Overview: SIMOREG 6RA7093-4KV62-0-Z Parameter Recovery in Drive Monitor
The SIMOREG DC-MASTER 6RA70 series is a fully digital thyristor power converter used for the armature and field supply of DC motors. The model code 6RA7093-4KV62-0-Z identifies a specific configuration of this family:
- 6RA7093 – 3-phase armature supply, 930 A rated DC current class (the "93" suffix designates the 930 A frame within the 6RA70 family)
- 4 – Field supply: 4-quadrant operation (both directions of torque and speed)
- KV62 – Hardware variant (control board / firmware option set)
- 0 – Standard firmware version baseline
- Z – Order designation marker (conformal coating / export variant)
Field engineers frequently need to recover or replicate the parameter set of a working 6RA7093 unit when commissioning a replacement drive, migrating to a new motor, or restoring a unit that has lost non-volatile parameter memory. Siemens provides the Drive Monitor PC tool for this purpose, with parameters exchanged in its native text-based Drive Monitor format (file extension .dnx or .txt depending on firmware generation).
Because the SIMOREG 6RA70 stores all tuning data, motor nameplate data, encoder scaling, and closed-loop coefficients in parameter memory, a parameter mismatch between drives almost always causes F030 (field current too low), F031 (field current too high), F034 (electronic overload trip), or simply poor speed/current regulation. The remainder of this document walks through the correct Drive Monitor workflow.
Drive Monitor Tool Requirements and Communication Setup
Drive Monitor is the official Siemens commissioning software for the SIMOREG 6RA70 family. It connects to the drive via serial point-to-point using the RS485 port on the PMU (Parameterizing and Monitoring Unit) or via the optional CBP2 PROFIBUS / CBD2 DeviceNet / CBC CAN communication boards with an RS232-to-RS485 converter on the host side.
Required Components
- Drive Monitor installation media (current revision supporting the 6RA70 firmware in use – typically DriveES SIMOREG or the standalone Drive Monitor from the SIMOREG Compendium CD)
- PC with a free RS232 (COM) port or USB-to-RS232 adapter (FTDI-based adapters are recommended for stable timing)
- Siemens serial cable (6SX7005-0AB00 or equivalent 9-pin straight-through RS485 cable) for the PMU port
- Appropriate parameter documentation for the firmware revision (see the SIMOREG Compendium manual)
Communication Parameters (Default)
| Parameter | Default Value | Description |
|---|---|---|
| P780 | 1 | Drive address (USS protocol on PMU port) |
| P781 | 1 | USS baud rate index (1 = 9600 baud, 2 = 19200 baud, 3 = 38400 baud) |
| P782 | 2 | Number of data bits (1=7E, 2=8E, 3=8N, 4=8O) |
| P783 | 0 | PKW word length (0 = normal, 1 = extended) |
For a standard Drive Monitor upload, leave the drive address at 1 and use 19200 baud / 8 data bits / even parity.
Understanding Parameter Numbering in the 6RA70
The SIMOREG 6RA70 organizes parameters into functional groups. Knowing the grouping is essential when you only have a partial parameter set, because motor and feedback scaling parameters sit in a different group than speed-controller tuning parameters.
Parameter Group Map
| Range | Function Block | Typical Contents |
|---|---|---|
| P000 – P049 | Display / measured values | Actual speed, current, field current, line voltage, status words |
| P050 – P099 | Motor / power section data | Rated armature voltage/current, field data, thermal time constant, tacho scaling |
| P100 – P199 | Speed setpoint / ramp-function generator | Setpoint source, ramp-up/ramp-down times, minimum/maximum speed |
| P200 – P299 | Speed controller / EMF controller | KP, TN, optimization runs, droop, friction compensation |
| P300 – P399 | Current controller / field weakening | Armature current PI, field current PI, field weakening characteristic |
| P400 – P499 | Limit values / monitoring | Torque limits, I²t thresholds, speed monitoring windows |
| P500 – P599 | Technology functions | Wobble generator, master/slave, fixed setpoints, brake control |
| P600 – P699 | Free blocks / connectors | Connector selection, BICO-style free interconnection |
| P700 – P799 | Control word / status word / serial interface | USS/PROFIBUS settings, control word bits, fault memory |
| P800 – P899 | Drive identification / hardware | MLFB, power section ID, software version, factory number |
| P900 – P999 | Parameter sets / ramp-down / password | Save parameter set, factory settings via P051=21, language, password |
Extracting Parameters from a Working 6RA7093-4KV62-0-Z
Follow this sequence to capture a complete working parameter set from a known-good drive. Always record parameters from the actual drive the user intends to clone – parameters from a different MLFB or motor pairing will not transfer correctly because motor nameplate, current rating, and field characteristics differ.
Step 1 – Establish Serial Communication
- Connect the RS485 cable between the PMU X500 (or X501 if used) and the PC COM port.
- Power the drive electronics (auxiliary 24 V or main supply). The PMU should display a value or "--- 0.0" standby.
- Open Drive Monitor, choose Online > Drive Connection, and select Serial/USS with baud rate = P781 value and drive address = P780 value.
- Click Connect. The status bar in Drive Monitor should display ONLINE with the drive order number (e.g., 6RA7093-4KV62) visible in the header bar.
Step 2 – Capture the Full Parameter List
- From the Drive Monitor menu, select Drive > Upload All Parameters to PC (or press F5 in some revisions). This uploads every indexed parameter, indexed from P000 through the highest parameter in the installed firmware.
- Save the upload to a Drive Monitor format file (typically
.dnxor comma-delimited.txt). Suggested filename convention:6RA7093-4KV62_FWx.x_SNxxxxx_yyyymmdd.dnxcapturing firmware revision, factory serial, and date. - Drive Monitor will report a number-of-parameters upload count. If the upload stops early, the communication parameters do not match – verify P780/P781/P782 against the Drive Monitor port settings.
Step 3 – Capture the Fault and Warning Memory
- Open Diagnosis > Fault Memory and save the contents. The 6RA70 stores the last eight faults and warnings in a non-volatile buffer.
- Save the current state of binary inputs/outputs (BICO) using Drive > Upload Free Block Configuration if your application uses free interconnection blocks.
P051 = 21: Factory Reset Procedure
If the unit has no usable parameter backup, restore the drive to Siemens factory defaults using parameter P051:
- Bring the drive to a safe, de-energized state. The line contactor should be open and the armature current at zero. The factory reset does not require main power, only the electronics supply.
- Set P051 = 21 from the PMU keypad or via Drive Monitor online. P051 is a confirmation parameter; setting it triggers the reset on the next power-up or on the next parameter save action.
- Confirm by setting P052 = 1 (write parameters to EEPROM, latch to non-volatile memory). Without this step, the factory reset is not retained after power-off.
- Cycle the electronics supply (24 V or auxiliary fan supply OFF → ON).
- On reboot the drive will display factory default values. Confirm by reading P051 again – it should return to 0 (idle).
Uploading the Captured Parameter Set to a Replacement 6RA70
- Connect Drive Monitor to the replacement drive and verify it is online.
- Select Drive > Download All Parameters from PC (or File > Send to Drive depending on revision). The download writes parameter values one at a time to the drive's RAM.
- After the download completes, set P052 = 1 to commit the parameter set to EEPROM. Failure to commit causes the drive to revert to the previous parameter set at the next power cycle.
- Cycle control power and verify the parameters have been retained by reading back P050, P100, P200, and P300 group values.
Key Parameters to Verify After Download
After a parameter download from a donor unit, validate the following critical parameters against the actual motor nameplate and the wiring of the recipient drive. Do not assume they are correct just because the file transferred without error.
| Parameter | Typical Value Source | Validation |
|---|---|---|
| P100 | Motor nameplate rated armature voltage (V DC) | Match to motor data plate |
| P101 | Motor nameplate rated armature current (A DC) | Match to motor data plate |
| P102 | Field current at rated flux (A DC) | Match to motor field data |
| P110 | Line-to-line AC supply voltage | Match to actual site supply |
| P111 | Power section rated DC current | Match to drive MLFB rating (930 A for 6RA7093) |
| P140 | Speed feedback source (tacho / encoder / EMF) | Match to actual feedback wiring |
| P141 | Tacho voltage at rated speed (V/1000 RPM) | Match to actual tacho nameplate |
| P143 / P144 | Encoder PPR | Match to actual encoder |
| P152 / P153 / P155 / P156 | Current controller P and I gains | Must be tuned to motor impedance – not transferable across motors |
| P170 / P171 | Speed setpoint source | Match to actual reference wiring |
| P390 / P391 | Line frequency / phase rotation | Match to site (50/60 Hz) |
| P820 / P821 | MLFB / software version | Verify the drive identity is intact after reset |
Common Parameter-Related Fault Codes
When a parameter download is incomplete or mismatched, the 6RA7093 reports one of the following faults. Use the table to map symptoms to the parameter group that needs review.
| Fault | Meaning | Likely Parameter Cause |
|---|---|---|
| F001 | Electronics supply fault | P052 not set after parameter write; EEPROM checksum invalid |
| F004 | Line voltage monitoring | P110 (line voltage) not matched to actual supply |
| F005 | Line frequency out of range | P390 (line frequency) not set to 50 or 60 Hz |
| F006 | Line phase failure | Check P390 / P391; verify phase rotation |
| F030 | Field current too low | P102 (field current) or field hardware mismatch |
| F031 | Field current too high | P102 (field current) mis-sized |
| F034 | Electronic overload trip (I²t) | P101 / P111 motor current set below actual load; thermal time constant P114 wrong |
| F035 | Motor overload | P114 thermal time constant mismatch |
| F036 | Wire break, tacho | P140 tacho source / P141 tacho scaling mismatch |
| F042 | Tachometer fault / encoder fault | P143/P144 encoder PPR wrong |
| F051 | Parameter checksum error | P052 not set after edit; EEPROM fault – try P051=21 then re-enter |
| W018 | Speed controller saturated | P200/P201 (speed controller Kp/Tn) not optimized for the motor |
For the complete fault list and recovery procedure, refer to the SIMOREG DC-MASTER Compendium (C98130-A1256 series) available from Siemens Industry Online Support.
Drive Monitor File Format Reference
The Drive Monitor parameter file is a plain ASCII text file. Each line represents one parameter and follows the structure:
P100 = 400.0 ; Rated armature voltage (V)
P101 = 720.0 ; Rated armature current (A)
P102 = 15.5 ; Rated field current (A)
P051 = 0 ; Reset / confirmation parameter (idle)
P052 = 1 ; Save parameters to EEPROM
Key formatting rules for a valid Drive Monitor file:
- Parameter index (P###) must be exactly four characters including the P.
- The equals sign must be surrounded by single spaces.
- The numeric value uses a period as decimal separator; no thousands separator.
- A trailing comment starts with a semicolon and is ignored on download.
- Index parameters (those with subindices, e.g., connector selection) use square brackets, for example
P600[1] = 0.
Working with Multi-Parameter Sets
The SIMOREG 6RA70 supports multiple parameter sets in some firmware revisions. Use the following to manage them:
- P056 = 0..3 – Select active parameter set (0 = factory, 1..3 = user sets).
- P057 – Copy active set to a target set.
- P058 – Copy parameter set to/from optional operator panel (OP1S) memory.
Optimization After Parameter Download
A downloaded parameter set provides a starting point but must be re-optimized for the recipient drive's motor and mechanical load. The standard optimization sequence on the 6RA70 is:
- Current controller optimization – Triggered by setting P051 = 25. The drive applies a current step and measures armature resistance and inductance to set P155 / P156 automatically. The motor must be uncoupled or free to rotate without load for this to succeed; for a coupled motor, the optimization will report partial results and the integrator component (P156) must be entered manually.
- Speed controller optimization – Triggered by setting P051 = 26. The drive runs a pre-defined speed profile and sets P200 (Kp) and P201 (Tn) for the closed-loop speed controller.
- Field weakening optimization – Triggered by setting P051 = 27. The drive maps the field characteristic for operation above base speed. Only run this with the motor uncoupled if the load cannot tolerate field reduction.
- EMF controller optimization – Triggered by setting P051 = 28. Optimizes the EMF controller for flux control.
Each optimization can take 30–90 seconds. If any optimization reports a fault (typically F030, F031, or F042), abort and investigate motor wiring and feedback hardware before retrying. The optimization procedure is detailed in the SIMOREG DC-MASTER Compendium manual C98130-A1256.
Parameter Backup Verification Checklist
Before relying on a captured parameter file, validate it using this checklist:
- ✓ File opens cleanly in Drive Monitor without "invalid index" warnings.
- ✓ P800 (drive MLFB) matches the source drive: 6RA7093-4KV62-0-Z.
- ✓ P820 (software version) is recorded in the file header or comments.
- ✓ All P150–P156 current controller values are present (not zero, not default 0/0).
- ✓ P200 / P201 speed controller values are present.
- ✓ P300–P340 field-related values are present.
- ✓ The parameter count reported by Drive Monitor on upload matches the count in the file (Drive Monitor displays this in the status bar after upload).
Troubleshooting Matrix: Parameter and Drive Monitor Issues
| Symptom | Root Cause | Action |
|---|---|---|
| Drive Monitor reports "No connection" | Incorrect baud rate or wrong drive address | Verify P780=1, P781=2 (19200), P782=2 (8E1); check COM port |
| Upload terminates early (e.g., P350 instead of P999) | Communication break, EMI, or wrong parity | Lower baud rate to 9600, replace serial cable, check shield grounding |
| Downloaded parameters revert to defaults at power-on | P052 = 1 not executed after download | Re-issue P052 = 1 to commit to EEPROM, then power cycle |
| Drive faults F051 (parameter checksum) | EEPROM write interrupted, or battery-backed SRAM failure on older hardware | Issue P051 = 21, re-enter parameters, confirm P052 = 1; if persistent, replace PMU card |
| Motor runs but with poor speed regulation | Speed controller Kp/Tn (P200/P201) not optimized for the recipient motor | Run speed controller optimization (P051 = 26) |
| F042 encoder fault after parameter download | Encoder PPR or type (P143/P144) does not match recipient hardware | Verify encoder wiring and PPR; re-enter P143/P144 to match |
| F030 / F031 on first run | Field current setpoint (P102) mismatched with motor field | Re-enter P102 from motor nameplate; verify field supply hardware |
| Drive runs at half-speed or overspeed | Tacho scaling (P141) or encoder PPR wrong | Verify P141 from tacho nameplate; confirm tacho polarity |
Safety and Operational Notes
Working with the SIMOREG 6RA7093 requires attention to lethal voltages – the DC bus on a 930 A unit can reach 800 V DC and the line-side three-phase AC is present at the power terminals whenever the line contactor is closed. Always:
- Lock out / tag out the main disconnect and verify zero energy with a properly rated meter before opening the cabinet.
- Wait at least 5 minutes after power removal for the bus capacitors to self-discharge below 50 V DC before touching any power section components.
- Parameter edits with the line contactor closed will become active immediately; the motor can start if a run command is present. Always disable the run command before downloading parameters.
- P051 = 21 (factory reset) does not require main power but does require that the drive is in a stopped state. If the drive is in run, the parameter is rejected.
FAQ
Can I copy parameters from one SIMOREG 6RA70 to a different MLFB?
You can copy parameters between drives of the same family, but motor-specific values (P100–P114, P140–P144, P155–P156, P200–P201) must be re-entered to match the actual motor nameplate. Current and speed controller gains must be re-optimized for the new motor because they are sized to armature resistance and inductance, which differ between motors.
What does P051 = 21 do on a 6RA7093-4KV62-0-Z?
P051 = 21 restores all adjustable parameters to Siemens factory defaults. The drive MLFB identity (P800–P820), the fault memory, and the communications address (P780) are typically not cleared. The reset must be committed to non-volatile memory by setting P052 = 1 and then cycling the electronics supply.
How do I capture parameters in Drive Monitor format?
Connect to the drive over the PMU RS485 port using Drive Monitor at the configured baud rate, then use Drive > Upload All Parameters to PC (F5). Save the file with a meaningful name including the drive order number, firmware version, and date. The saved file can be re-loaded into another drive with Drive > Download All Parameters from PC followed by P052 = 1 to commit.
Why does the drive still fault after I downloaded the parameter file?
Most common cause: the parameter download was not committed to EEPROM (P052 = 1 was not executed), so the drive reverted to its previous set on the next power-on. Secondary cause: the parameters were copied from a different motor or feedback hardware, so the speed/current controller gains and the tacho/encoder scaling do not match the actual installation. Verify P052, then verify P101, P102, P141, and P143/P144 against the actual motor nameplate.
Where do I find the official SIMOREG 6RA70 parameter list and fault code reference?
The SIMOREG DC-MASTER Compendium (C98130-A1256 series) contains the complete parameter list, fault code table, and commissioning procedure. It is available as a PDF from the Siemens Industry Online Support portal at support.industry.siemens.com, including the attachment C98130-A1256-A002-14-7619.pdf referenced in the SIMOREG DC-MASTER support documentation.