Connecting KTP HMI to LOGO! 8 (0BA8) via Ethernet — Setup Guide

David Krause10 min read
HMI ProgrammingSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Connecting KTP HMI to LOGO! 8 (0BA8) via Ethernet — Setup Guide

Siemens LOGO! 8 (order suffix 0BA8) Base Modules ship with a built-in 10/100 Mbit Ethernet interface, which makes direct HMI coupling practical without extra communication modules. Any SIMATIC KTP Basic Panel with an Ethernet port — the KTP400 Basic, KTP600 Basic, KTP700 Basic, KTP1000 Basic, and KTP1200 Basic — can be wired to a LOGO! 8 over a standard patch cable. This guide covers the supported panels, the Siemens cable part numbers, the IP addressing scheme, the TIA Portal / LOGO! Soft Comfort configuration, and field verification of the connection.

Read first: LOGO! 8 Base Modules without the Ethernet suffix (older 0BA7 stock) do not support the workflow below. Confirm the device label reads 6ED1052-xxx08-0BA0 (Base Module 0BA8) or higher before commissioning.

1. System Architecture

A typical LOGO! 8 + KTP point-to-point architecture looks like this:

LOGO! 8 (0BA8) Base Module + Ethernet IP: 192.168.0.10 KTP Basic Panel KTP400/600/1000 IP: 192.168.0.20 Cat 5e patch 6XV1850-2GH20 Engineering PC LOGO! Soft Comfort V8.4 TIA Portal V18

For the canonical light-control example from Siemens that exercises exactly this topology, see the Light control with LOGO! and HMI Panel application document (PDF, application ID 109747758).

2. Supported KTP Panels

The following SIMATIC HMI Basic Panels are confirmed for direct Ethernet communication with LOGO! 0BA8. The "Basic" line is the cost-effective range; "Comfort" panels are also supported but only required when features beyond LOGO! tag mapping are needed.

Panel MLFB (Siemens Part No.) Display Ethernet Touch Typical Use
KTP400 Basic 6AV2123-2DB03-0AX0 4" mono/TFT 1× RJ45 10/100 Resistive Compact machines, 8–16 tags
KTP600 Basic 6AV2123-2GB03-0AX0 6" TFT color 1× RJ45 10/100 Resistive Mid-size systems, 32+ tags
KTP700 Basic 6AV2123-2GA03-0AX0 7" TFT color 1× RJ45 10/100 Resistive Color HMI, 64+ tags
KTP1000 Basic 6AV2123-2KE03-0AX0 10" TFT color 1× RJ45 10/100 Resistive Larger visualization, 128+ tags
KTP1200 Basic 6AV2123-2MA03-0AX0 12" TFT color 1× RJ45 10/100 Resistive High-tag-count dashboards

All panels support the SIMATIC S7/LOGO communication driver, which is the only driver required for LOGO! 8 tag access. No additional option or add-on is required on the HMI side.

3. Cables, Connectors, and Siemens Part Numbers

LOGO! 8 and the KTP Basic Panels both use industrial RJ45. A standard Cat 5e SF/UTP patch cable is sufficient for point-to-point links up to 100 m. The Siemens catalog reference for a 2 m grey IE patch cable is:

  • 6XV1850-2GH20 — IE TP Cord RJ45/RJ45, 2 m, Cat 5e, pre-assembled, 1:1 wired (TIA-568B). Suitable for direct LOGO! ↔ KTP and LOGO! ↔ PC links.
  • 6XV1850-2GN10 — 10 m version of the same cord.
  • 6XV1850-2GN50 — 50 m version.

For PC engineering access (LOGO! Soft Comfort program transfer), two cable options exist:

Interface Siemens Part No. Notes
Ethernet (preferred) Standard RJ45 patch (6XV1850-2GH20) Uses integrated Ethernet port on 0BA8
USB PC ↔ LOGO! 6ED1057-1AA01-0BA0 LOGO! PC cable, USB-A to LOGO! programming port. Use when Ethernet is unavailable on the PC or for legacy projects.
Watch the topology: the USB PC cable (6ED1057-1AA01-0BA0) plugs into the LOGO! side connector, not the HMI. The HMI connects to the LOGO! Ethernet port with an RJ45 patch — not via USB.

4. IP Addressing Scheme

LOGO! 0BA8 Base Modules ship with default IP 192.168.0.10 and subnet mask 255.255.255.0. The HMI and PC must share the same subnet. A robust small-network default is:

Device IP Address Subnet Mask Default Gateway
LOGO! 8 Base Module 192.168.0.10 255.255.255.0 0.0.0.0
KTP Basic Panel 192.168.0.20 255.255.255.0 0.0.0.0
Engineering PC 192.168.0.100 255.255.255.0 0.0.0.0

To change the LOGO! IP from the device itself, navigate LOGO! menu → Network → IP Address. To change the KTP IP, use Control Panel → Network and Dial-up Connections → Onboard Ethernet → Properties → IP Address on the panel itself, or push it from the TIA Portal project at transfer time.

5. Configuring the LOGO! 8 Network Parameters

  1. Power up the LOGO! 0BA8 Base Module and wait for the display to settle.
  2. From the LOGO! onboard display, press ESC to reach the main menu, then navigate to Network.
  3. Set the IP Address (default 192.168.0.10), Subnet Mask (255.255.255.0), and confirm that the Server role is enabled (LOGO! 8 is always a server on S7/LOGO).
  4. Verify the Ethernet link by plugging the RJ45 patch and observing the LINK LED on the RJ45 socket (solid green = link up).

For an Ethernet ↔ LOGO! programming session from LOGO! Soft Comfort, choose Tools → Select Interface → Ethernet in the Soft Comfort toolbar, then enter the LOGO! IP. The discovery tool (Tools → Discover) will list every LOGO! on the broadcast domain.

6. Configuring the KTP in TIA Portal

Use TIA Portal V17 or later (V18 SP1 is the current mainstream release at the time of writing). The KTP project must use the SIMATIC S7/LOGO protocol driver.

6.1 Add the Panel

  1. Open your project, then in the project tree select Add new device → SIMATIC HMI → Basic Panel → [4/6/7/10/12 inch] → KTPxxx Basic.
  2. Open the panel's Device Configuration, double-click the PROFINET interface, and enter:
    • IP address: 192.168.0.20
    • Subnet mask: 255.255.255.0

6.2 Create the LOGO! Connection

  1. In the project tree, expand the panel → Connections → double-click Connections to open the editor.
  2. Click Add and choose the SIMATIC S7/LOGO driver.
  3. Set the partner (LOGO!) endpoint:
    • PLC type: LOGO!
    • Address: 192.168.0.10
    • Rack/Slot: 0 / 0 (LOGO! 8 uses Rack 0, Slot 0; do not configure rack 0/slot 1, which is the older S7-200 convention)

6.3 Map Tags

LOGO! exposes the following addressable memory areas to the S7/LOGO driver:

LOGO! Area HMI Address Syntax Access Typical Use
Digital Inputs (I) DB1.DBX0.0 … DB1.DBX7.7 Read-only Display I1–I24
Digital Outputs (Q) DB1.DBX8.0 … DB1.DBX9.7 Read Display Q1–Q16
Merker (M) / Flags DB1.DBX10.0 … DB1.DBX11.7 Read/Write Internal flag status, button toggles
Analog Inputs (AI) DB1.DBD12 … DB1.DBD60 (words) Read AI1–AI8
Analog Outputs (AQ) DB1.DBD80 … DB1.DBD92 Read AQ1–AQ2
Variable Memory (VW) DB1.DBW100+ Read/Write Network inputs/outputs, user V-memory
Note on ranges: The exact DB1 offset is firmware-dependent. The LOGO! 0BA8 communication manual LOGO! 8 System Manual (109741041) lists the current mapping table for firmware FS08 and later.

6.4 Compile and Transfer

  1. Compile the HMI project (Project → Compile → Software (rebuild all)).
  2. Connect the engineering PC to the same Ethernet subnet (192.168.0.x) as the panel.
  3. Right-click the panel → Transfer to device → select the panel's IP. The runtime image and project are pushed to the HMI.
  4. After the transfer, the panel will auto-start runtime and attempt to connect to the LOGO! IP defined in the connection.

7. Sample Screens (Minimum Viable Project)

For a 3-screen start-up project:

  1. Screen 1 — Overview: eight I/O indicator fields linked to DB1.DBX0.0 through DB1.DBX0.7; eight output fields on DB1.DBX8.0–DB1.DBX8.7. Two area-button objects to navigate forward.
  2. Screen 2 — Setpoints: two I/O field objects (data type INT) bound to DB1.DBW100 and DB1.DBW102 for entering thresholds into LOGO! variable memory.
  3. Screen 3 — Diagnostics: a status display reporting the S7/LOGO connection state (use the system tag Connection state in the HMI tag properties).

Set the start screen in HMI tags → Screen management properties → Start screen = Screen 1.

8. Verification

  1. Link layer: the green LINK LED on both the LOGO! RJ45 and the KTP RJ45 must be solid. If only one is lit, the cable or one of the ports is bad.
  2. LOGO! ping: from the engineering PC, open a command prompt and run ping 192.168.0.10. Four replies with sub-millisecond time confirm the Ethernet path.
  3. HMI runtime connection: on the KTP, open Control Panel → Service / Commissioning → Status / Control. The S7/LOGO connection should report Connected within ~5 s of the panel booting.
  4. Tag round-trip: in LOGO! Soft Comfort, force a merker (M1) high. Within one HMI scan cycle (default 1 s), the M1 indicator on the panel must turn on. Force low; it must turn off.
  5. Write path: from the panel I/O field on Screen 2, write the integer 1234 into the configured DB1.DBW100 word. In Soft Comfort, place a watch on VW100; the value 1234 must appear.
  6. Disconnect behavior: unplug the patch cable. After the configured timeout (default ~5 s), the panel should display a system event "Connection to PLC interrupted". Plug it back in; the connection must auto-recover without restarting the HMI runtime.

9. Troubleshooting Matrix

Symptom Likely Cause Fix
LINK LED dark on LOGO! Cable damaged, wrong pinout (crossover vs. 1:1), or no PoE/aux power on the panel side Replace with Siemens 6XV1850-2GH20 (1:1)
Ping fails, PC is on the right subnet Windows firewall blocking ICMP or different subnet mask Disable firewall on private profile; verify ipconfig /all
Panel reports "Connection to PLC interrupted" Wrong IP, wrong rack/slot, S7/LOGO driver not assigned Verify partner IP in the HMI connection; LOGO! 8 = Rack 0 / Slot 0
Tags show "####" on the panel Address offset wrong for the firmware version Re-check DB1 offsets in the LOGO! 8 System Manual
Inputs update slowly (> 2 s) Acquisition cycle set to default 1 s; many tags Lower cycle time on the HMI tag, but stay ≥ 100 ms to avoid load
Touch button does not write to LOGO! Tag set to read-only or wrong access mode Open HMI tag properties → Acquisition mode = "Cyclic on use", set access to Read/Write
LOGO! Soft Comfort "No device found" Network discovery blocked, or PC on a different VLAN Add LOGO! IP manually in Tools → Select Interface → Ethernet
Runtime image is loaded but values stay at 0 The HMI compile was built with stale tag pointers Compile "rebuild all", re-transfer

10. Starter Kits and Alternatives

Siemens bundles several starter kits that include a LOGO! 8 Base Module, a KTP Basic panel, and LOGO! Soft Comfort on a single DVD or download card. Check the Siemens LOGO! product page for the current regional part numbers (e.g., 6ED1057-3BA01-0AA8 in EU). These kits remove the cable-compatibility guesswork and pre-validate the panel firmware against the LOGO! 0BA8 firmware shipped in the kit.

If you have a non-Basic Comfort Panel (TP700 Comfort, TP1200 Comfort), the same S7/LOGO driver and addresses apply, but you also gain access to PROFIenergy, Sm@rtServer, and Web features on the HMI side. Stick with Basic Panels for cost-sensitive LOGO! deployments where only tag visualization is needed.

11. Best Practices

  • Document the IP and rack/slot in the panel name in the TIA Portal project tree (e.g., "KTP600_192.168.0.20_R0S0") for faster field replacement.
  • Reserve a static range (192.168.0.10–.30) for LOGO! networks and keep DHCP out of the same scope.
  • For multi-LOGO! projects (LOGO! ↔ LOGO! + KTP), use a small managed switch and reserve IP-per-MAC entries; unmanaged switches are fine for ≤ 4 devices.
  • Set the LOGO! display password if the cabinet is field-accessible — the HMI will still control outputs even if the LOGO! onboard UI is locked.
  • Keep the LOGO! 0BA8 firmware on FS08 or later; the DB1 area layout was extended in earlier FS releases and tag offsets differ.
  • Always transfer a backup of the compiled HMI runtime + the LOGO! Soft Comfort .lsc program to the project archive.

12. FAQ

Can I use any KTP400, KTP600, or KTP1000 with LOGO! 8?

Yes — any SIMATIC KTP Basic Panel with an Ethernet port (KTP400 Basic, KTP600 Basic, KTP700 Basic, KTP1000 Basic, KTP1200 Basic) supports the SIMATIC S7/LOGO driver and connects to LOGO! 0BA8 over a standard Cat 5e patch cable such as Siemens 6XV1850-2GH20.

Which cable do I need to program the LOGO! 8 from a PC?

Use the LOGO! Ethernet port with a Cat 5e patch cable (e.g., 6XV1850-2GH20) plus LOGO! Soft Comfort V8.4 or later. If only USB is available, the Siemens PC cable 6ED1057-1AA01-0BA0 connects the PC to the LOGO! programming port directly.

What IP address does the LOGO! 8 default to?

The 0BA8 Base Module ships with IP 192.168.0.10, subnet mask 255.255.255.0. The HMI and PC must be on the same 192.168.0.x subnet to discover and connect.

Does the KTP need TIA Portal or can I use WinCC flexible?

Use TIA Portal V17 or later for new KTP Basic projects — WinCC flexible is out of maintenance. The SIMATIC S7/LOGO driver is included in TIA Portal and is the only driver required for LOGO! 8.

Are Comfort Panels (TP700/TP1200) supported on LOGO! 8?

Yes. The same S7/LOGO driver and DB1 addressing apply, but Comfort Panels add functions such as Sm@rtServer, PROFIenergy, and remote Web access that LOGO! 8 cannot fully exercise. Basic Panels are the cost-effective choice for tag-only visualization.

Back to blog