Problem Overview
An S7-300 CPU 315-2DP, configured as part of a software-redundant (SWR) pair and communicating over MPI to its partner and Profibus to existing SCADA/HMI, is forced into STOP immediately after the engineering station downloads a modified hardware configuration containing a newly added CP 343-1 Ethernet module (catalog number 6GK7 343-1CX10-0XE0). The CPU SF (Group Error) LED and BF (Bus Fault) LED blink together, the mode selector remains in RUN-P, and SIMATIC Manager > PLC > Diagnostics/Setting > Diagnostics Buffer records a single terminating event. The buffer entry identifies the stop as a user-program-initiated STOP command, originated from the warm-restart OB (OB100), and reports an FC call (FC 100) at module address 2860. Because FC 100 is part of the protected Software Redundancy library, the engineer cannot open the block source to confirm what is being executed.
This is one of the most common first-day failures when retrofitting Ethernet onto a live S7-300 SWR pair, and the root cause is almost always the same: a previously set test breakpoint still active in the startup sequence. When the warm restart calls OB100, the breakpoint fires, STEP 7/S7-PLCSIM/S7-300S debug firmware executes an internal SFC 46 STP, and the CPU drops to STOP before the redundancy initialization can complete.
Affected Hardware and Software Stack
| Item | Catalog / Version | Role in Failure |
|---|---|---|
| CPU | 6ES7 315-2AFxx-0AB0 (CPU 315-2DP, firmware v2.x or v3.x) | Executes OB100; calls FC 100 from the SWR library |
| Redundant partner | Identical CPU 315-2DP | Connected via MPI cable for SWR synchronization |
| Profibus CP | CP 342-5 (e.g. 6GK7 342-5DA02-0XE0) | Existing SCADA/HMI Profibus segment, unchanged |
| New Ethernet CP | 6GK7 343-1CX10-0XE0 (CP 343-1 Lean, 2-port switch) | Added for SCADA TCP/IP communication |
| Software Redundancy library | "S7-SWRED" for S7-300, blocks FB 100, FB 101, FC 100, DB 100, DB 101 | Protected FC 100 is called from OB100; source not editable |
| Engineering | SIMATIC Manager V5.5 + SPx, STEP 7 V5.6 | HW Config download triggers warm restart |
The CP 343-1 Lean (CX10) provides one RJ45 port pair (10/100 Mbit/s) and supports S7 communication, TCP, UDP, ISO-on-TCP, and PROFINET IO controller (limited). It is suitable for the SCADA migration; the failure is not a result of catalog number or firmware mismatch.
Decoding the Diagnostics Buffer
Read the buffer top-down (most recent event at the top). The terminating entry is the only one that matters for the root cause; entries above it are downstream effects (communications failure, partner CPU no longer reachable, etc.) caused by the local STOP.
| Field | Value Reported | Engineering Meaning |
|---|---|---|
| Event ID | 16#457F | Standard S7 diagnostics ID meaning "STOP caused by STOP command" - a request, not a fault |
| Cause text | "STOP caused by STOP command" | An OB or system block explicitly called SFC 46 (STP) |
| Breakpoint in user program | Startup OB (OB100) | Stop was triggered during warm restart, not during cyclic OB1 |
| Priority class | 27 | Priority of the startup OB on S7-300 (startup class) |
| FC Number | 100 | The block that was executing when the STOP was issued |
| Module address | 2860 (decimal) = 0x0B2C | STEP 7 internal block-ID; with OB100 + FC100, this points to the location in the load memory where the breakpoint trap was armed |
| Previous operating mode | START UP (warm restart) | Confirms OB100 was the active OB at the moment of STOP |
| Requested operating mode | STOP (internal) | STOP was requested by the firmware/debug logic, not by the mode selector |
| Event direction | Incoming | Event first occurrence on this STOP |
The combination of Breakpoint in user program + FC 100 + OB100 + Event 16#457F is the canonical signature of a residual debug breakpoint. STEP 7 stores breakpoints as instruction-pattern patches in the loaded S7 program. When a breakpoint is set, the STEP 7 online editor replaces the original machine instruction with a STP (or BLD/STA pattern that the firmware interprets as a breakpoint trap). The trap halts execution and requests a transition to STOP so that the PG can take control. When the program is later downloaded without first clearing the breakpoints, the patch remains in the CPU load memory.
Why Adding the CP 343-1 Triggered the Stop
- The project is offline-edited: HW Config is opened, the CP 343-1 CX10 is dragged into slot 4 (or the next free slot), and the new Ethernet network is configured (IP address, subnet, S7 connection).
- Station > Save and Compile rebuilds the system data blocks (SDB) and the offline program. The recompilation may strip breakpoint metadata or, depending on the option set, may leave the SDBs but rearm breakpoints during the next download.
- PLC > Download to Target writes the new SDBs and user program to both CPUs of the SWR pair. The CPU detects a configuration change that requires a warm restart and executes OB100.
- OB100 in a standard SWR application calls FC 100 (the SWR initialization block). FC 100 is reached. The instruction patch armed by the breakpoint trap fires.
- The debug firmware recognizes the trap and calls SFC 46 STP internally. The CPU transitions to STOP. The BF LED blinks because the now-stopped CPU has dropped its bus connections, including the just-configured Ethernet interface.
- The SF LED blinks because the SF group error is asserted for any STOP-with-error condition that is not a clean power-off/STOP-from-selector path.
The previously-added Ethernet CP is a symptom of the timing, not a cause. The same failure would appear on any future restart - for instance after a partner CPU failover, after a battery change, or after a manual restart from STEP 7.
Step-by-Step Resolution
Follow this sequence in order. Steps 1-3 fix the immediate problem; steps 4-6 harden the system so the issue does not recur.
Step 1 - Clear all breakpoints in the offline project
- In SIMATIC Manager, open the S7 program and the OB100 source (and OB101/OB102 if present).
- From the menu, choose Debug > Breakpoints > Delete All. This removes the instruction patches from the offline blocks.
- Repeat the action for the entire project: in the LAD/FBD/ST editor you can use the keyboard shortcut
Ctrl+Shift+F5to remove all breakpoints in the open block, and PLC > Clear All Breakpoints when online to remove any breakpoints that are also armed in the CPU's online copy. - Save and recompile (Program > Compile All).
Step 2 - Perform a clean program download
- Connect to CPU 0 (the master of the SWR pair). The CPU is in STOP.
- Use PLC > Download User Program to Memory Card or, if the project is on a PG with EPROM, write the MMC with the cleaned blocks first.
- Perform PLC > Download to Target and select the option Download user program only with Replace object enabled, so that all blocks (OB, FB, FC, DB, SDB, SFB, SFC) are overwritten with the freshly compiled versions.
- Wait for the download to complete. Do not switch the mode selector yet.
Step 3 - Bring CPU 0 to RUN and validate
- Turn the mode selector from STOP to RUN. The CPU performs a warm restart.
- OB100 executes. FC 100 runs to completion. No breakpoint trap fires. SWR initialization (FB 100/FB 101 sequence) completes and reports the partner CPU as the standby.
- Verify in PLC > Diagnostics/Setting > Diagnostics Buffer that the new entry is Mode transition from STARTUP to RUN (Event ID 16#4542 or similar) without a 16#457F entry.
- Verify that the SF and BF LEDs extinguish within a few seconds of RUN entry. BF may briefly blink during Ethernet link negotiation; this is normal.
Step 4 - Repeat for CPU 1 (the standby)
Software redundancy is hot-standby symmetric: both CPUs must have identical breakpoints configuration. Connect to CPU 1, perform the same clear/download/verify cycle. Some teams prefer to bring CPU 1 up first to avoid a partner-side STOP propagation, but either order works as long as both CPUs are eventually verified clean.
Step 5 - Verify the new Ethernet CP is online
- From Start > Simatic > SIMATIC Manager > Options > Set PG/PC Interface, select the TCP/IP interface pointing at the CP 343-1.
- Open PLC > Accessible Nodes. The CPU should appear with the configured IP.
- Open a free S7 connection (e.g. Options > Configure Network > right-click the S7 connection > Connection Status). Status should report
ESTABLISHEDfor the S7 connection to the SCADA partner.
Step 6 - Lock the engineering workflow against re-introduction
- Document in the project README that "FC 100 is a protected SWR block; never set breakpoints in the SWR library path (OB100/OB101/FB100/FB101/FC100)".
- Add a project-level sign-off step: any engineer downloading to the SWR CPUs must confirm Debug > Breakpoints > Delete All immediately before download.
- Disable the Debug menu in the runtime PG profile used for production download, or restrict it via Windows group policy if the project is governed by a change-management process.
Verification Matrix
| Check | Expected Result | Where to Read |
|---|---|---|
| CPU mode | RUN, SF off, BF off (or briefly blinking during Ethernet negotiation) | Mode selector + LED panel |
| Latest diagnostics event | Mode transition to RUN, no 16#457F entry | Diagnostics Buffer, top entry |
| SWR status | CPU 0 = Master, CPU 1 = Standby, both online and healthy | FB 100 instance DB > status word (e.g. DB 100.DBW0) |
| Ethernet CP online | Connection established, link LED on, IP reachable | Accessible Nodes, NCM S7 Diagnostics > Connections |
| SCADA HMI comms | Profibus CP + Ethernet CP both show established S7 connections | NCM Diagnostics > Connection list, all green |
| Breakpoints in CPU | None in any OB/FB/FC | Online > Accessible Blocks > right-click > Breakpoints list (must be empty) |
Why FC 100 Is Protected and What It Does
The S7-300 Software Redundancy package ("S7-SWRED" / library ID SWRED) ships with a small set of blocks that the customer is not supposed to edit. FC 100 is one of those blocks. Its role in OB100 is to perform the redundancy initialization handshake: it reads the role (master or standby) from the SWR instance DB, validates the partner's role and synchronization state, and prepares the data containers used by FB 100 (cyclic SWR operation) and FB 101 (start-up and resynchronization).
Because the block is delivered as compiled-only ("protected"), you cannot open the STL to find the literal CALL SFC 46. The breakpoint fires before SFC 46 is reached, so even a hypothetical STL view would only show the trap patch and the line after it. This is why the diagnostics buffer reports Breakpoint in user program rather than SFC 46 called from user program - they are the same event, but the breakpoint message takes precedence in the buffer formatting.
Alternative Root Causes (If Breakpoints Are Not the Issue)
If step 1-3 above do not clear the 16#457F entry, work through this list. Each row includes the diagnostic signal and the corrective action.
| Alternative Cause | Diagnostic Signature | Corrective Action |
|---|---|---|
| Different HW Config between the two SWR CPUs | Partner CPU reports "Configuration mismatch" or "Station failure"; only one CPU stops | Download the same HW Config to both CPUs; verify rack and slot order match exactly |
| MMC with old project still in CPU 0, new program in CPU 1 | Diagnostics buffer shows "STOP caused by parameter assignment error" with SDB mismatch | Pull MMC, MRES, reload from PG; never mix MMC and online download for SWR |
| CP 343-1 firmware older than the minimum supported by the CPU firmware | Buffer shows "Module failure" or "Parameter assignment error" for slot 4; F LEDs on CP | Upgrade CP firmware via SIMATIC Manager > Options > Firmware Update; cross-check Siemens compatibility tool |
| IP address conflict with another device on the plant network | CP 343-1 BF LED steady on; "Duplicate IP address detected" or ARP storm in network log | Re-IP the CP, isolate the SCADA VLAN, confirm with network admin |
| CPU 315-2DP memory exceeded by the new SDBs (S7-300 has limited work memory) | Buffer shows "STOP due to memory exhaustion" with event 16#45xx | Check the load memory / work memory budget in PLC > Module Information > Memory; use a CPU 315-2 PN/DP or 317-2 if required |
| Operator accidentally pressed the mode selector to STOP during commissioning | Buffer shows 16#4580 (operator-initiated STOP), not 16#457F | Re-engage RUN-P; no code change required |
For each of the above, the fix is in HW Config or firmware, not in the SWR library. Most of these produce a different event ID; 16#457F combined with the words Breakpoint in user program almost always points back to the breakpoint path.
Reading the S7 Diagnostics Event IDs Used Here
| Event ID | Standard Meaning | What to Look For |
|---|---|---|
| 16#457F | STOP caused by STOP command (user program or breakpoint) | OB100 entry, FC 100, address 2860, priority 27 - this article |
| 16#4542 | Mode transition STARTUP to RUN, no error | Healthy warm restart |
| 16#4580 | STOP caused by mode selector (operator) | Not user-program-induced |
| 16#45A0 | STOP due to parameter assignment error | HW Config / SDB mismatch |
| 16#4302 | Module removed or failed | Check the slot mentioned in the entry |
| 16#38xx | Communication error on S7 connection | Check CP and connection list |
The full mapping of S7-300/400 event IDs is documented in the Siemens Online Help for STEP 7 (Help > Contents > Diagnostics > Event IDs). Use this table only as a quick triage; the live buffer is the source of truth.
Reading Module Address 2860 in Context
The decimal value 2860 (0x0B2C) is not a Profibus station number or an Ethernet IP - it is an internal STEP 7 reference into the load-memory block table. For OB100 + FC 100, 2860 is a stable identifier on CPU 315-2DP for the breakpoint location inside FC 100's first network. Treat the address as confirmation that the breakpoint is inside the protected SWR block, not as a hint about the network or the new CP.
Safe Commissioning Procedure for S7-300 SWR with a New CP
Use this procedure when the protected FC 100 is in the project and you must change hardware. It is written to be executed offline on a simulated or stopped system, then promoted to the live system.
- Open the offline project in SIMATIC Manager. Verify the SWR library version is consistent between the offline and online projects (Options > Compare Blocks).
- Choose Debug > Breakpoints > Delete All in the LAD/FBD/ST editor. Save the project.
- Open HW Config, add the CP 343-1, configure the Ethernet interface and any S7 connections. Save and compile.
- Connect online to the standby CPU first (the lower of the two MPI addresses; SWR master is typically MPI 2, standby is MPI 3 by convention).
- Place the standby CPU in STOP. PLC > Download to Target with the option Download user program and HW configuration. After the download, the CPU remains in STOP.
- Switch the standby to RUN. The CPU warm-restarts, runs through OB100/FC100, and goes to RUN. Verify the diagnostics buffer shows the healthy STARTUP-to-RUN transition.
- Repeat steps 4-6 for the master CPU. The two CPUs will renegotiate their roles on the next redundancy scan; if FB 100 reports the master role has flipped, this is normal after a download and the plant will not see a process interruption if SWR is configured for bumpless role swap.
- Verify the new Ethernet CP from Accessible Nodes and confirm SCADA traffic is restored.
Edge Case: Breakpoint Set on the Online Copy Only
If a breakpoint was set on the online copy of OB100 but never on the offline block (a common situation during remote debugging sessions), the offline project looks clean and a recompile-and-download will not necessarily clear the online breakpoint. In that case:
- Connect online to the CPU.
- Open OB100 online.
- From the menu, choose Debug > Breakpoints > Delete All. The instruction patches are removed from the online copy without changing the offline project.
- Switch the CPU to STOP and back to RUN to clear the in-flight trap. If the CPU is in STOP because of the trap, simply clear the breakpoints and switch to RUN; the warm restart will run cleanly.
Edge Case: Compiled With Different Compiler Settings
STEP 7 V5.5 SP4 and later can produce blocks that contain new breakpoint trap opcodes that older firmware does not recognize. The reverse is also possible. If the SWR project is shared between engineering stations on different STEP 7 versions, recompile on a single agreed version and stamp the build with a project header that records the compiler version. Mismatched compilers have been known to produce blocks that carry a stray breakpoint marker across downloads.
Long-Term Hardening Checklist
- Keep one PG as the "production download" station, locked to a single STEP 7 version, with breakpoints disabled by default and the Debug menu pinned to a custom profile.
- Maintain a versioned archive of the offline project including the SWR library. Tag the archive with the date of the last breakpoint check.
- When migrating SCADA, follow the standard offline-edit > simulate > dry-run on a stopped CPU > promote to live workflow. Do not live-edit HW Config on a running SWR pair.
- Add the diagnostics buffer 16#457F signature to the site's PLC alarm classification so that on-call engineers can recognize the breakpoint case within minutes.
- Review the project's F-block and protected-block list once a quarter; remove any know-how-protected blocks that are no longer in active use, to keep the breakpoint surface area small.
Reference: SFC 46 STP Behavior
SFC 46 (STP) is the user-callable block that forces the CPU to STOP. The breakpoint trap implemented by the STEP 7 debug firmware uses the same CPU mechanism - the firmware pre-empts the call by replacing the instruction at the breakpoint with a STP opcode and setting a flag indicating it is a debug trap. The result is functionally identical to a user CALL SFC 46 from the engineer's point of view, which is why the diagnostics buffer records Event 16#457F in both cases.
SFC 46 has no parameters; it is a procedural "go to STOP now" instruction. OB1, OB100, OB101, OB102, OB121, OB122, and any FB/FC may call SFC 46. A well-written application calls SFC 46 only from a controlled error path (e.g. a hardware-fatal OB that requests an orderly shutdown). Calling SFC 46 in OB100 is a debug artifact, not a designed shutdown.
Reference: S7-300 Software Redundancy Block Set
| Block | Type | Name | Editable? | Called From |
|---|---|---|---|---|
| FB 100 | FB | SWR_ZYK (cyclic SWR operation) | No - protected | OB1 (or OB35 in time-driven mode) |
| FB 101 | FB | SWR_START (start/resync) | No - protected | OB100/OB101 (depending on role) |
| FC 100 | FC | SWR_INIT (initialization helper) | No - protected | OB100 (per the customer's project) |
| DB 100 | DB | SWR instance data | Yes - via FB 100 instance view | N/A |
| DB 101 | DB | SWR start instance data | Yes - via FB 101 instance view | N/A |
The actual block numbers and names vary slightly across SWR library revisions; the role of FC 100 as the OB100 initialization block is the same across versions. The exact block numbers should be confirmed against the project's SWRED library header.
FAQ
What does Event ID 16#457F mean on an S7-300 CPU?
Event 16#457F means "STOP caused by STOP command" - the CPU entered STOP because OB100 (in this case) called SFC 46 STP, either directly or because a debug breakpoint trap fired at that location. It is a controlled user-program-initiated stop, not a hardware fault.
Why does the CPU stop with FC 100 even though FC 100 is protected?
FC 100 is the protected Software Redundancy initialization block called from OB100. A breakpoint set in the protected code replaces the original instruction with a trap that the firmware handles as if SFC 46 were called. Because the source is protected, you cannot see the trap in the editor; the diagnostics buffer's "Breakpoint in user program" line is the only hint that a breakpoint is the cause.
How do I clear breakpoints permanently on an S7-300 SWR CPU?
Open the project in SIMATIC Manager, choose Debug > Breakpoints > Delete All in each editor, save, recompile, and download with Replace object enabled. For breakpoints that exist only online, connect to the CPU, open the block online, and use the same Delete All command. Repeat the cycle for both CPUs of the SWR pair.
Does adding a CP 343-1 (6GK7 343-1CX10-0XE0) cause the CPU 315-2DP to stop?
Not directly. The CP itself and the HW Config change are not the root cause. The HW Config download triggers a warm restart; OB100 runs and the breakpoint that was already armed in FC 100 fires, calling SFC 46 STP. Removing the breakpoint before any subsequent download (with or without further hardware changes) eliminates the failure.
Can I keep using software redundancy on a CPU 315-2DP while adding Ethernet?
Yes, provided the SWR library is correctly installed, the MPI redundancy link is intact, and the new Ethernet CP is added on a free slot without disturbing the existing Profibus CP. Validate the redundancy behavior after the change by performing a forced partner failover and confirming a bumpless process transition.
What is the difference between event 16#457F and 16#4580?
16#457F is a STOP command issued from the user program (or a breakpoint trap inside it). 16#4580 is a STOP command issued by the operator via the mode selector. The corrective action is different - 16#457F requires removing the breakpoint or the offending SFC 46 call; 16#4580 only requires switching the selector back to RUN.