Downloading STEP 7 Micro/WIN SMART v2.7 for S7-200 SMART PLCs
STEP 7 Micro/WIN SMART is the dedicated programming and configuration software for the SIMATIC S7-200 SMART compact PLC family. Unlike the legacy STEP 7 Micro/WIN V4.0 used for the original S7-200, the SMART variant is engineered for the Ethernet-equipped S7-200 SMART CPUs (SR/ST series) and is distributed primarily through Siemens regional channels in Asia. This guide consolidates the official acquisition path, system prerequisites, version mapping, and first-connection commissioning procedure for engineers who need a clean, working install of STEP 7 Micro/WIN SMART V2.7.
1. Product Overview
STEP 7 Micro/WIN SMART provides a full IEC 61131-3 programming environment tailored to the cost-optimized S7-200 SMART platform. It supports the standard ladder logic (LAD), statement list (STL), and function block diagram (FBD) editors, plus the SMART-specific wizards for high-speed counters, PTO motion, PID loops, and recipe handling.
| Attribute | Specification |
|---|---|
| Product name | STEP 7 Micro/WIN SMART |
| Target hardware | SIMATIC S7-200 SMART (SR20/SR30/SR40/SR60, ST20/ST30/ST40/ST60) |
| Latest publicly indexed build | V2.7 |
| Earlier indexed builds | V2.3, V2.4, V2.5, V2.6 |
| Connection to PLC | Ethernet (TCP/IP), RS-485 (PPI/Freeport via CM01 signal board) |
| Project file extension | *.smart (project), *.mwp (legacy Micro/WIN import) |
| Primary regional availability | South-East Asia, India, China, Latin America distribution channels |
For the legacy S7-200 (CPU 21x, CPU 22x, CPU 224XP, CPU 226), the correct tool remains STEP 7 Micro/WIN V4.0 SP9, distributed under Siemens support entry 58523240 – STEP 7 Micro/WIN V4.0 SP8 and SP9. Do not substitute the SMART build for legacy CPU programming.
2. Prerequisites
Before downloading, confirm the engineering workstation meets the supported environment. The V2.7 release is the last publicly distributed build that retains Windows 7 SP1 compatibility; later internal builds assume Windows 10/11.
| Component | Minimum / Recommended |
|---|---|
| Operating system | Windows 7 SP1 (32/64-bit), Windows 10 (64-bit, 1809 or later) |
| CPU | Intel Core i3 (2nd gen) or equivalent; i5 recommended for large projects |
| RAM | 4 GB minimum, 8 GB recommended |
| Disk space | 2.5 GB free for installation; SSD recommended |
| Display | 1366 × 768 minimum; 1920 × 1080 recommended for ladder editing |
| Ethernet | 10/100 Mbps NIC for direct-to-CPU programming |
| Framework | .NET Framework 4.6.2 or higher |
| Administrator rights | Required for install and for the SMART Ethernet driver service |
3. Supported S7-200 SMART CPUs
Micro/WIN SMART V2.7 maintains forward compatibility with every S7-200 SMART CPU released to date, including the relay-output (SR) and transistor-output (ST) variants. Use the article numbers below to verify spare-part ordering against your installed base.
| CPU model | Article number | I/O count | Output type | Ethernet ports |
|---|---|---|---|---|
| SR20 | 6ES7288-1SR20-0AA1 | 12 DI / 8 DO | Relay | 1 (RJ45) |
| SR30 | 6ES7288-1SR30-0AA1 | 18 DI / 12 DO | Relay | 1 (RJ45) |
| SR40 | 6ES7288-1SR40-0AA1 | 24 DI / 16 DO | Relay | 1 (RJ45) |
| SR60 | 6ES7288-1SR60-0AA1 | 36 DI / 24 DO | Relay | 1 (RJ45) |
| ST20 | 6ES7288-1ST20-0AA1 | 12 DI / 8 DO | Transistor (source) | 1 (RJ45) |
| ST30 | 6ES7288-1ST30-0AA1 | 18 DI / 12 DO | Transistor (source) | 1 (RJ45) |
| ST40 | 6ES7288-1ST40-0AA1 | 24 DI / 16 DO | Transistor (source) | 1 (RJ45) |
| ST60 | 6ES7288-1ST60-0AA1 | 36 DI / 24 DO | Transistor (source) | 1 (RJ45) |
4. Official Download Procedure
STEP 7 Micro/WIN SMART is distributed by Siemens regional organizations because the S7-200 SMART line is positioned as a value-platform for cost-sensitive applications. For engineers in India and surrounding regions, the canonical acquisition point is the Siemens India product page linked from Siemens India – STEP 7 Micro/WIN SMART. Engineers outside this region should request the package from the local Siemens Industry Online Support representative, who can transfer the installer package plus the matching service pack.
4.1 Step-by-step download
- Open the Siemens India S7-200 SMART product portal: new.siemens.com/in/en/products/automation/systems/industrial/plc/simatic-s7-200-smart/step7-micro-win-smart.html.
- Scroll to the Software & Downloads section and select the Micro/WIN SMART entry.
- Choose the V2.7 build (the highest publicly indexed release). Earlier builds (V2.5, V2.6) are retained for engineers who must match a project previously archived on an older toolchain.
- Register or sign in with a Siemens Industry Online Support account when prompted; the download is gated by the same SSO used for the global SIOS portal.
- Download the self-extracting installer (filename typically
MicroWinSmart_V27.exe, approximately 1.6 GB). - Verify the SHA-256 checksum against the value listed on the Siemens download page to confirm installer integrity before execution.
- If your local Siemens channel does not host a public download, open a Support Request via the regional contact form and request the "STEP 7 Micro/WIN SMART V2.7 – DVD image" media number.
STEP 7 Micro/WIN SMART V2.7) and the target CPU article number (e.g., 6ES7288-1ST60-0AA1) when contacting the channel.
4.2 Verifying you have the correct package
Before launching the installer, confirm the executable self-identifies as the SMART build:
- Right-click
MicroWinSmart_V27.exe→ Properties → Details. The Product name field must read STEP 7 Micro/WIN SMART. - File size is typically 1.5–1.7 GB. Anything under 400 MB is likely the legacy S7-200 Micro/WIN V4.0 SP9 build, which will not work with S7-200 SMART CPUs.
- The installer launches a splash screen branded SIMATIC S7-200 SMART, not the blue Micro/WIN V4 splash.
5. Installation Procedure
- Close all running Siemens software (TIA Portal, STEP 7 V5.x, Micro/WIN V4.0) to prevent shared-service conflicts.
- Right-click
MicroWinSmart_V27.exeand select Run as administrator. - Accept the license agreement; the SMART toolchain is supplied free of charge for use with S7-200 SMART hardware.
- Select the install path. The default
C:\Program Files (x86)\Siemens\MicroWin Smartis recommended so that the PG/PC interface registry entries resolve correctly. - Choose Typical installation to include the Ethernet driver, the SMART OPC server (for SCADA bridging), and the project documentation export utility.
- When prompted, allow the installer to add an inbound firewall rule for TCP port 102 and UDP port 161 (SNMP optional).
- Reboot when prompted; the SMART Ethernet driver service starts automatically at the next logon.
5.1 Post-install verification
After reboot, confirm the install completed cleanly:
- Start menu entry: Siemens Automation → STEP 7 Micro/WIN SMART V2.7 is present.
- PG/PC interface: Open Control Panel → Set PG/PC Interface. The access point MicroWin SMART → TCPIP.Auto.1 must be listed with the active NIC selected.
-
Service:
services.mscshows SIMATIC MicroWin Smart Ethernet Service in Running state. - Help → About: Reports STEP 7 Micro/WIN SMART V2.7 with a build date. Cross-reference the build date against the Siemens release notes to confirm you are not running a beta that has been superseded.
6. First Project and CPU Connection
Once installed, complete a one-time commissioning handshake to validate end-to-end Ethernet connectivity before loading any production logic.
- Launch STEP 7 Micro/WIN SMART V2.7.
- Open File → New Project. Save it locally; avoid network shares because the SMART compiler writes back intermediate
.bakfiles that can lock on slow links. - From the navigation tree, select CPU → Type and choose the exact CPU model in your panel (e.g., CPU ST60 (6ES7288-1ST60-0AA1)).
- Open Communication → Set PG/PC Interface and verify MicroWin SMART → TCPIP.Auto.1 is bound to the wired Ethernet NIC (not a Wi-Fi adapter if the CPU is on a crossover direct link).
- Click Communication → Find CPUs. The tool broadcasts UDP discovery on the local subnet; the CPU responds with its IP, MAC, and firmware version.
- If the CPU does not appear, assign a static IP via the Communication → Edit Ethernet Parameters dialog to match the CPU's current address (factory default is
192.168.2.1 / 255.255.255.0). - Once discovered, click Flash LED to confirm physical link; the CPU's LINK/ACT LED pulses for 5 seconds.
- Select Upload to read the current program (or Download if you are commissioning a fresh unit).
192.168.2.1, subnet 255.255.255.0. Configure the PG/PC NIC with a static address in the same subnet (192.168.2.10) before the first connection attempt. DHCP is not enabled by default.
7. Version Mapping and Firmware Compatibility
| Micro/WIN SMART version | Earliest firmware supported | Latest firmware supported | Notes |
|---|---|---|---|
| V2.3 | V1.0 | V2.3 | Windows XP/7 baseline; legacy install footprint |
| V2.4 | V2.0 | V2.4 | Added PROFINET configuration basics |
| V2.5 | V2.3 | V2.5 | Improved Web server editor, S7 protocol library updates |
| V2.6 | V2.3 | V2.6 | Added motion wizard extensions, security log export |
| V2.7 | V2.3 | V2.7 (current) | Windows 10/11 signing, expanded symbol export |
Always confirm the CPU firmware with CPU → Information before downloading a project. A downgrade of project features is necessary if the target CPU firmware is older than the build used to compile the offline program; otherwise, expect an SF system fault on first scan.
8. Common Errors and Field Fixes
| Symptom | Likely cause | Remediation |
|---|---|---|
| Installer aborts with Error 1920 – Service failed to start | Conflicting Siemens service on TCP 102 | Stop legacy SIMATIC Net services; rerun installer as Administrator |
| CPU not discovered on Find CPUs | PC NIC on different subnet than CPU | Set PC to 192.168.2.10/24; disable Wi-Fi |
| Download fails with SF + BF LEDs lit on CPU | Firmware mismatch with project compile target | Recompile project for the CPU's actual firmware under CPU → Type |
| PG/PC interface missing from dropdown | Service disabled or NIC changed | Re-run Set PG/PC Interface; re-select the wired NIC |
| STEP 7 Micro/WIN cannot be installed on this OS | Wrong build (legacy V4.0 attempted on S7-200 SMART) | Confirm SMART build via file properties before installing |
| Web server pages return 404 | Web server disabled or wrong port | Enable web server in CPU properties; default port 80 |
9. Troubleshooting Matrix
| Category | Symptom | Diagnostic | Action |
|---|---|---|---|
| Acquisition | No download on regional Siemens site | Check page locale (in/en vs com) | Use the India portal or open a SIOS ticket |
| Install | Service not registered | services.msc lookup | Reinstall with elevated privileges |
| Connectivity | No CPU discovery | ping 192.168.2.1 |
Verify NIC, cable, CPU IP, subnet mask |
| Compile | Build error on motion blocks | Check axis table; ensure PTO mapping | Reassign outputs in Motion Wizard |
| Runtime | CPU in STOP with SF LED | Read diagnostic buffer via CPU → Information | Address fault; recompile and reload |
| Migration | Legacy S7-200 program cannot be opened | File extension is .mwp
|
Open with Micro/WIN V4.0 SP9, export symbols, port manually |
10. Migrating from Legacy STEP 7 Micro/WIN V4.0
Engineers who have an installed base of legacy S7-200 programs in .mwp files cannot open those files directly in Micro/WIN SMART V2.7 because the compiler, instruction set, and memory map differ. Use the two-step migration:
- Open the legacy project in STEP 7 Micro/WIN V4.0 SP9 (SIOS 58523240).
- Use File → Export → Symbol Table (CSV) and File → Export → Data Block to extract tag and DB data.
- In Micro/WIN SMART V2.7, recreate the memory layout manually, observing the SMART memory model:
I/Q/M/Vranges are similar but the process-image size and high-speed counter mapping differ. - Use Tools → Compare with Smart (when available via a project add-in) to flag unsupported instructions such as legacy USS and MODBUS library blocks that require the SMART-specific libraries.
11. Field Commissioning Checklist
- Confirm Micro/WIN SMART V2.7 installed and licensed (no license key required for the SMART build).
- Verify PG/PC interface points to the wired Ethernet NIC.
- PC static IP set within the CPU subnet (
192.168.2.x / 24). - CPU firmware matches the project compile target.
- Firewall allows outbound TCP 102 and inbound UDP discovery.
- One backup copy of the offline
.smartproject archived to the engineering repository.
12. Frequently Asked Questions
Where can I download STEP 7 Micro/WIN SMART V2.7?
The official distribution point for the S7-200 SMART toolchain is the Siemens India product portal at new.siemens.com/in/en/products/automation/systems/industrial/plc/simatic-s7-200-smart/step7-micro-win-smart.html. If your region does not expose a direct link, request the V2.7 DVD image from your local Siemens Industry Online Support representative, quoting article number 6ES7288-1ST60-0AA1 (or your specific CPU) for context.
Can I use STEP 7 Micro/WIN V4.0 SP9 with an S7-200 SMART CPU?
No. STEP 7 Micro/WIN V4.0 SP8/SP9 (SIOS 58523240) is the legacy tool for the original S7-200 family (CPU 21x/22x) and uses PPI over RS-485 or USB. S7-200 SMART CPUs only accept the Micro/WIN SMART toolchain over Ethernet on TCP port 102.
Is STEP 7 Micro/WIN SMART V2.7 free to download?
Yes. The SMART toolchain is supplied free of charge for use with S7-200 SMART hardware. Registration with the Siemens Industry Online Support portal may be required to receive the download link from the regional channel.
Which Windows versions does Micro/WIN SMART V2.7 support?
V2.7 supports Windows 7 SP1 (32/64-bit) and Windows 10 (64-bit, version 1809 or later). For Windows 11, install the tool in Windows 10 compatibility mode and confirm the Ethernet driver service starts under the newer network stack.
Why does Find CPUs not detect my ST60 (6ES7288-1ST60-0AA1)?
Three checks resolve 90 percent of discovery failures: (1) confirm the PC NIC has a static IP in the 192.168.2.x/24 subnet, (2) disable Wi-Fi so the PG/PC interface does not bind to a wireless adapter, and (3) allow the SIMATIC MicroWin Smart Ethernet Service through the Windows firewall for private networks. If discovery still fails, ping the CPU's default IP 192.168.2.1 to confirm physical link.
Can I open a legacy .mwp project from S7-200 directly in V2.7?
No. .mwp files must be opened in Micro/WIN V4.0 SP9 first, then exported (symbols, DBs) before manual reconstruction in Micro/WIN SMART V2.7. Communication blocks (USS, MODBUS, NETR/NETW) must be re-bound to the SMART Ethernet instructions because the underlying transport changed from PPI/RS-485 to TCP/IP.
What is the default IP address of a new S7-200 SMART CPU?
Factory default IP is 192.168.2.1 with subnet mask 255.255.255.0, gateway 0.0.0.0. The CPU does not enable DHCP by default; configure both the CPU and the engineering PC with static addresses on the same subnet before the first connection.