192.168.0.1:4840and authenticate (Anonymous or Username/Password per security policy).
10. Troubleshooting Matrix
| Symptom | Likely cause | Corrective action |
|---|---|---|
| PC Station download fails with "Partner not found" | PC NIC IP / IE General IP mismatch | Reconcile Windows NIC IPv4 properties and IE General IP in NetPro; restart SIMATIC NET service |
| OPC Scout shows "Address not defined" on every tag | Wrong partner TSAP, slot mismatch with CPU | Open CP 443-1 Properties → S7 Connection → verify partner TSAP equals CPU rack/slot (e.g. 01.01) |
| WinCC channel status "Disconnected" and CPU still in RUN | Subnet mask difference between PC and CP 443-1 | Both must share a subnet mask (255.255.255.0 typical); also verify no router in path if both are in same broadcast domain |
| WinCC runtime stops updating; CP 443-1 reports SF (group fault) | Duplicate IP assigned by another device | Scan subnet with a tool such as ARP ping, remove duplicate |
| OPC UA browse returns "Bad_CommunicationError" | FW version does not support OPC UA server, or port 4840 blocked | Upgrade CP 443-1 to firmware V3.2.x (where applicable); open TCP 4840 in firewall |
| Operator can read tags but cannot write | OPC server security policy denies write or CPU is in read-only protection | Check CPU password/protection level in STEP 7; review OPC server item-level rights |
| CP 443-1 not visible in NetPro "Insert New Connection" | CP 443-1 not associated to Ethernet subnet | Edit CP 443-1 Properties → Ethernet → Select "Ethernet (1)" subnet |
| PC Station download fails after PLC firmware update | Configuration mismatch | Run NetPro Check Consistency, recompile, then re-download PC Station |
11. Migrating to TIA Portal — Equivalent Steps
For new deployments or retrofits the same engineering goal is reached via TIA Portal:
- Insert a PC system from the device catalog.
- Add the WinCC RT application (WinCC Professional / Comfort) and an IE general interface (CP 1623 or Softnet).
- Add the S7-400 station with CP 443-1 hardware.
- Use Devices & Networks → Connections to create an S7 connection between the PC station and the S7-400.
- Compile and download the PC station configuration.
The download semantics are the same: only the SCADA PC is touched. The S7-400 stays in RUN.
12. Field-Proven Commissioning Notes
- Order of operations. Bring up the S7-400 first (CPU in RUN, CP 443-1 reachable via ping), and only then connect the SCADA PC. Reverse the order and intermittent connection faults become very hard to attribute.
- Keepalive. S7 connections on port 102 are long-lived. The CP 443-1 sends keepalive approximately every 30 s; firewalls idle-timing port 102 must be disabled or set > 60 s.
- Cycle load. Sustained update rates < 250 ms across hundreds of tags may saturate the OPC server and the CP 443-1 connection resource. Schedule a mix of 500 ms, 1 s, and 2 s updates by exception class.
- TSAP collisions. If multiple S7 connections are opened against the same CPU through the same CP 443-1, each must use a unique TSAP pair. NetPro assigns automatically but verify when copying connections.
- Router sit-down. If the SCADA PC and S7-400 live in different VLANs, the configured router (default gateway) on both the IE General and the CP 443-1 must be inside the broadcast domain of each side.
- Security layers. When OPC UA is used, Basic256Sha256 with a certificate trust list is recommended for production. Anonymous access is acceptable for engineering but must be disabled in productive operation.
13. FAQ
Which IP address should I configure under IE General — the CP 443-1 default or a new one?
Use a new unique address in the same subnet as the CP 443-1, and match it exactly with the Windows NIC IPv4 properties of the SCADA PC. The CP 443-1 itself does not have a fixed default IP — it is unconfigured out of the box and the active address is the one assigned in STEP 7 Hardware Configuration.
Will downloading the PC Station to the target system stop my S7-400 CPU?
No. The PC Station download writes only to the SCADA PC's SIMATIC NET database and OPC server configuration. It does not communicate with the S7-400 and cannot change the CPU operating mode. A restart of the SIMATIC NET service on the PC is typically required for the new configuration to take effect.
Should I use the TCP/IP channel or the OPC channel in WinCC?
Use TCP/IP for the leanest path when no external OPC clients are needed. Use the OPC (or Named Connections) channel when third-party MES clients must read the same tags WinCC reads. Use OPC UA only when you need vendor-neutral, authenticated transport or are integrating S7-400 with S7-1200/1500 in one stack.
Which CP 443-1 firmware versions support OPC UA?
OPC UA server capability on the CP 443-1 was added with firmware V3.2.x and is prominent on the 6GK7 443-1UX00-0XE0 variant. Older EX/GX modules need a firmware update to a version released for that hardware. Check the device-specific firmware release notes before enabling OPC UA in productive operation.
What is the default port the CP 443-1 uses for S7 communication?
S7 communication (ISO-on-TCP / RFC 1006) uses TCP port 102 by default on both the CP 443-1 and the OPC server side. OPC UA uses TCP port 4840 when the embedded server is enabled. Firewalls along the path must allow both ports for the protocols you intend to use.
Why does my PC Station show the connection as established but no tag values update?
This is almost always a TSAP, slot, or slot-to-CPU mapping error. Verify the partner rack/slot under CP 443-1 Properties → S7 Connection matches the CPU's physical rack/slot (e.g. Rack 0, Slot 3) and the OPC server is pointing at the correct slot, not the CP 443-1's own slot. Also confirm any CPU password / protection level allows the type of access (read or write) being performed.