Overview
Distributed I/O diagnostics on a SIMATIC S7-400H redundant controller talking to ET 200M stations over PROFIBUS DP requires more than passive error LEDs. When an IM 153-2 backplane loses a signal module, inserts a wrong module, or drops off the bus, the DP master must classify the event, localize the slot, and (in an H system) decide whether the active or standby CPU owns the diagnostic record. This reference covers the three practical detection paths that engineers actually deploy in S7-400H cells:
- Evaluation of OB86 local-temp variables for rack/station faults.
- Cyclic reading of DP slave diagnostic data with SFC13 DPNRM_DG.
- Use of the Siemens diagnostic blocks FB125 and FC125 from entry ID 387257, which decode the standard PROFIBUS diagnostic frame and expose slot-level, module-level, and channel-level status to user code and to WinCC flexible / ProTool message screens.
The same toolchain applies to single-CPU S7-400 and S7-300 masters; the H-specific constraints (master/standby, master-master changeover, redundant DP) are called out in dedicated sections below.
System Architecture and Addressing
A typical S7-400H PROFIBUS-DP cell with ET 200M islands consists of:
- Two CPU 417-4H controllers, each with a DP master port (X1 or X2 depending on slot configuration) configured for PROFIBUS DP and synchronized over fiber-optic sync modules.
- One or more ET 200M stations built around the IM 153-2 interface module (6ES7153-2BA02 / -2BB00 / -2BA10 / -2BA70 / -2BA82 depending on feature set). The IM 153-2 is the PROFIBUS DP slave side; it accepts up to 8 or 12 signal modules depending on variant.
- Diagnostic addresses that are unique per station. Each ET 200M rack occupies a single PROFIBUS station address (for example, station 8 and station 9) but its slots are mapped inside the station's process image and its diagnostic address is the DP slave's logical base address.
The IM 153-2 operating instructions (see ET 200M Operating Instructions, edition 06/2009 or later) define the diagnostic buffer structure that FB125 parses. When you parameterize the IM 153-2 in HW Config, set:
| Parameter | Recommended value | Comment |
|---|---|---|
| DP slave diagnostic address | Unique per station (e.g. 2048, 2049) | Passed to FB125 as DIAG_ADDR
|
| Slot routing | Activated | Allows slot-level diagnostic frames |
| Module replacement during operation | Enabled where supported | See section below |
| Response monitoring | Enabled (default) | Disable only with explicit user-mode justification; outputs then hold last value on master failure (per IM 153-2 manual) |
Detection Path 1: OB86 Local-Temp Variables
OB86 (Rack failure / station failure OB) fires whenever a DP master detects a station come, go, or change event. The startup information gives you the DP master system ID, the station number, the event type, and the slot for module-level events.
Key local-temp bytes (OB86_START_INFO) per the S7-300/400 System and Standard Functions manual:
| Byte / Word | Symbol | Meaning |
|---|---|---|
| LW0 | OB86_FLT_ID | Event class: W#16#3900 station return, W#16#3901 station failure, W#16#3902 station fault, W#16#3903 slave diagnostics, W#16#3904 S7-400H master-master changeover |
| LB4 | Reserved | — |
| LW6 | OB86_MDL_ADDR | Logical base address of the DP slave reporting |
| LB8..LB11 | OB86_Z23 / OB86_Z33 | Slot/insert-event payload |
| LW12..LW15 | OB86_RESERVED_1 | H-system add-ons: master/standby flag, time stamps |
For a basic class-of-fault indicator, evaluate OB86_FLT_ID in OB86 and copy OB86_MDL_ADDR and slot information into a global diagnostic flag block. This delivers a low-latency, event-driven indication that the rest of the application can latch without polling PROFIBUS.
Detection Path 2: SFC13 DPNRM_DG
SFC13 DPNRM_DG reads the standard PROFIBUS DP diagnostic frame of a slave in compliance with EN 50170. It works on both S7-300 and S7-400 masters, including the active master in an H system. Inputs and outputs:
| Parameter | Type | Description |
|---|---|---|
| REQ | BOOL | Trigger with positive edge to read the next slave |
| LADDR | WORD | Configured diagnostic address of the DP slave (e.g. W#16#800) |
| RET_VAL | INT | Return value; 0 = ok, W#16#80A1 = resource busy, W#16#80A2 = parity error in DP frame, W#16#80A3 = DP protocol error, W#16#80A4 = bus fault, W#16#80A7 = DP slave not available |
| RECORD | ANY (BYTE) | Target area for the diagnostic data (recommend ≥ 34 bytes to capture the standard 6-byte header plus ID-related diagnostics) |
| BUSY | BOOL | 1 = operation in progress, 0 = complete |
Recommended approach in an S7-400H cell: schedule a low-priority OB1 (or OB35 cyclic) call that cycles through the configured diagnostic addresses, calling DPNRM_DG only when BUSY of the previous call is 0. Decoding the resulting buffer by hand is tedious (you must walk the ID-related diagnostic block at offset 6, parse module status bit-by-bit, and decode channel-specific diagnostics at offset 12+). This is exactly the pain that FB125 removes.
Detection Path 3: FB125 and FC125
The Siemens-supplied block pair is the de-facto standard for ET 200M diagnostics in STEP 7 classic projects:
| Block | Type | Capability |
|---|---|---|
| FC125 | FC (function) | Reads standard diagnostic data for one DP slave and decodes station-level status. Does not report the slot number of a defective module inside an ET 200M. |
| FB125 | FB (function block) | Adds per-slot decoding using the slot routing mechanism of the IM 153-2. Reports slot number, module type, channel number, and channel error code. Also returns H-system master/standby status. |
Installation
- Download the package from Siemens Support entry 387257 (search title: "Function block for PROFIBUS DP diagnostics / FB125, FC125").
- Unzip into a working directory and open the included STEP 7 project (or copy the STL sources into your project).
- Open your S7 program, right-click the Blocks folder, and import the S7 library. The package ships FB125, its associated DB (DB125), the UDTs for the diagnostic structures, and example OB calls.
OB Calls Required
FB125 must be called in all three OBs the DP slave state machine can fire into:
- OB1 (or OB35) — cyclic polling, captures the standard diagnostic frame between events.
- OB82 — module diagnostic interrupt (analog cards, smart cards, channel faults).
- OB86 — rack/station failure & return.
Failing to wire all three OBs leads to silent loss of state transitions: a module that goes from "diagnostic pending" to "module removed" will not surface in DB125 unless OB86 also calls the block.
FB125 Interface (condensed)
| I/O | Symbol | Meaning |
|---|---|---|
| INPUT DIAG_ADDR | WORD | Configured diagnostic address of the slave |
| INPUT CALL_FROM_OB | BYTE | OB context: 1=OB1, 82=OB82, 86=OB86, 121/122=H-changeover |
| INPUT OB86_RESERVED_1 | DWORD | Pass OB86_RESERVED_1 directly from the H-system OB86 start info |
| OUTPUT SLOT_NUM | INT | Slot (1..12) of the offending module inside the ET 200M, or 0 if station-level only |
| OUTPUT MODULE_TYPE | BYTE | Module category (DI/DO/AI/AO/IM/...) decoded from ID-related diagnostics |
| OUTPUT CHANNEL_NUM | INT | Channel number for channel-diagnostic events |
| OUTPUT ERROR_CODE | WORD | Channel error code per the standard PROFIBUS mapping |
| OUTPUT MASTER_STANDBY | BOOL | H-system indicator: 0=master, 1=standby |
| OUTPUT NEW_DIAG | BOOL | Set when a fresh diagnostic event has been latched |
Wire the output UDT to your HMI message system, your plant historian, and a maintenance-page bit. Reset NEW_DIAG with a positive edge from the operator "acknowledge" button.
Encoding Channel Error Codes
When FB125 surfaces a channel-level fault, the upper three bits of ERROR_CODE indicate the error type per EN 50170 / IEC 61158-6:
| Bit pattern (b2..b0) | Type | Typical cause |
|---|---|---|
| 000 | Reserved | — |
| 001 | Short circuit | Sensor or load wiring fault |
| 010 | Under-voltage | 24 V supply collapsed, wire break on supply |
| 011 | Over-voltage | Overrange on analog input |
| 100 | Overload | Output exceeded rating |
| 101 | Overtemperature | Module or terminal too hot |
| 110 | Wire break | Open circuit on input or output side |
| 111 | Upper limit exceeded | Process value > configured overrange |
Map this to a human-readable string in your HMI rather than shipping raw bit fields to the operator.
S7-400H-Specific Behavior
Three constraints dominate diagnostics on a CPU 417-4H redundant pair:
- Standby CPU does not run OB82/OB86 by default. The standby CPU copies the master's memory areas but does not execute user program. It receives DP diagnostic events only via the link-up and master-master changeover. You cannot rely on standby-side OBs to feed your historian.
-
Master-master changeover (H-system failover) fires OB86 with
OB86_FLT_ID = W#16#3904. When OB86 fires with that event, both CPUs mark the DP diagnostic state of the previously-active CPU as "stale". Call FB125 in OB86 to re-initialize DB125 after a changeover; otherwiseNEW_DIAGwill report events that belong to the pre-failover period. -
Redundant ET 200M pairs (two IM 153-2 in the same rack, switched via Y-Link) require Y-Link-aware diagnostics. The Y-Link itself reports as one PROFIBUS station; the two ET 200M backplanes appear as sub-slots. FB125 with slot routing set in HW Config will resolve sub-slots, but you must extend
DIAG_ADDRto the Y-Link's logical base address and verify the slot mapping against the Y-Link manual.
Module Replacement During Operation (Hot-Swap)
ET 200M supports pulling and inserting modules while the backplane is powered, provided the IM 153-2 supports "Module replacement during operation" and the function is enabled in HW Config. From the TIA Portal help: Configuration of the 'Module replacement during operation' function:
- Right-click the IM 153-2 in the device view and open Properties > Module parameters > General.
- Enable Module replacement during operation (also called Module swapping without PG).
- Configure the slot from which modules may be replaced. Out of the box, the IM 153-2 reserves slot 0 for itself; slots 1..12 accept field modules. Reserved slots cannot be hot-swapped.
- If required, configure the substitute module type per slot. The IM 153-2 verifies the inserted module against the configured type and either accepts the replacement silently (configured substitute) or raises a diagnostic interrupt (incorrect type).
Diagnostic flow during hot-swap:
- Operator pulls a module → OB82 fires with module-removed diagnostic.
- FB125 decodes
SLOT_NUMandMODULE_TYPEand setsNEW_DIAG. - Operator inserts replacement → OB82 fires again with module-inserted diagnostic.
- FB125 clears the per-slot fault and the new module's process image updates.
If the IM 153-2 reports the new module as type mismatch, the slot stays in diagnostic state and the process image of the slot is zero. Use this to alarm the operator that the wrong spare was inserted.
Response Monitoring Behavior
The IM 153-2 ships with response monitoring enabled. When the DP master fails or the bus is broken, the ET 200M outputs follow the configured fallback strategy:
- Response monitoring ON (default): outputs go to a safe state (typically 0) within the configured watchdog time (default 100 ms, configurable from 10 ms to 600 s).
- Response monitoring OFF: outputs hold their last value on a DP master failure. This is permitted by the IM 153-2 manual and is sometimes used in continuous-process applications where brief bus interruptions must not perturb the plant, but it must be enabled with a clear process-safety justification.
Cross-reference: ET 200M Operating Instructions, section on response monitoring.
Commissioning Procedure
- In HW Config, configure the ET 200M station and set a unique diagnostic address in the DP slave properties. Note the address in the project documentation.
- Enable Slot routing on the IM 153-2 (this is required for FB125 to deliver slot numbers).
- Install FB125 / FC125 in the S7 program. Confirm DB125 is generated automatically when FB125 is first compiled.
- Call FB125 in OB1, OB82, and OB86 with the correct
DIAG_ADDRfor each DP slave. In H systems, install on the active-master side only. - Compile and download.
- Force a test event: pull a DI module, observe OB86 fire, confirm
NEW_DIAGin DB125, confirm the slot number on the HMI. Re-insert the module, confirmNEW_DIAGclears and the process image updates. - Trigger a bus fault by unplugging the PROFIBUS connector. Confirm
OB86_FLT_ID = W#16#3901and that the operator screen reflects the station as failed. - In H systems, force a master-master changeover. Confirm OB86 fires with
W#16#3904, confirm DB125 is re-initialized, confirm the new active master takes ownership of DP diagnostics.
Troubleshooting Matrix
| Symptom | Likely cause | First check | Fix |
|---|---|---|---|
OB86 fires with W#16#3901 but FB125 reports SLOT_NUM = 0
|
Slot routing not enabled in HW Config | DP slave properties > Slot routing | Enable slot routing, re-download HW Config |
| SFC13 returns W#16#80A2 repeatedly | Diagnostic buffer too small or uninitialized | Length of the ANY pointer passed as RECORD | Use ≥ 34 bytes, initialize the buffer with 0 |
| No OB82 fires when an analog input breaks a wire | Channel diagnostic not enabled on the module | Module parameters > Diagnostics > Wire break | Enable "Wire break check" in the analog module properties |
After master-master changeover, NEW_DIAG stays latched |
FB125 not called in OB86 on the new master | OB86 source code in the new active master | Add FB125 call to OB86 on both CPUs; H link-up propagates the call |
| ET 200M goes into station failure in BF (bus fault) LED but process values keep updating on the HMI | Stale data displayed from a DB mirror that is not refreshed | DB transfer or process-image update logic | Invalidate the mirror DB on OB86; refresh the mirror on OB1 only with VALID bit set |
| FC125 used but slot number required | FC125 does not decode slot routing | Block type in the program | Replace with FB125; the slot decoding is the FB's purpose |
| Diagnostics flood WinCC with one event per channel during a single fault | No debounce / aggregation in the message system | WinCC message configuration | Aggregate per-slot and per-second in WinCC; show first/last event time |
Parameter Checklist (Print and Tape Inside the Cabinet Door)
- DP master interface: X1 of CPU 417-4H, PROFIBUS DP, baud 1.5 Mbit/s unless long trunks require 187.5 kbit/s.
- Bus terminators: ON at both physical ends, OFF on all intermediate stations. Use active RS-485 terminator element 6ES7972-0DA00-0AA0.
- IM 153-2 PROFIBUS address: unique, set with DIL switch on the module, must match HW Config.
- Diagnostic address: in slot 0 of the IM 153-2 properties; record the value in the HMI tag list.
- Watchdog: 100 ms default; increase to 300 ms for noisy plants, never above the process-safety limit.
- Slot routing: enabled (required for FB125).
- Module replacement during operation: enabled (operator-friendly, recommended).
- Response monitoring: ON unless process-safety review authorizes OFF.
Frequently Asked Questions
What is the difference between FC125 and FB125 for ET 200M diagnostics?
FC125 reads the standard PROFIBUS DP diagnostic frame of a slave and decodes the station-level state, but it does not resolve which slot in an ET 200M rack caused the event. FB125 adds slot-level decoding using the slot routing mechanism of the IM 153-2, returning slot number, module type, channel number, and channel error code. Use FB125 whenever a plant must point the operator to a specific module.
Do I need to call FB125 in OB82, OB86, and OB1?
Yes. Each of those OBs receives a different subset of the PROFIBUS state machine: OB1 is the cyclic polling context, OB82 handles module diagnostic interrupts (analog faults, wire break, hot-swap), and OB86 handles station come/go events. Missing any of them leaves FB125 with a partial picture and the NEW_DIAG output will not latch every transition.
Why does OB86 on a CPU 417-4H fire with event W#16#3904?
W#16#3904 is the H-system master-master changeover event, raised when the standby CPU takes over DP communication. In OB86, copy OB86_RESERVED_1 into FB125 so it can re-initialize the diagnostic image after failover. Without that step, the new active master inherits a stale DB125 with events from the pre-failover period.
How do I detect a module in a redundant ET 200M pair behind a Y-Link?
Configure the Y-Link (6ES7197-1LB00-0XA0) as a single DP station with a unique diagnostic address. Inside the Y-Link, the two ET 200M sub-racks appear as sub-slots. Enable slot routing in HW Config on both IM 153-2 sub-stations and call FB125 with the Y-Link's diagnostic address; FB125 will resolve the sub-slot of the faulted module. Verify the sub-slot mapping against the Y-Link manual because it differs from a directly-addressed ET 200M.
Can I rely on the standby CPU to log diagnostics in an S7-400H system?
No. The standby CPU does not run the user program (only the master does), so OB82 and OB86 do not fire on the standby side. In an H system, install FB125 on the active master only and ensure the new active master re-initializes DB125 after a master-master changeover; otherwise, diagnostic events from the pre-failover period appear in your message system as if they were current.