Problem Definition: Why DB Re-Initialization Is a Concern on a Running Machine
On a live S7-1200 or S7-1500 CPU, an unintended transition from RUN to STOP during a download causes the process to halt, outputs to drop, and any data block values that are not retentive to be re-initialized to the initial values declared in the offline project. For a packaging line, a bottling skid, a furnace temperature controller, or any continuous process, that translates directly into scrapped product, lost throughput, and a process engineer standing at the panel asking why the system just went down.
The most common trigger is a documentation-only change — adding, editing, or deleting a comment on a tag in a PLC tag table, on a tag inside a global DB, on a network title, or on a block header. In the offline engineering tool, these look like harmless edits. In the CPU's change-tracking logic, they are compiled into a project delta that is compared against the online project. If the change check determines that the delta affects anything other than pure comments, the CPU is forced to STOP to re-initialize the affected blocks and reload them.
The good news: TIA Portal and the S7-1200/S7-1500 firmware explicitly support comment-only downloads in RUN. The bad news: there is one major exception — comments inside the device and network configuration of the hardware (HW Config) — and several edge cases that engineers trip over in the field. The remainder of this article walks through what is safe, what is not, and the exact procedure to perform a comment-only download in RUN without re-initializing any data blocks.
How TIA Portal Decides Between RUN and STOP
When you click Download to device, TIA Portal performs a consistency check against the CPU's current online content. The result of this check determines the operating mode transition. The decision tree is summarized in the SVG flowchart below.
The classification table that the S7-1200/S7-1500 firmware uses internally is shown below.
| Change Class | CPU Operating Mode During Download | DB Re-Initialization |
|---|---|---|
| Tag comment added or modified (PLC tags, DB tags) | Stays in RUN | No |
| Block comment / title / version / author | Stays in RUN | No |
| Network title / network comment in FBD or LAD | Stays in RUN | No |
| User constant comment inside a UDT | Stays in RUN | No |
| UDT element comment (no rename, no type change) | Stays in RUN | No |
| Tag name change (rename, not just comment) | CPU goes to STOP, block re-initialized | Yes (values revert to declared initial values) |
| Data type change of an existing tag | CPU goes to STOP, block re-initialized | Yes |
| Insert / delete of a tag inside an existing DB | CPU goes to STOP, block re-initialized | Yes |
| Change to the retentivity attribute of a tag | CPU goes to STOP, block re-initialized | Yes |
| Any change in Devices & Networks (HW Config), including a device comment | CPU goes to STOP, hardware re-initialized | Yes (full hardware restart) |
| Topology view edit (device name, port assignment) | CPU goes to STOP, hardware re-initialized | Yes |
The S7-1200 supports downloads in RUN from firmware V4.0 onward (article group 6ES721x-1xxxxx-xxxx). The S7-1500 supports it from the first shipped firmware version (V1.0+). The official Siemens support FAQ titled "Downloading blocks in the 'RUN' operating mode to the device" documents the supported change classes and is the authoritative reference for the rules above. For TIA Portal project engineering context, refer to the TIA Portal V18/V19 documentation on the Siemens Industry Online Support portal.
The Hardware Configuration Exception
STOP download. The CPU performs a hardware re-initialization, and any non-retentive DBs are reset to their initial values.
The reason is that the hardware configuration is treated as a single compiled object. The online/offline diff does not look inside the HW Config object to determine whether a sub-element is a comment or a topology change. From the CPU's perspective, an HW Config download is an atomic event that requires a controlled re-initialization of the module addressing tables and PROFINET/PROFIBUS device lists.
Practical implication: if you are working on a live machine and want to add documentation to a tag, do not add that documentation inside the Devices & Networks editor. Add the comment in the PLC tag table, the DB tag declaration, or the watch table — these are the safe locations for RUN-mode downloads.
Retentive vs. Non-Retentive: What Survives a STOP Even When You Get It Wrong
Even if a download does force a STOP transition, tags marked with the Retain attribute retain their last-written values across the stop/start cycle. The at-risk tags are those without the Retain attribute — they are reset to the Initial value declared in the offline DB declaration.
| Tag Class | Behavior on STOP Transition | Behavior on Successful RUN-Mode Comment Download |
|---|---|---|
| Retentive static tag (Retain = true) | Value preserved across STOP/start | Value preserved; comment is updated in CPU |
| Non-retentive static tag (Retain = false) | Value reset to declared initial value | Value preserved; comment is updated in CPU |
| Input / Output / InOut parameter of a global DB | Reset to initial value | Value preserved; comment is updated in CPU |
| Temp tag (lifetime = single scan) | Reset to 0 / declared initial value | Reset on next scan; not a persistent state |
The default setting in TIA Portal for new tags is Retain = false. Engineers frequently rely on this default without realizing that a STOP transition will reset their counters, setpoint registers, and state-machine flags. Verify the retentivity assignments of the tags most critical to your process before performing any online download to a live machine.
Firmware and Software Prerequisites
Confirm the following prerequisites before attempting a comment-only download in RUN:
- CPU firmware: S7-1200 must be at firmware V4.0 or higher. The order number group 6ES721x-1xxxxx-xxxx covers all variants. Check the firmware version in Online & Diagnostics → Diagnostics → CPU information or on the CPU's display. S7-1500 supports RUN-mode downloads from all shipped firmware versions (V1.0+).
- Failsafe CPU consideration: On a failsafe CPU (S7-1200F, S7-1500F), comment-only downloads are still permitted, but the failsafe program signature is recomputed. Safety mode is not affected as long as no program logic changes. The safety-related change log inside the CPU's diagnostic buffer records every signature change for audit purposes.
- TIA Portal version: TIA Portal V13 SP1 or higher is required for the full RUN-mode download feature set on S7-1200. TIA Portal V14 or higher is recommended for S7-1500. The current engineering tool is TIA Portal V18 / V19. Older TIA Portal versions can read the project but the Download in RUN option may be greyed out.
-
Online connection: PROFINET, PROFIBUS, or Ethernet — any online path supported by TIA Portal works. The CPU does not need to be put into a special state; the active
RUNmode is sufficient. - Project consistency: The offline project must compile without errors. The download will be refused if the project is dirty or has unresolved references.
- Project ↔ CPU binding: Verify the offline project is bound to the correct CPU by right-clicking the device node and selecting Go online → .... A common field error is downloading a project compiled against one CPU's serial number to a different physical CPU. TIA Portal will warn, but the warning can be overridden in the field.
Pre-Download Checklist
- Open the project in TIA Portal and perform Project → Compile → All (rebuild). Resolve any compiler errors. Comments are not validated as code, so a comment typo will not cause a compile error — but a typo in a tag name that you intended to add as a new tag will.
- Open Project tree → PLC → PLC tags and add the new comment to the relevant tag row. The comment column is the rightmost column in the tag table; if it is hidden, right-click the column header and select Show/Hide columns and enable Comment.
- For DBs, open the DB in the project tree, double-click the Static section header, and edit the comment column on the target tag.
- Save the project. TIA Portal will update the comment in the offline project. The CPU still shows the old comment until you download.
- Click Go online in the toolbar. Confirm the online connection to the target CPU. Do not use the Online → Accessible nodes shortcut for the first connection — use the project tree right-click → Go online → Secure online connection (or plain online) to ensure the right CPU is selected.
- Sanity-check the change set by going Online → Compare offline/online. The comparison must show comment changes only, with no interface or code deltas flagged.
Step-by-Step: Performing the Comment-Only Download in RUN
- Right-click the PLC node in the project tree (not the device) and select Download to device → Software (only changes). The phrase only changes is the critical selection — this tells TIA Portal to compute a delta and download only the changed blocks.
If you choose Download to device → Hardware and software, TIA Portal will attempt to re-flash the device configuration and force a
STOPtransition. Use this only for full configurations, not for documentation updates. - TIA Portal performs the consistency check and displays a preview dialog listing the blocks that will be downloaded. Verify that the listed blocks are exactly the ones you edited comments in. A typical comment-only download list looks like:
DB_Recipe (DB100) - comment header updated PLC_Tags - default tag table, comments modified No code change, no interface change - Confirm the dialog. TIA Portal asks for the operating mode fallback. The default option is Download in RUN if possible, otherwise STOP. Keep this default. The CPU will stay in
RUNbecause the change class is comment-only. - Click Download. The transfer takes 1–3 seconds per block depending on block size. The CPU does not stop; the
RUNLED remains solid green. - After download, the load preview dialog closes and a status message confirms Download (RUN) finished, no errors. The online view of the block now shows the new comment.
- Perform an Online → Compare offline/online check to confirm the offline project matches the online CPU.
- Open Online → Online & Diagnostics → Diagnostic buffer and confirm a Download of changes in RUN entry with the current timestamp and no STOP entry with the same timestamp.
Symbolic Comments, Network Comments, and Block Comments — All Safe in RUN
The following comment locations are all classified as comment-only changes by the S7-1200/S7-1500 change-check logic and will not force a STOP:
- PLC tag table comments: the rightmost column on the default tag table, on user-defined tag tables, and on the system tag tables for the CPU's own special functions (high-speed counters, pulse outputs, etc.).
- DB tag comments: the comment column on the Input, Output, InOut, Static, and Temp sections of a global DB or instance DB.
- UDT (user-defined data type) comments: the header comment and per-element comments inside a UDT are comment-only. Renaming a UDT element, however, propagates to every DB that uses the UDT and forces a STOP.
- Block header / title / version / author / family comments: the block properties dialog's General tab and the Information tab.
- Network title and network comment: in FBD and LAD editors, the small comment box on the right of each network.
- Function (FC) and function block (FB) interface comments: the comment column on the Input, Output, InOut, Static, and Temp sections of the block interface declaration.
- Watch table comments: the comment column in a watch table is stored in the offline project only, not the CPU, and is therefore a local edit with no download required.
Verifying That the CPU Did Not Re-Initialize
After a comment-only download in RUN, perform the following checks to confirm the system state is preserved:
-
Operating mode LED: The
RUNLED on the CPU remains solid green. If the LED drops toSTOP(yellow) or blinks (stop with error), the change was not comment-only and the CPU re-initialized. - Diagnostic buffer: Open Online → Online & Diagnostics → Diagnostic buffer. Look for an entry of class Download with text "Download of changes in RUN". There should be no entry of class STOP or Re-initialization with a timestamp matching the download.
- DB values: Open the affected DB in the project tree, right-click → Monitor/Modify, and verify that the actual values match the values you expect from the running process. Non-retentive tags should retain their last-written values because no re-initialization occurred.
- Retentive tag sanity: If your DB uses the Retain attribute on specific tags, those tags will survive a STOP transition anyway. The non-retentive tags are the ones at risk — check those first.
- Process status: Confirm with the operator that the controlled process did not drop out. If the process is automated and you cannot query the operator, check the HMI trend logs for the timestamp of the download; a one-cycle or several-cycle gap indicates a process interruption.
- Online/offline block signature: In the project tree, the block's online/offline comparison icon should be a green check after a successful comment download. A yellow triangle or red cross indicates a deeper mismatch.
Troubleshooting Matrix: When the Download Drops to STOP
| Symptom | Likely Cause | Diagnostic Step | Corrective Action |
|---|---|---|---|
| CPU goes to STOP during download; diagnostic buffer shows Download in STOP, re-initialization | An HW Config change was bundled with the comment change | Open the load preview dialog; check if any device or sub-module is in the list | Ungroup the HW Config change into a separate maintenance window, or use Download to device → Software (only changes) after reverting HW Config edits |
| CPU goes to STOP; diagnostic buffer shows DB re-initialization for a specific DB | A tag was renamed, added, deleted, or had its data type changed | Open the DB and compare the tag list to the version that was last successfully downloaded | Restore the original tag declarations, or schedule a controlled stop for the tag interface change |
| Download in RUN rejected with error "The block is locked by a different action" | Another TIA Portal session is online with the same CPU, or a Webserver session is open on the CPU | Check active online sessions; close the Webserver if it is editing the same CPU | Re-attempt the download after the other session releases the lock |
| Download in RUN rejected with "Insufficient work memory" | CPU is at memory limit; comment metadata pushes block over the limit | Check the CPU's Memory tab in Online & Diagnostics | Archive and remove unused DBs or blocks, or upgrade the CPU's memory card (SIMATIC Memory Card) |
| Comment change not visible online after a "successful" RUN download | Comment was edited in a local project copy, not the project bound to the CPU | Verify the project name and CPU binding under Project → Properties → Protection | Re-edit the comment in the bound project, recompile, and re-download |
| RUN-mode download refuses to start; prompt asks for STOP permission every time | TIA Portal's Download in RUN setting is disabled in the project options | Open Options → Settings → Online & Diagnostics → Download in RUN | Enable the option Allow download in RUN; recompile and retry |
| Comment-only download succeeds but operator reports a process blip one scan later | A retentive tag was touched by the comment change because the tag's metadata was rebuilt | Open Online & Diagnostics → Memory and inspect the DB's start address and length | If the issue persists, schedule a controlled STOP and download the comment in the same maintenance window |
| S7-1200 displays SF (system fault) LED after a comment download | Firmware older than V4.0 does not support RUN-mode downloads and has interpreted the comment change as a block change | Check the firmware version under Online & Diagnostics → CPU information | Update the S7-1200 firmware to V4.0 or higher using the SIMATIC Automation Tool or TIA Portal's Online → Firmware update |
Best Practices for Live-Machine Documentation Updates
- Always perform a change-only download: from the project tree's PLC node, choose Download to device → Software (only changes). Avoid the hardware-and-software option for any work performed on a live CPU.
- Document in the tag table, not in the watch table: a watch-table comment lives only in your offline project; a tag-table comment lives in the CPU after download. If you want the comment visible to anyone else who later opens the project, put it in the tag table.
- Avoid bundling comments with structural changes: if you need to rename a tag and also fix its comment, do it in two separate downloads. Add the comment in RUN first; then schedule a maintenance window to perform the rename in a controlled STOP.
- Use block comments for cross-reference: a single block-level comment in the DB header explaining the purpose of the block is more valuable to the next maintainer than per-tag comments and is also less likely to require future edits.
- Keep a comment-only change log: in the project tree, use the Project history feature to record the date, author, and purpose of every comment-only change. This is invaluable during audits and during post-incident analysis if a process stop does occur.
- Verify after every download: always inspect the diagnostic buffer immediately after a RUN-mode download. The presence of a Download of changes in RUN entry with the current timestamp, and the absence of any STOP entry with the same timestamp, confirms that the change was comment-only.
- Use secure online connections: when downloading to a CPU on a production network, use the secure online connection option in TIA Portal. The secure connection does not affect whether the comment downloads in RUN; it only protects the integrity of the transfer.
- Backup before the first download: take an online snapshot of the CPU (Online → Snapshot of the online data) before the first comment download. If anything goes wrong, the snapshot lets you restore the CPU to its exact pre-download state.
Related RUN-Mode Considerations
Comment-only downloads are the simplest case of in-process online editing. The same change-check framework also supports the following operations in RUN:
-
Function block instance initial values: changes to the Initial value column of a static tag inside an FB can be downloaded in
RUNas long as the tag type is unchanged. The actual instance values are not affected. - Code-block online editing: TIA Portal supports Edit online for FCs and FBs. The change-check rules for online edits are stricter than for comments, but they are also documented in the Siemens RUN-mode download FAQ.
- Recipe DB regeneration: regenerating a recipe DB from its UDT requires STOP. Plan the recipe schema change for a maintenance window. Recipe data values inside an unchanged UDT can be edited and downloaded in RUN as a comment-only change to the DB.
- Watch table: a watch table is a local engineering artifact, not stored on the CPU. Comments in a watch table are personal notes and require no download.
FAQ
Which firmware versions of the S7-1200 support downloading tag comments in RUN mode without DB re-initialization?
Firmware V4.0 or higher is required on the S7-1200. All S7-1500 firmware versions (V1.0+) support the feature. The S7-1200 V4.0 release was the first to bundle the change-check logic that classifies comment-only edits as RUN-safe. On older S7-1200 firmware, the CPU drops to STOP and reports a system fault on the SF LED after a comment download attempt.
Do I need to put the CPU in STOP to download a comment change to a global DB?
No. A comment change to a tag inside the Static, Input, Output, or InOut section of a global DB is a comment-only edit. Use Download to device → Software (only changes) from the PLC node. The CPU stays in RUN, and the DB is not re-initialized. Renaming, adding, deleting, or changing the data type of a tag is not a comment-only edit and does require a STOP.
Can I add a comment to a tag inside the Devices & Networks editor without stopping the CPU?
No. The Devices & Networks editor handles comments as part of the hardware configuration. TIA Portal treats any change to HW Config — including a comment — as a hardware download, which forces a CPU STOP and a hardware re-initialization. Add your tag comments in the PLC tag table or the DB tag table instead, which are the safe locations for RUN-mode downloads.
What entry should I look for in the diagnostic buffer after a successful comment download in RUN?
Look for an entry of class Download with the text "Download of changes in RUN" and a timestamp matching the download you just performed. The absence of any STOP or Re-initialization entry with the same timestamp confirms that the CPU did not transition and the DBs were preserved. If a STOP entry exists, the change was not comment-only and the operator must be informed.
Does editing a watch-table comment require a download to the CPU?
No. Watch-table comments are stored in the offline project on the engineering station only. They are not part of the CPU's online project and require no download. Watch-table comments are useful as personal notes but are not visible to another engineer who opens the project on a different engineering station. For comments that must travel with the project, use the PLC tag table or the DB tag table.
Are retentive tags safe even if a comment download accidentally forces a STOP?
Yes. Tags with the Retain attribute keep their last-written values across a STOP/start transition. Non-retentive tags are reset to the initial values declared in the offline DB. The risk surface for a comment download that goes wrong is the non-retentive tag set: counters, setpoint registers, state-machine flags, recipe selections, and operator-entered values that were not explicitly marked as Retain.