Connecting Multiple Load Cells to SIWAREX FTA Wiring

David Krause11 min read
Sensor IntegrationSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Overview: SIWAREX FTA Multi-Load-Cell Applications

The Siemens SIWAREX FTA (Function Technology Weighing) is a strain-gauge weighing module designed for integration into SIMATIC automation systems (S7-300, S7-400, ET 200S, ET 200SP via the appropriate adapter). Although the FTA module itself has only one analog load-cell input, large vessels, silos, hopper scales, and platform scales routinely use two, three, four, or more load cells mechanically supporting a single weighing structure. The electrical sum of these parallel load cells must be presented to the FTA as a single equivalent bridge.

This article explains:

  • How to wire 2–4 (or more) load cells to a single SIWAREX FTA input.
  • The role of the SIWAREX JB junction box.
  • Bridge excitation / sense line compensation when 4-wire load cells are used with a 6-wire FTA cable.
  • How the theoretical calibration value changes when multiple cells share the load.
  • Step-by-step configuration with SIWATOOL FTA.
  • Field verification, troubleshooting, and FAQ.
Engineering rule: From the SIWAREX FTA's perspective, one load cell or four load cells in a properly wired junction box is electrically identical. All differences are mechanical (load distribution) and calibration-related (total characteristic value).

2. Prerequisites

Item Specification / Catalog Reference
SIWAREX FTA module 7MH4900-1AA01 (1-channel, ET 200S) or 7MH4900-2AA01 (S7-300 design). Check firmware ≥ V1.0 for parameter set revision.
Load cells Strain-gauge full bridge, 350 Ω or 1000 Ω nominal, sensitivity 1–4 mV/V (typ. 2 mV/V), excitation 5–12 V DC.
Junction box SIWAREX JB (4-cell or 6-cell version), or any IP65/IP67 summing box with adjustment resistors.
Shielded cable (FTA ↔ junction box) 6-wire shielded, e.g. LiYCY 6×0.34 mm², twisted pair for sense lines.
Configuration tool SIWATOOL FTA V4.x (USB service interface, SIWAREX IS or RS-232 cable).
SIMATIC integration SIMATIC S7-300/400 or ET 200S with SIWAREX FTA function block (FB SIWA) in STEP 7 / TIA Portal library.
Reference weights Calibrated test weights (or water/dry sand with known mass) for verification calibration.

3. Wiring Topology — One FTA, Multiple Load Cells

3.1 Why a Junction Box Is Mandatory

When a vessel rests on N mechanically parallel load supports, each cell sees only a fraction 1/N of the total weight (in the ideal equal-load-distribution case). The SIWAREX FTA can only read one bridge, so the individual bridges must be wired in parallel (input, output, and sense lines tied together) and routed through a junction box that also provides:

  • A single multi-conductor output cable to the FTA.
  • Optional trim resistors in each corner of each bridge, used to balance cell outputs so the combined bridge zero is near zero at no-load.
  • A means to disconnect individual cells for diagnostics.

3.2 4-Wire vs. 6-Wire Load Cells

Cell Type Leads Sense Lines? Required at Junction Box
6-wire load cell EX+, EX−, SIG+, SIG−, SEN+, SEN− Yes Parallel all six lines; no jumper required.
4-wire load cell EX+, EX−, SIG+, SIG− No (sense is taken at the cell) Bridge SEN+ ↔ EX+ and SEN− ↔ EX− inside the JB; route a 6-wire cable to the FTA so its remote sense sees the actual excitation at the JB.

The 4-wire → 6-wire conversion is necessary because long cables between the JB and the FTA introduce a voltage drop on the EX lines that the FTA's differential amplifier would interpret as a weight error. By using the FTA's sense inputs to measure the excitation at the JB terminals, the excitation error is rejected.

3.3 Pinout Reference (FTA ↔ JB)

FTA Terminal Signal JB Terminal (typical)
1 SEN+ Jumper to EX+ (4-wire) or to cell SEN+ (6-wire)
2 SEN− Jumper to EX− (4-wire) or to cell SEN− (6-wire)
3 EX+ (BR+) EX+ of every cell in parallel
4 EX− (BR−) EX− of every cell in parallel
5 SIG+ (DO+) SIG+ of every cell in parallel
6 SIG− (DO−) SIG− of every cell in parallel
7 SHIELD Junction box ground lug; one end only to PE
All four (or N) cells must share identical polarity. Reversing EX+/EX− or SIG+/SIG− on a single cell produces a sign-inverted contribution that cancels a healthy cell, halving the apparent sensitivity.

3.4 Schematic (Inline SVG Topology)

SIWAREX JB LC1 LC2 LC3 LC4 FTA Module BR+ BR− D+ D− SEN+ SEN− Vessel / Hopper Mechanical supports to LC1, LC2, LC3, LC4

4. Theoretical Calibration With Multiple Load Cells

Two calibration paths exist. Both are documented in Siemens Support Entry 37734709 — SIWAREX FTA Basic Configuration & Calibration.

4.1 Calibration With Test Weights (Recommended)

  1. Mechanically load the empty vessel. The FTA reports the dead load.
  2. Place calibrated weights equal to ~50–100% of nominal capacity on the vessel.
  3. Enter the value in SIWATOOL's Adjustment dialog: weight → 2,000.00 kg (example). The FTA scales its characteristic value automatically.

This method works identically for 1, 2, 4, or 6 cells.

4.2 Theoretical (Calculation-Based) Calibration

Use this only when no test weights are available. The total characteristic value Cv_total is the parallel sum of individual cell characteristic values:

Cv_total = Cv_1 + Cv_2 + … + Cv_N   [mV/V]

The characteristic value of each cell is given by the cell's data sheet:

Cv_i = (Sensitivity_i in mV/V) × (Capacity_i / Capacity_vessel_i)

Where Capacity_vessel_i is the load that cell i is expected to bear at full vessel load (ideal: nominal_load / N). With four identical cells of 2.0 mV/V and 5,000 kg capacity each supporting a 20,000 kg vessel equally:

  • Cv_total = 2.0 + 2.0 + 2.0 + 2.0 = 8.0 mV/V

This value is entered in SIWATOOL under DR 14 / Characteristic value. The empty-vessel zero step is still required.

If load distribution is unequal (e.g., silo center of gravity offset, eccentric discharge), weighing accuracy degrades. Use load-distribution check weights (place 1/4 weight on each support individually) and confirm no cell deviates more than the manufacturer-stated linearity spec before relying on theoretical calibration.

5. SIWATOOL FTA Configuration Procedure

  1. Connect PC via USB SIWAREX IS service cable to the FTA's front X1 port.
  2. Launch SIWATOOL FTA V4.x → choose Online → Connect. Read current parameters first (read-modify-write pattern).
  3. Set the parameter set to a free DS (e.g. DS 0 = 'Standard').
  4. Enter calibration values:
    • DR 1 — Calibration weight 0 (no-load)
    • DR 2 — Calibration weight 1 (e.g. 0 kg reference)
    • DR 3 — Calibration weight 2 (e.g. 2,000.00 kg)
    • DR 14 — Characteristic value (Cv_total from §4.2)
    • DR 30 — Zero setting range (% of nominal)
    • DR 31 — Nominal weight (kg)
    • DR 32 — Unit (kg / t / lb)
  5. Trigger zero: with empty vessel, click Adjustment → Zero. The FTA stores the digital zero.
  6. Trigger span: with calibrated weights on the vessel, click Adjustment → Span (only needed if you used a theoretical Cv).
  7. Save to RAM and to the parameter set on the FTA.
  8. Verify with intermediate load steps (25%, 50%, 75%, 100%).

6. Mechanical & Installation Best Practices

  • All load cells must be the same capacity, same sensitivity class, same model. Mixing cells introduces thermal drift asymmetry.
  • Use mounting kits with check-nodes or self-aligning load buttons to avoid side load.
  • The vessel's center of gravity should fall inside the convex hull of the cell support points.
  • Install arrestor rods / check rods so the vessel cannot tip during wind, vibration, or material impact.
  • Route the 6-wire JB→FTA cable away from VFD output cables and welding leads. Maintain ≥30 cm separation; cross at 90° when needed.
  • Ground the shield only at one end (FTA side recommended) to avoid ground loops.
  • For outdoor scales, use SIWAREX JB with IP65 sealing and cable glands matched to cable OD.

7. Verification Procedure

  1. Power cycle the FTA and confirm the Process value is stable for ≥5 minutes at no load.
  2. Apply 0% / 25% / 50% / 75% / 100% / 0% known weights. Record FTA reading each step.
  3. Compute error: e_i = (reading_i − applied_i) / applied_i × 100%. OIML R76 Class III typical acceptable limits: ≤ ±0.02% of span for non-automatic weighing, ≤ ±0.05% for industrial scales.
  4. Repeatability: 3× 100% load cycles. Repeatability error should be < 1 internal count (≈ 0.01% of full scale at default resolution).
  5. Check linearity: plot error vs. load; the curve must remain within the cell manufacturer's linearity band.
  6. Corner-load test: with ¼ of full load placed directly above each individual cell. The reading must equal the total weight within tolerance. Differences reveal cell imbalance → adjust trim resistors in the JB or apply mechanical shimming.

8. Troubleshooting Matrix

Symptom Likely Root Cause Diagnostic Action Fix
Process value saturated high (999,999) or low (-999,999) Sense line open / EX line broken / cell disconnected Measure EX+↔EX− voltage at JB: must be 5–12 V DC per cell data sheet Repair wiring; verify SEN+/SEN− jumpers for 4-wire cells
Process value reads half of expected weight One cell wired with reversed polarity (EX+/EX− or SIG+/SIG− swapped) Disconnect cells one at a time and observe net reading change Reverse the mis-wired cell's leads in the JB
Reading drifts with temperature Mixed cell types / different TC of sensitivity Compare individual cell data sheet temperature coefficients Replace with matched cells or perform in-place temperature compensation in SIWATOOL DR 41–43
Zero shifts after cable movement Loose JB terminal, intermittent cell wire Torque-check all JB screws; flex cable and watch raw mV/V Re-torque to 0.6 N·m; replace defective crimps
Theoretical calibration off by > 5% Load distribution uneven (cells not equal shares) Perform corner-load test (§7) Use test-weight calibration instead; or shim supports to equalize
Raw count jumps ±10 counts randomly EMI pickup from VFD, no shield, sense lines not twisted Inspect cable routing; check shield termination Re-route cable, ground shield at FTA end only, add ferrite
FTA reports diagnostic bit "Sense line error" SEN+ or SEN− open Check jumpers / 6-wire cable continuity Repair or replace cable
Tare / zero button does not stick DR 30 zero range too tight Inspect DR 30 setting Increase zero range to 5–10% of nominal
Weight reading shows negative when empty Vessel lighter than the mechanical tare assumed during zero Re-zero with empty vessel currently installed Repeat zero adjustment

9. SIWATOOL DR (Data Record) Reference Cheat-Sheet

DR Name Typical Multi-Cell Value
1 Calibration weight 0 (zero) 0.00 kg
2 Calibration weight 1 0.00 kg (reference)
3 Calibration weight 2 (span) 2000.00 kg (example)
14 Characteristic value (Cv_total) Sum of all cells' Cv in mV/V
30 Zero setting range 5.00 %
31 Nominal weight 20000.00 kg (vessel capacity)
32 Unit kg
38 Filter (low-pass) 2.0 Hz default for tank weighing
41–43 Temperature compensation Per cell datasheet if available
52 Operation mode 0 = standard

10. PLC Integration Notes (STEP 7 / TIA Portal)

  • Use the FB SIWA (TIA: in SIWAREX library under "SIWAREX FTA") to read FTA_DIAG, FTA_PROCESS_VALUE, and to write FTA_COMMAND.
  • The process value is returned as a REAL in engineering units (kg) once calibration is complete; no scaling math is required in the PLC.
  • Diagnostic word bit 5 = sense line error; bit 10 = calibration data invalid. Wire these to HMI alarms.
  • For redundant weighing (two SIWAREX FTA on the same tank), use a voting block — never connect two FTA modules to the same cell junction box without isolation amplifiers.

11. Sample SCL / Structured Text Snippet

// Read SIWAREX FTA process value
IF FTA_DIAG.%X5 THEN  // Sense line error bit
    bAlarmSenseLine := TRUE;
END_IF;

IF FTA_DIAG.%X10 THEN  // Calibration invalid
    bAlarmCalInvalid := TRUE;
END_IF;

rGrossWeight := FTA_PROCESS_VALUE;          // REAL in kg
rNetWeight   := rGrossWeight - rTareWeight; // tare from HMI setpoint

// Tare command (rising edge on HMI button)
IF bTareRequest AND NOT bTareRequestOld THEN
    FTA_COMMAND := 16#0001;                 // zero command per FB SIWA spec
END_IF;
bTareRequestOld := bTareRequest;

12. Frequently Asked Questions

Does SIWAREX FTA need a different firmware when using four load cells?

No. The FTA firmware is identical for one cell or multiple cells. Only the mechanical installation and the calibration characteristic value (DR 14) differ — the total Cv is the sum of all cells' Cv values.

Can I mix load cells of different capacities in the same vessel?

It is not recommended. Different capacities have different mechanical stiffness and temperature coefficients, which cause asymmetric drift and shift the corner-load balance. If unavoidable, perform a test-weight calibration rather than a theoretical calibration and verify corner-load behavior at each support.

What wire type should run between the SIWAREX JB and the FTA?

Use a 6-wire shielded cable (e.g. LiYCY 6×0.34 mm²), with the two sense lines twisted together. Keep the cable away from VFD power wiring and route the shield to PE only at the FTA end. Maximum recommended cable length is 100 m with 350 Ω cells, longer runs may require 1000 Ω cells to maintain signal integrity.

Why is my reading exactly half of expected after wiring four cells?

One of the four cells is wired with reversed polarity, so its output subtracts from the others. Disconnect cells one at a time at the JB and observe the change in the FTA's raw mV/V signal — the mis-wired cell will move the reading in the opposite direction. Correct the EX+/EX− or SIG+/SIG− wiring of that cell.

Can I omit the junction box and wire all four cells directly to the FTA?

Not recommended. A junction box gives you a single cable run, a clean shield termination, trim resistors for cell balancing, and the ability to disconnect a single cell for service. Direct wiring to the FTA is impractical for more than two cells and prevents any meaningful diagnostics or corner-load balancing.

How do I perform a theoretical calibration for four identical 5,000 kg / 2.0 mV/V cells?

Set DR 14 (Characteristic value) to 8.0 mV/V (= 2.0 × 4), set DR 31 (Nominal weight) to the vessel's nominal capacity (e.g. 20,000 kg), then perform the empty-vessel zero. If load distribution is unequal, replace the theoretical calibration with a test-weight calibration on site.

Back to blog