Troubleshooting AG_SEND/AG_RECV Delays in S7-300/S7-400 Online Monitoring
Engineers using STEP 7 V5.4 to commission an ISO-on-TCP link between an S7-300 and an S7-400 frequently report a symptom that looks like a network fault but is actually a deterministic side effect of online monitoring: a one-second incrementing watchdog on the partner PLC appears to advance only every several seconds in the variable table, and continues to advance for a long time after the partner stops sending. When the engineer terminates the online session, the watchdog snaps to the expected value. This article isolates the root cause (CP receive buffer queueing under online load), documents the affected blocks and firmware ranges, and gives a sequenced set of corrective actions plus a verification procedure.
AG_SEND / AG_RECV function blocks from the SIMATIC NET library. The patterns and remedies also apply to PROFINET interface variants of the S7-400 (e.g. CPU 41x-PN) and to S7-300 PN CPUs that expose the same library interface.1. Problem Description
The reference installation is configured as follows:
| Item | Value |
|---|---|
| Sender CPU | S7-300, e.g. CPU 315-2 PN/DP or CPU 319-3 PN/DP |
| Receiver CPU | S7-400, e.g. CPU 414-3 PN/DP or CPU 416-3 PN/DP |
| Send block (sender) | FC AG_SEND (FB 5 / FC 5 from SIMATIC NET CP library) |
| Receive block (receiver) | FC AG_RECV (FB 6 / FC 6 from SIMATIC NET CP library) |
| Transport | ISO-on-TCP (RFC 1006), connection type 04 / 0B |
| Watchdog payload | One INT inside a shared DB, incremented once per second on the S7-300 |
| Engineering tool | STEP 7 V5.4 + SPx, online via Variable Table (VAT) and Monitor/Modify |
Observed symptoms
- When the engineer opens a Variable Table in Monitor mode, the watchdog value visible on the S7-400 increments in steps of 1, but the apparent step interval is many seconds — often 10 s to several minutes, depending on the number of monitored variables and the OB1 cycle time.
- The value is never wrong by a non-integer amount and never jumps. It is a deterministic, monotonic lag.
- If the S7-300 stops sending (
AG_SENDno longer called, orENcleared), the S7-400 value continues to increase for a long time and only gradually catches up. - Closing the online session causes the watchdog to immediately snap to the value the partner would have shown, confirming that no data was lost — only queued.
The pattern is not a defective cable, a faulty CP, or a wrong connection configuration. The hardware path is correct; the issue is the rate at which the receiver CP can deliver buffered frames to the CPU while the CPU is simultaneously servicing the online monitor.
2. Why Online Monitoring Slows the Visible Update
STEP 7 V5.4 online monitoring is implemented as a parallel read service against the CPU. While a VAT is in monitor mode, the programming device (PG) issues OPTI_PE/OPTI_PI / OPTI_RD-style read requests at the configured poll rate (default ~1 s for VAT, 500 ms for the Monitor/Modify dialog). Each request:
- Interrupts the current OB1 scan at the next communication load window.
- Consumes a slice of the CPU's communication budget.
- Is dispatched into the Ethernet CP through the internal backplane bus.
The S7 CPU firmware partitions its scan into the process image update, the user program, and the communication share. The communication share is bounded; if the share is exhausted, the rest of the scan finishes before the OS services the next communication request. This is a deterministic design choice; it guarantees that cyclic OB1 time never starves the process, at the cost of bounding throughput on the communications bus.
When AG_RECV is called every OB1 cycle and the PG is also polling the VAT, two consumers fight for the same communication share. The frames that the S7-400 CP has already received from the S7-300 are correctly stored in the CP's internal receive buffer, but the CPU does not free the buffer until the next AG_RECV call is dispatched with available communication share. The result is a growing queue in the CP and a visible lag in the variable table.
3. Affected Products and Firmware
| Component | Order Number (MLFB) | Firmware range of interest | Notes |
|---|---|---|---|
| S7-300 CPU 315-2 PN/DP | 6ES7315-2EH14-0AB0 | V3.3 and later | Integrated PN interface, ISO-on-TCP supported |
| S7-300 CPU 319-3 PN/DP | 6ES7319-3EL00-0AB0 | V3.2 and later | Higher performance variant |
| S7-400 CPU 414-3 PN/DP | 6ES7414-3EM07-0AB0 | V7.0 and later | Default comm. load 20% |
| S7-400 CPU 416-3 PN/DP | 6ES7416-3ES07-0AB0 | V7.0 and later | Default comm. load 20% |
| CP 343-1 (S7-300) | 6GK7343-1EX30-0XE0 | V3.0 and later | ISO-on-TCP, TCP, UDP, PROFINET |
| CP 443-1 (S7-400) | 6GK7443-1EX30-0XE0 | V3.0 and later | ISO-on-TCP, TCP, UDP, PROFINET |
| CP 343-1 Advanced | 6GK7343-1GX31-0XE0 | V3.0 and later | Adds Security, FTP |
| CP 443-1 Advanced | 6GK7443-1GX31-0XE0 | V3.0 and later | Adds Security, FTP |
| STEP 7 V5.4 + SP5 or higher | 6ES7810-4CC08-0YA8 | n/a | Last classic STEP 7 release |
Any S7-300/S7-400 combination that uses the SIMATIC NET CP library blocks AG_SEND (FC 5) and AG_RECV (FC 6) over ISO-on-TCP can exhibit the symptom. The S7-200 series uses different blocks (ETHx_CTRL, ETHx_SEND, ETHx_RECV) and is not in scope.
4. Root Cause Analysis
The root cause is the combination of three independent design parameters. If any one of them is changed, the symptom magnitude changes accordingly.
4.1 CPU Communication Load Setting
The communication load is the share of the CPU scan reserved for communication services. The valid range is hardware-dependent:
| Platform | Min. comm. load | Max. comm. load | Default |
|---|---|---|---|
| S7-300 (all CPUs) | 10% | 50% | 20% |
| S7-400 classic (CPU 412–417) | 10% | 50% | 20% |
| S7-400 PN (CPU 41x-PN) | 5% | 50% | 20% |
The communication load is configured in HW Config → Properties of the CPU → Cycle/Clock Memory tab → Communication Load. The S7 firmware checks every millisecond whether the communication budget is exhausted; if it is, communication services are deferred to the next millisecond. With the default 20% load and a 100 ms OB1, only 20 ms of each cycle is available for all communication, including:
- AG_RECV completion of one buffered frame
- PG polling of the VAT
- Any active HMI connection (e.g. WinCC, TIA Portal HMI tag service)
- Time-of-day synchronisation (where configured)
4.2 Call Frequency of AG_RECV
The user is invoking AG_RECV inside OB1 (or in a low-priority cyclic OB), which is the conventional pattern. However, if OB1 is 140 ms and the S7-300 is sending at 1 Hz, the CP still receives every frame in real time, but the receiver CPU only services one frame per AG_RECV call. If the S7-300 sends faster than the receiver can drain, the CP buffer grows.
Buffer sizing for the CP 343-1 / CP 443-1 family is documented in the SIMATIC NET manuals: each ISO-on-TCP connection has a configurable receive window, defaulting to 8192 bytes per connection. A 1 Hz INT payload (2 bytes) generates roughly 1.6 kB of buffered data per hour; this is trivial. The real queueing is the unserviced frames — the CP holds the frame in its internal RAM until AG_RECV is dispatched with a free communication share.
4.3 Parallel Demand from Online Monitor
Every visible variable in the VAT consumes one read service per VAT poll cycle. STEP 7 V5.4 issues these reads as individual request-response pairs to the CPU, not as a single bulk read. With a 10-variable VAT and a 1 s poll, the PG places 10 read requests per second on the same communication bus. This is the dominant extra load during online monitoring, and it is absent when the VAT is closed.
4.4 Quantitative Model
Let T_OB1 be the OB1 cycle time of the receiver CPU, ρ the configured communication load, N_AG the number of AG_RECV call completions per second, and N_PG the number of PG read requests per second. The theoretical communication time share per second is:
T_comm = ρ × 1000 ms (per second of wall time)
Each AG_RECV completion costs approximately 1.0–1.5 ms of CPU time on an S7-400, and each PG read of a single variable costs approximately 0.5–0.8 ms. The system enters a backlog condition when:
N_AG × t_AG + N_PG × t_PG > ρ × 1000 / T_OB1 (per OB1 cycle)
For an S7-400 with T_OB1 = 100 ms, ρ = 0.20, t_AG = 1.2 ms, t_PG = 0.6 ms per variable and 10 visible variables, the budget per cycle is 20 ms. The demand is 1 × 1.2 + 10 × 0.6 = 7.2 ms per cycle — within budget, but the headroom evaporates once HMI tags or additional PG requests are added. The symptom is therefore most pronounced on installations with parallel HMI servers or large VATs.
5. Diagnostic Procedure
Before changing any code or configuration, prove that the symptom is buffering and not packet loss. Run the following checks:
- Close all VATs and HMI sessions and leave the system running for 5 minutes. The watchdog should advance at exactly 1 Hz on the receiver.
- Open a single VAT with the watchdog value and one or two adjacent variables. The watchdog should advance at 1 Hz.
- Add a second VAT on the same connection, monitoring 20 unrelated variables. The watchdog should begin to lag.
-
Capture the OB1 scan time from the CPU diagnostic buffer (Path: PLC → Module Information → Diagnostic Buffer, look for Cycle time exceeded or read
OB1_LAST_CYCLEvia the system clock area). A scan time > the configuredT_OB1confirms the CPU is overrunning. - Read the CP statistics on the receiver side via the SIMATIC NET diagnostics (in STEP 7 V5.4: PLC → Ethernet → Diagnostics). Look at Number of received frames and Number of discarded frames. Discarded = 0 confirms no loss; the lag is purely a queue effect.
- Trace with a managed switch (e.g. SCALANCE XC-208 port mirror) using Wireshark with the s7comm dissector. You will see frames arriving on the wire at 1 Hz, regardless of the VAT lag — definitive proof of the queue.
6. Solution Matrix
Four independent remedies are available. Apply them in the order listed, and re-test after each change.
6.1 Raise the Communication Load
Open HW Config → CPU properties → Cycle/Clock Memory tab → Communication Load. Increase the value from 20% to 50% (the maximum on S7-300 and classic S7-400). Verify that OB1 scan time remains well below the configured maximum; the trade-off is that the OB1 cycle time floor increases because the CPU always reserves the configured share, even when no communication is in progress.
The relationship between communication load ρ and the minimum achievable OB1 cycle time is:
T_OB1_min = T_OB1_typical / (1 − ρ)
For a typical OB1 of 50 ms and a change from 20% to 50%, the minimum scan time rises from approximately 62.5 ms to 100 ms. This is acceptable for non-deterministic process applications but must be evaluated against the worst-case response time of the controlled process.
6.2 Switch to BSEND/BRECV or PUT/GET
BSEND/BRECV (S7 communication) and PUT/GET (S7 communication, server function on the partner) use a different mechanism than AG_SEND/AG_RECV. They use the S7 communication load scheduling described earlier (10–50% on S7-300/S7-400 classic, 5–50% on S7-400-PN), which is more efficient for cyclic, small-payload data exchange and is the Siemens-recommended replacement for AG_SEND/AG_RECV on S7-300/S7-400 installations.
Migration steps:
- In NetPro on the S7-300 side, insert an S7 connection rather than a TCP/ISO-on-TCP connection. Set the partner to the S7-400.
- On the S7-400 side, accept the partner connection; no application-side configuration is required because PUT/GET runs as a server.
- Replace
AG_SENDcalls withBSEND(FB 12) calls andAG_RECVwithBRECV(FB 13) calls. Reference the SIMATIC NET programming manual for the IDB structure (the LEN, R_ID, and SD_1..SD_4 inputs are now mandatory). - If a unidirectional, server-side initiated write is sufficient, use
PUT(FB 15) andGET(FB 14) on the client side. PUT/GET does not require any code on the server CPU.
Sample BSEND IDB configuration (representative excerpt):
DATA_BLOCK DB_Comm
STRUCT
REQ : BOOL; // rising edge triggers a send
R : BOOL; // abort current job
ID : WORD; // W#16#1 – connection ID from NetPro
R_ID : DWORD; // any unique value, must match BRECV on partner
DONE : BOOL; // job completed without error
ERROR : BOOL; // job completed with error
STATUS : WORD; // status code from BSEND
SD_1 : WORD; // first 2 bytes of user data
SD_2 : WORD; // bytes 3..4 of user data
SD_3 : WORD; // bytes 5..6 of user data
SD_4 : WORD; // bytes 7..8 of user data
LEN : WORD; // number of valid bytes in SD_1..SD_4
END_STRUCT
END_DATA_BLOCK
6.3 Use a Time-Triggered Send Pattern (no replacement of blocks)
If AG_SEND/AG_RECV must be retained, restructure the user program as follows:
- Place the call sequence in OB1 as:
AG_RECVfirst, then process logic, thenAG_SENDlast. This ensures that one receive is serviced per cycle before any new send occupies the communication share. - Trigger the
AG_SENDfrom a 1 s timer (e.g. clock memory bit M10.7 from the CPU clock memory byte, or a TP/SE timer in OB35) and not from OB1 edges. This decouples the transmission rate from the OB1 cycle time. - Hold the previous send's
DONEflag as a guard, and only re-triggerAG_SENDafterDONEhas been received. IfDONEdoes not appear within 10 s, the previous send is considered failed and the next is initiated with a fresh IDB instance.
This pattern is the one used in the Siemens SIMATIC NET application examples for S7-300 ISO-on-TCP communication. The reference example is in the S7-1200 PTP programming manual collection which describes the same global-DB-backed communication buffer pattern: Programming the STEP 7 program – SIMATIC S7-1200 Manual Collection.
6.4 Separate the Online Monitor from the Production Link
Open the VAT through a different physical interface than the AG_SEND/AG_RECV traffic. Two options are supported on most S7-300 and S7-400 CPUs:
- Use the MPI/DP interface for online monitoring (set the PG/PC interface to MPI or PROFIBUS). MPI/DP has its own communication budget and does not contend with the Ethernet CP.
- Use the second Ethernet interface of a CPU 41x-PN or a CP 443-1 Adv (a separate IP subnet) for the engineering channel, leaving the primary Ethernet interface dedicated to AG_SEND/AG_RECV.
This is the cleanest solution for installations where the communication budget cannot be increased and the block code cannot be migrated.
7. Programming Pattern: Corrected AG_SEND / AG_RECV Cycle
The following structural pattern is recommended for installations that must keep AG_SEND/AG_RECV. It implements the four improvements described in §6 in a single FB.
FUNCTION_BLOCK FB_Comm_Cycle
VAR
tSend : TON; // 1 s send timer
tWatch : TON; // 10 s send timeout
bSendBusy : BOOL;
bSendDone : BOOL;
bSendError : BOOL;
wSendStatus : WORD;
END_VAR
BEGIN
// 1) Receive first – drain the CP buffer as early as possible
AG_RECV(
ID := 1,
LADDR := W#16#0100, // I/O address of the CP from HW Config
RECV_DB := 100, // DB that holds the watchdog and other data
NDR := bNDR_recv,
ERROR := bErr_recv,
STATUS := wStat_recv,
LEN := wLen_recv);
// 2) Application logic here – operates on the data in DB100
// 3) Trigger send once per second, but only when not busy
tSend(IN := NOT bSendBusy, PT := T#1S);
tWatch(IN := bSendBusy, PT := T#10S);
IF tWatch.Q THEN
// previous send has been pending for >10 s – abort and re-arm
AG_SEND(
ID := 1,
LADDR := W#16#0100,
SEND_DB := 100,
REQ := FALSE,
DONE := bSendDone,
ERROR := bSendError,
STATUS := wSendStatus);
bSendBusy := FALSE;
END_IF;
IF tSend.Q AND NOT bSendBusy THEN
bSendBusy := TRUE;
AG_SEND(
ID := 1,
LADDR := W#16#0100,
SEND_DB := 100,
REQ := TRUE,
DONE := bSendDone,
ERROR := bSendError,
STATUS := wSendStatus);
END_IF;
// Latch the DONE / ERROR edge and clear REQ in the next cycle
IF bSendDone OR bSendError THEN
AG_SEND(
ID := 1,
LADDR := W#16#0100,
SEND_DB := 100,
REQ := FALSE,
DONE := bSendDone,
ERROR := bSendError,
STATUS := wSendStatus);
bSendBusy := FALSE;
tSend(IN := FALSE, PT := T#1S);
END_IF;
END_FUNCTION_BLOCK
The pattern is critical at two points:
-
REQ := FALSEmust be issued afterDONE/ERRORto release the block; ifREQstaysTRUE, the block will fire a second job as soon as the first completes, doubling the load on the communication share. - The 10 s timeout (variable
tWatch) protects against a deadlock where the partner CP has stopped acknowledging (e.g. cable fault, partner CPU in STOP). Without it, the FB will stay inbSendBusy := TRUEforever and the watchdog will appear to freeze on the receiver side.
8. AG_SEND / AG_RECV Status Codes
The status words of AG_SEND and AG_RECV (output STATUS) use the following error classes. Inspect these in the VAT as the first diagnostic step.
| STATUS (hex) | Meaning for AG_SEND | Meaning for AG_RECV | Action |
|---|---|---|---|
| 0000 | Job completed, no error | Job completed, no error | None |
| 7000 | Block idle, no job active | Block idle, no job active | None |
| 7001 | Job active, first call | Job active, first call | None, wait for DONE/NDR |
| 7002 | Job active, subsequent call | Job active, subsequent call | None, wait for DONE/NDR |
| 8085 | LADDR invalid | LADDR invalid | Correct the LADDR parameter to match the CP slot/I/O address |
| 80A0 | Negative acknowledge from CP (CP not ready, no connection) | Negative acknowledge from CP (CP not ready, no connection) | Check NetPro connection, CP online, partner reachable |
| 80A1 | Establishment of connection in progress | Establishment of connection in progress | Wait – first call after PLC start |
| 80A2 | DP/PN send resource busy | DP/PN receive resource busy | Reduce send rate; another job is in progress |
| 80A3 | Connection or resource still established | Connection or resource still established | Wait for release |
| 80A7 | CP in STOP or data inconsistency | CP in STOP or data inconsistency | Bring CP to RUN, re-check DB length |
| 80B0 | DB does not exist on the CPU | DB does not exist on the CPU | Create the DB on the S7-300, length ≥ LEN |
| 80B1 | DB too short | DB too short | Extend DB length on the S7-300 |
| 80C0 | Protocol error (internal) | Protocol error (internal) | Reinitialise the connection (power-cycle CP or NetPro download) |
| 80C1 | Partner CPU not in RUN | Partner CPU not in RUN | Place partner CPU in RUN; otherwise the watchdog will continue to advance on the S7-300 only and appear to be lost |
| 80C2 | Send job aborted by R = TRUE | Receive job aborted by R = TRUE | Check user logic for accidental R = TRUE |
| 80C3 | Internal protocol error | Internal protocol error | Upgrade CP firmware to latest V3.x |
| 80C4 | Temporary lack of resources in CP | Temporary lack of resources in CP | Reduce number of concurrent AG_SEND jobs |
| 80D0 | CP does not recognise the connection | CP does not recognise the connection | Re-compile NetPro; download connection configuration to both stations |
For the symptom described in this article, the STATUS word on both sides will read 0000 (DONE) at each successful transfer — the job itself is succeeding; it is the dispatch of the next job that is being delayed. STATUS is therefore a poor diagnostic on its own; the Wireshark trace described in §5 is the more reliable evidence.
9. Verification Procedure
After applying any of the four remedies, perform the following to confirm the issue is resolved:
- Open the VAT containing the watchdog and the diagnostic
STATUSword from AG_RECV. ConfirmSTATUS = 16#0000continuously. - Add 20 additional unrelated variables to the VAT. The watchdog must continue to increment at 1 Hz within ±10%.
- Start a WinCC flexible / WinCC RT instance that polls 200 tags over the same connection. The watchdog must continue to increment at 1 Hz within ±10%.
- Disconnect the partner S7-300 from the network. Within 10 s (the
tWatchtimeout from §7), the receiver must report a fault; no further watchdog updates should occur. - Reconnect the partner. The receiver must resume watchdog updates at 1 Hz within 2 s.
- Read the CPU diagnostic buffer on the S7-400: Diagnostic Buffer → Communication. No Communication error events with ID 0x0E31 / 0x0E32 / 0x0E33 should be logged. These IDs map to connection abort events and would indicate packet loss rather than queueing.
10. Related Configuration Caveats
-
Connection type in NetPro: For ISO-on-TCP, the S7-300 connection must be of type TCP native / ISO-on-TCP with active role on the S7-300 side and passive on the S7-400 side. Reversing the role causes
80A0at startup. -
CP slot/I/O address: The
LADDRparameter in AG_SEND/AG_RECV is the diagnostic address of the CP, not the slot number. In HW Config, right-click the CP → Properties → Addresses and read the Input addresses start. Use this value asLADDRin hex (e.g. 256 dec → W#16#0100). -
DB length on the partner: The send and receive DBs on both sides must be at least the maximum
LENof any job, or80B1is reported on the very first send. - PG/PC interface selection: In STEP 7 V5.4, Options → Set PG/PC Interface must select the network card bound to the same subnet as the CP. Selecting the wrong adapter causes the online monitor to time out at the IP level and may appear to be a buffering issue because STATUS will not change.
- Time synchronisation: If the S7-300 is the time master and broadcasts time-of-day to the S7-400, the broadcast itself consumes communication share. Set the time synchronisation interval to 10 s or longer unless 1 s is required by the process.
11. Quick-Reference Fault Matrix
| Observed symptom | Likely cause | First action |
|---|---|---|
| Watchdog lags seconds-to-minutes during VAT; snaps when VAT closed | CPU communication share saturated by PG polling | Apply §6.1, §6.3, §6.4 |
| Watchdog does not advance at all; STATUS = 16#80A0 | Connection not established (NetPro not downloaded, CP in STOP) | Check CP online status, download connection configuration |
| Watchdog freezes after a random uptime; STATUS = 16#80C4 | CP resources exhausted by too many concurrent AG_SEND jobs | Consolidate sends to one job per cycle, or upgrade CP firmware |
| Watchdog advances on S7-300 but not on S7-400; Wireshark shows traffic | AG_RECV not called, or called with wrong ID/LADDR | Verify ID and LADDR in the receiver FB |
| Watchdog advances on S7-400 but is incorrect (off by 1 frame or constant) | DB alignment mismatch (INT vs WORD, byte order) | Reconcile data types; ISO-on-TCP is byte-stream, not typed |
| Watchdog ok during commissioning, lags after a few weeks | CP firmware memory leak; CP needs warm restart | Upgrade CP firmware; CP 343-1 V2.x → V3.0+ resolves known leaks |
| Both sides report STATUS = 16#80C1 | Partner CPU in STOP | Place partner in RUN; check for STOP caused by I/O fault |
12. Frequently Asked Questions
Why does the watchdog lag during online monitoring but catch up when I close the VAT?
The CP receive buffer holds all incoming frames correctly. While the VAT is open, the PG consumes communication share faster than AG_RECV can dispatch; when the VAT is closed, AG_RECV drains the queue at line rate and the watchdog snaps to the partner value. No data is lost.
What is the valid range of the communication load parameter on an S7-300?
10% to 50% in 1% increments, default 20%. On S7-400-PN CPUs the lower bound is 5%. Increasing the value raises the floor of the OB1 scan time by a factor of 1/(1−ρ), so a 20% → 50% change on a 50 ms typical scan time increases the minimum OB1 to ~100 ms.
Can I replace AG_SEND/AG_RECV with BSEND/BRECV or PUT/GET without rewriting the S7-300 program?
No — the call interface is different. BSEND/BRECV require an IDB with R_ID, LEN, and SD_1..SD_4; PUT/GET are call-direction-specific. NetPro must be reconfigured to an S7 connection rather than an ISO-on-TCP connection, and the connection must be downloaded to both stations. Plan for one engineering day of work for a typical S7-300/S7-400 pair.
How do I prove that the issue is buffering and not packet loss?
Mirror the receiver port on a SCALANCE switch and run Wireshark with the s7comm dissector. Frames arrive at the partner's configured rate (1 Hz in this scenario) regardless of the lag in the VAT. Also check the CP diagnostic counters — Discards = 0 — via PLC → Ethernet → Diagnostics in STEP 7 V5.4.
Does the problem occur with S7-300/S7-400 PN CPUs using the integrated PROFINET interface?
Yes. The integrated PROFINET interface on CPU 31x-PN and CPU 41x-PN supports AG_SEND/AG_RECV over ISO-on-TCP via the same SIMATIC NET library. The communication share is shared with the PROFINET IO controller, so a heavily loaded PROFINET device tree will exacerbate the lag during online monitoring. Consider reserving a separate subnet for the engineering channel.
Is the AG_SEND status 16#80A2 (send resource busy) ever normal?
Yes, briefly during a multi-call job. A persistent 80A2 means the previous job was not released by setting REQ := FALSE after DONE/ERROR. See the corrected FB in §7 for the correct edge handling.