Overview
The SINUMERIK 828D CNC is a panel-based controller whose functional scope is shaped almost entirely by software options. Hardware alone determines only the upper mechanical ceiling; every additional axis, spindle, technology cycle, and machining step is unlocked by a license key that is bound to the serial number of the CompactFlash Card (CF card) installed in the Panel Processing Unit (PPU). This article covers the two option part numbers most commonly shipped with an 828D Basic T Horizontal machine package, PPU 241.2:
- 6FC5800-0AC20-0YB0 — Controllable interpolation axes, extension (1 additional axis / 1 additional spindle)
- 6FC5800-0AP58-0YB0 — Advanced Technology Functions (extended milling/turning/drilling cycles)
Both articles are delivered on paper. The paper document carries a license key string that must be entered once into the controller (or reloaded from CF card) before the option becomes operative. If the option is referenced in machine data but the license is missing, the control raises the alarm "Option activated without license" and refuses to traverse the affected axis or execute the affected cycle.
The intended audience is the commissioning engineer or service technician who has just received a fresh 828D shipment, has mechanically and electrically installed the PPU, and is preparing the controller for the first power-up.
Hardware Context: PPU 241.2 Basic T Horizontal
The PPU 241.2 is a horizontal-mount, 10.4" TFT variant of the 828D operator panel. It integrates the CNC kernel, the SINAMICS S120 drive-clique line modules, and the I/O backplane into a single housing. According to the SINUMERIK 828D brochure, the 828D family is positioned for compact milling and turning machines; the "Basic T" suffix indicates the standard turning software set without the SWD (ShopTurn / ShopMill) graphical programming environment.
The default axis count of a PPU 241.2 is determined by the order code but is typically four interpolating axes plus one spindle. To add a fifth axis (commonly a C-axis on a driven tool turret, a sub-spindle, or a secondary linear axis) the 0AC20 option must be present. Without it, MD30350 $MA_IS_ROT_AX and the related configuration machine data for the extra axis are rejected at startup, and the channel will not come ready.
Decoding the Two Option Part Numbers
| Field | 6FC5800-0AC20-0YB0 | 6FC5800-0AP58-0YB0 |
|---|---|---|
| Article number prefix (6FC5800) | SINUMERIK 828D software option catalog | |
| Option code | 0AC20 | 0AP58 |
| Function | 1 additional controllable axis / spindle | Advanced Technology Functions |
| Delivery form suffix (…-0YB0) | Paper license (Certificate of License) | Paper license (Certificate of License) |
| License binding | Bound to CF card serial number | Bound to CF card serial number |
| Reactivation on replacement CF | Possible via Web License Manager | Possible via Web License Manager |
The trailing -0YB0 is critical. It tells the order entry system that the entitlement is to be issued as a printed Certificate of License (CoL), not preloaded onto the CF card at the factory. Engineers who see a different trailing suffix should treat the procedure differently: -0YB0 = manual entry, -0YB1 = CoL with the same content but a different export-control classification, and the absence of a Y-suffix usually indicates the option is already burned into the card at shipment.
6FC5800-0AC20-0YB0 — Additional 1 Axis / 1 Spindle
This option extends the maximum number of configurable axes or spindles by one. On a turning package, the most common use cases are:
- Adding a counter-spindle (axis name
SP2orCS) for part pickup on subspindle lathes. - Adding a driven-tool C-axis (axis name
C) on a milling-turning centre with live tooling. - Adding a second independent linear axis such as a tailstock (
TX) or a steady rest (SX). - Adding a Y-axis on a mill where the basic configuration only supports X, Z, and the spindle.
The option is consumed per additional axis. If the machine requires two extra axes (for example, a Y-axis and a counter-spindle), two CoLs are required, or the higher-capacity option 6FC5800-0AC21-0YB0 (two additional axes) is purchased. The 0AC20 part number is a single-credit license.
6FC5800-0AP58-0YB0 — Advanced Technology Functions
The Advanced Technology option is a bundled cycle library that extends the standard technology set. The 828D Basic T already includes a baseline set of cycles for turning (CYCLE95, CYCLE97, CYCLE98) and drilling (CYCLE81 through CYCLE89); the AP58 option adds productivity-oriented cycles that shorten programming time and improve surface finish. The category groups offered with the option include:
| Category | Representative cycles | Typical use |
|---|---|---|
| Milling cycles (extended) | Pocket cycles with islands, trochoidal milling, residual-material recognition | Reduce air cutting on prismatic parts |
| Turning cycles (extended) | Grooving with relief, contour turning with multiple plunges, undercut support | Eliminate hand-written grooving macros |
| Drilling cycles (extended) | Deep-hole drilling with chip-breaking, tapping with compensating chuck, boring with retraction | Replace ISO-code drilling blocks |
| Multi-channel support | Synchronised spindle movements, multi-channel blank programs | Required for mill-turn machines with the counter-spindle |
The AP58 option is consumed once per control. It does not stack — a second CoL does not add a second copy of the cycles. The 828D differentiates "not licensed" from "licensed but disabled" at the cycle level using a softkey tree under Setup > Etc > Licenses.
License Format and Paper-Delivery Decoding
A paper CoL contains four machine-readable fields plus a tamper-evident holographic sticker. The four fields are:
-
License number — a 30-character alphanumeric string in the form
XXXX-XXXX-XXXX-XXXX-XXXX-XXXX-XXXX. - CF card serial number — the unique 12-character identifier that the license is bound to. The value must match the serial number of the CF card physically installed in the PPU; if the card is later replaced, the license must be reissued.
-
Option code — the four-character designator (e.g.,
AC20orAP58). - Signature hash — a checksum that the controller validates before accepting the key.
Paper delivery is mandatory in regions where the import or export of cryptographic key material is regulated, or where end customers demand an auditable chain of custody for licensed software. Siemens is moving the bulk of new shipments to electronic delivery (the Web License Manager at www.siemens.com/automation/license), but the two options covered here are typically ordered on paper for the Asian and Indian machine-tool OEM market.
Prerequisites for Activation
- The 828D PPU 241.2 has been mechanically mounted and the 24 V DC logic supply is on, with no field wiring faults present on SINAMICS DRIVE-CLiQ.
- The CF card is the original Siemens part with the 828D firmware image. Aftermarket CF cards cause licensing to fail at signature validation.
- Access level Manufacturer (password-protected) is available. The licenses softkey is only visible at Manufacturer or Service level.
- The paper CoL is in hand and the CF card serial number printed on it matches the controller being commissioned.
- The firmware version on the CF card supports the option. AP58 requires SW 4.5 SP2 or later; AC20 is supported on every shipping 828D firmware from SW 4.4 onward.
Step-by-Step Activation Procedure
The procedure is the same for both options and uses the controller's own HMI; no external programming tool is required.
- Power up the PPU and wait for the standard operator screen to appear. Press the Setup area key on the horizontal softkey bar (second key from the left on PPU 241.2).
- Press the Etc key ( > ) at the right end of the softkey bar to switch to the second softkey page.
- Press the Licenses softkey. The control opens the license overview, which lists every option slot, the option code, the current state, and the available license count.
- Press the Set option according to license softkey. The control displays a prompt asking whether all options contained on the CoL should be activated. Confirm with OK.
- Alternatively, place the cursor on the row corresponding to the single option you wish to enable (for example, the row labelled
AC20) and press the Set softkey. Enter the license number from the CoL, confirm with OK, and the option transitions from not licensed to licensed. - Cycle 24 V DC power on the PPU. Many of the option bits are sampled only at cold start; a hot activation will be accepted but the affected axis will not come ready until the next reboot.
- After reboot, return to
Setup > Etc > Licensesand verify the state column now reads set for both options.
Verification: Confirming the License is Active
After reboot, the license state can be read from three independent sources. Cross-checking all three catches the case where a single HMI page is showing cached data.
-
HMI license overview. Navigate to
Setup > Etc > Licenses. Each option row carries a status column; set means active, not set means licensed but disabled, not licensed means absent. -
Machine data query. Read
MD19610 $ON_TECHNO_FUNCTION_MASKfor AP58, and the axis-specific machine dataMD30350 $MA_IS_ROT_AX,MD30300 $MA_IS_ROT_AX, and the channel-specificMD20070 $MC_AXCONF_MACHAX_USEDfor AC20. A non-zero value that the control accepted at startup indicates the option bit is set. - Alarm log. With the option set, the alarm "Option activated without license" (alarm 8022) must be absent from the clearable alarm list on the alarm screen.
DOCON WEB Reference
Engineers who need the canonical Siemens documentation for the license procedure can look up the relevant operator-component manual on the official Siemens documentation portal. The SINUMERIK 828D brochure confirms the part numbering scheme and the option taxonomy, while the Operator Components and Programming Manual (document number 6FC5398-8BP40) covers the softkey navigation shown above. Always cross-check the manual revision against the SW version of your CF card — Siemens frequently re-screenshots menus across major releases.
Machine Data Considerations
Setting the license is necessary but not sufficient. The axis or cycle must also be referenced in machine data, otherwise the controller will report the option as licensed but the spindle / axis / cycle will still be invisible. The minimum machine data set to review is:
| MD number | Name | Used by | Typical value |
|---|---|---|---|
| MD10000 $MN_AXCONF_MACHAX_NAME_TAB | Machine axis names | AC20 | Add the new axis name (e.g., C1) |
| MD20070 $MC_AXCONF_MACHAX_USED | Channel axis assignment | AC20 | Append the new channel axis index |
| MD30350 $MA_IS_ROT_AX | Axis type (rotary / linear) | AC20 | 1 for C-axis, 0 for linear |
| MD35000 $MA_SPIND_ASSIGN_TO_MACHAX | Spindle-to-axis assignment | AC20 | Set when adding a 2nd spindle |
| MD19610 $ON_TECHNO_FUNCTION_MASK | Bit mask enabling tech cycles | AP58 | Bit 0 / bit 1 per cycle group |
| MD52200 $MCS_TECHNOLOGY | Technology (miller / turner) | AP58 | 1 = turning, 2 = milling |
MD19610 is the master switch for the AP58 cycles. Each bit in the mask enables a cycle group; if the bit is zero the cycle is not offered in the input screens even though the option is licensed. The default mask on a fresh PPU is 0x0 — the commissioning engineer must set the bits that match the actual machine configuration.
Option Bits and $ON_SET_OPT — The Behind-the-Scenes Mechanism
Each license, once accepted, writes a 64-bit word into a non-volatile counter on the CF card. The word is read on every cold start and copied into the option-bit word $ON_SET_OPT. The HMI Licenses screen is a re-formatted view of this same word. The relevant data flow is:
- CF card holds the license record (serial-number bound, signed).
- On startup, the license manager verifies the signature against the public key stored in the firmware.
- Verified options are written to
$ON_SET_OPTand to the option database filesloptions.daton the CF card. - Each option-aware machine data read consults
$ON_SET_OPT; if the bit is zero the data is treated as if the option does not exist.
This mechanism is also why a CF card swap is not free: the new card does not have the signature records, and the licenses must be reissued through the Siemens Web License Manager by quoting the new card serial number.
Troubleshooting Matrix
| Symptom | Alarm code | Root cause | Remedy |
|---|---|---|---|
| "Option activated without license" appears at every NC start | 8022 | MD references option that is not licensed | Set license per Step 1–7 above; if CoL is missing, escalate to OEM |
| Axis visible in MD but not in channel | — | License set but axis not assigned in MD20070 | Append axis to $MC_AXCONF_MACHAX_USED
|
| Cycle softkey missing in ShopTurn / programGUIDE | — | AP58 licensed but MD19610 mask = 0 | Set MD19610 bits per cycle group required |
| Set option softkey is greyed out | — | Access level below Manufacturer | Switch to Manufacturer or Service password |
| License number rejected as invalid | 8023 | CF card serial number on CoL does not match installed card | Verify serial on HMI under Diagnostics > Version; reissue CoL if mismatch |
| License accepted, but lost after firmware upgrade | — | Firmware install re-formatted CF card | Re-enter license from CoL after upgrade; backup sloptions.dat first |
| AP58 cycles not visible despite licensed status | — | Technology set incorrectly (e.g., milling cycles in turning context) | Verify MD52200 matches the actual machine technology |
Edge Cases and Field-Commissioning Caveats
- Counter-spindle plus C-axis on a single 0AC20. A common OEM mistake is to order a single 0AC20 and try to use it for two extra axes. Each axis consumes one credit. Order 6FC5800-0AC21-0YB0 instead for a two-axis credit pack, or two single-axis CoLs.
- Re-licensing after a service CF swap. If the original CF card is replaced under RMA, the new card has a different serial number. The Web License Manager can reissue the CoL to the new serial at no additional cost if the original order is in warranty; outside warranty a reissue fee applies.
- Option "licensed but disabled" state. The license overview distinguishes "not licensed" (no CoL present) from "not set" (CoL present but softkey not pressed). Engineers troubleshooting should always check the state column, not just the existence of a CoL in the cabinet.
- AP58 on Basic T versus SWD. Basic T is the G-code turning variant. ShopTurn (SWD) is a separate option. The AP58 cycles are available in both environments, but the input screens differ.
- Firmware downgrade. Downgrading from SW 4.7 to SW 4.5 will lose any options that were licensed on 4.5-or-newer catalogs. Always confirm the target firmware supports the desired options before downgrade.
Safety and Operational Notes
The AP58 technology cycles are software-only; they do not introduce new axes or new safety-relevant hardware. Even so, any new cycle must be validated on a test part before production release. The validation should cover dry-run, single-block, and reduced-feedrate execution to confirm tool-path behaviour.
Frequently Asked Questions
What does the trailing "-0YB0" on a SINUMERIK 828D part number mean?
The -0YB0 suffix indicates that the option is delivered on paper as a Certificate of License (CoL) and must be entered manually under Setup > Etc > Licenses. -0YB0 always requires the CF card serial number to match; -0YB1 is the same delivery form with a different export-control classification. The absence of a Y-suffix usually means the option is preloaded onto the CF card at the factory.
How many extra axes does a single 6FC5800-0AC20-0YB0 license unlock?
Exactly one additional controllable interpolation axis or spindle. For a mill-turn that adds both a Y-axis and a counter-spindle, two CoLs (or the bundled 6FC5800-0AC21-0YB0 for two axes) are required.
Why does the controller show "Option activated without license" (alarm 8022) even after entering the license number?
Either the access level is below Manufacturer (the softkey is greyed out but the value is not actually written), the CF card serial on the CoL does not match the installed card, or the license was entered with a hot start and requires a 24 V reboot. Clear the alarm with the Cancel key, reboot, and re-check the Licenses screen.
Do I need to re-license after a firmware upgrade?
Only if the upgrade re-formats the CF card (major version jump, for example 4.5 to 4.7). Minor SP upgrades preserve the option database. Always back up the sloptions.dat file before any firmware operation so the CoL numbers can be re-entered if necessary.
What machine data enables the AP58 technology cycles after the license is set?
Set MD19610 $ON_TECHNO_FUNCTION_MASK to the bit pattern that matches the cycle groups required (bit 0 for the first group, bit 1 for the second, and so on). Also confirm MD52200 $MCS_TECHNOLOGY is set to 1 (turning) or 2 (milling) depending on the actual machine configuration.
Can a single AP58 license be used on two PPU 241.2 controllers?
No. The license is bound to a single CF card serial number. Each PPU requires its own CoL. The Web License Manager can reissue a CoL to a new serial number when a CF card is replaced under RMA.