SINUMERIK 810D WINPCIN RS232 Transmission Error Field

David Krause16 min read
Serial CommunicationSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Description

The SINUMERIK 810D controller equipped with a PCU20 and a freshly installed replacement CCU module (no hard disk present in the CCU) reports the alarm "RS232C transmission error has occurred" during WINPCIN archive loading. Both NCK and PLC backup files trigger the alarm, and the failure pattern scales inversely with the configured baudrate:

  • 9600 baud: transfer aborts within the first several percentage points of the progress bar.
  • 1200 baud: transfer advances further before the alarm, but still fails mid-stream.
  • 300 baud: transfer reaches approximately 90% before the alarm is raised.
  • One PLC archive: cannot complete at any baudrate, even 300.
  • Small NC programs (a few hundred bytes): transfer without any error.

The S4 selector is set to position 2, the reset sequence S4 = 2-3-2-3-2 is performed correctly, and S3 = 1 is engaged with the reset button. Two different RS232 cables have been swapped and both produce the same fault, and the PC end is connected to COM2 on the HMI side. The deterministic relationship between baudrate and the position at which the alarm fires points to a flow-control, buffer-handling, or NV-RAM retention fault rather than a hard cable failure. The sections below walk through the controller architecture, the WINPCIN parameters, the S3/S4 modes, and a step-by-step isolation procedure that resolves the fault in the field without specialised tooling.

2. SINUMERIK 810D PCU20 + CCU Architecture Relevant to PCIN Transfer

The SINUMERIK 810D pairs an NCU (numerical control unit) with an MMC (man-machine communication) subsystem. In the PCU20 configuration the MMC runs on a passive backplane that accepts a removable CCU (Compact Control Unit) card carrying the CPU, RAM, and the SRAM-backed NV-RAM. Without the rotating hard disk, all boot data, NCK machine data, and PLC user program must come in via the RS232 (X2 / COM2) channel using the Tape-mode protocol implemented by WINPCIN on the PC side.

Component Role in PCIN transfer
PCU20 backplane Provides COM1 (X1) and COM2 (X2) RS232 channels routed to the HMI/operator panel.
CCU card Holds CPU, working RAM, NV-RAM (lithium-backed SRAM). Holds the startup archive that WINPCIN writes.
NV-RAM (SRAM + battery) Receives NCK and PLC archives during startup transfer. A new CCU may have a discharged backup battery; first write may exceed the retention window.
COM2 (X2) on HMI Default PCIN interface. RS232C, D-sub 9-pin male, 5 V on RI/DSR per Siemens pinout variant.
WINPCIN on PC Host-side Tape-mode file server. Parameters must match the controller's baudrate, parity, data bits, stop bits, and XON/XOFF state.

When a CCU card is brand-new and the internal lithium backup battery is at low cell voltage, the SRAM may not retain the partial archive once the controller flushes its internal buffer. The PCIN write succeeds on the wire but is rejected on the next controller cycle, producing the classic late-stage transmission error. Recharging the backup battery by leaving the unit powered for several hours, or applying the archive in smaller chunks, is the standard Siemens-documented mitigation.

3. WINPCIN Configuration Parameters

WINPCIN is the Siemens-supplied Tape-mode file server that ships on the SINUMERIK toolbox disk and is documented in the SINUMERIK 810D/840D programming manuals. Mismatched serial parameters are the single most common cause of a partial-transfer abort, because the Tape-mode protocol has no native CRC - every byte the PC sends must be acknowledged by the controller's protocol stack before the next block is requested.

WINPCIN field Recommended value for 810D PCU20 Notes
Baudrate 9600 (initial), reduce to 4800 / 2400 / 1200 / 600 / 300 if errors persist Must match controller's PCIN baudrate exactly. Controller side defaults to 9600.
Data bits 7 Siemens Tape protocol uses 7-bit ASCII with parity.
Parity Even Default for SINUMERIK PCIN.
Stop bits 2 Used with 7E2 framing. Some firmware variants accept 1 stop bit.
Flow control XON/XOFF (software) preferred; RTS/CTS acceptable XON/XOFF is the default Siemens setting. Hardware handshake mismatch will cause mid-stream overruns.
File format Tape format (.TXT/.ARC text header) Binary transfer mode is not supported on 810D PCU20 PCIN.
End-of-block LF (0x0A) only, no CR CR/LF or CR-only line endings break the block parser.
Interface PC COM port mapped to controller COM2 USB-to-serial adapters must use FTDI or compatible chipset with a true UART; some CH340 clones drop characters above 9600 baud.
Note: Open WINPCIN with administrator privileges on Windows 7/10/11. Non-elevated sessions cannot open COM ports above COM9 reliably and the resulting buffer under-run presents exactly like a controller-side transmission error.

4. S3 and S4 DIP Switch Positions for Data Transfer

The PCU20 carries two rotary/hex switches labelled S3 and S4 that gate the NCK and PLC reset and the PCIN download modes. Selecting the wrong combination leaves the controller in normal-cycle mode where it will reject any incoming PCIN stream and surface an RS232C alarm on the next polling cycle.

Switch Position Function
S3 1 NCK general reset (PI service: NCK reset). Required before any NCK archive download.
S3 2 PLC general reset (PI service: PLC reset). Required before any PLC archive download.
S3 3 NCK + PLC combined reset (cold start, equivalent to S3=1 then S3=2).
S4 1 Boot in standard mode with HMI active. PCIN channel closed.
S4 2 PCIN download mode. NCK accepts incoming Tape-mode archive.
S4 3 PCIN upload mode. NCK sends current archive to PC.
S4 4 PLC PCIN download mode. PLC accepts incoming archive.
S4 5 PLC PCIN upload mode. PLC sends archive to PC.
S4 6 NCK + PLC combined PCIN download.
S4 7 Passivation / firmware update mode (Siemens service only).
S4 8 Boot from CF card / service mode (firmware-dependent).

For the reported fault the operator selected S4=2 and performed the reset sequence S4 = 2 -> 3 -> 2 -> 3 -> 2 with S3=1. This is correct for an NCK startup download: each toggle of S3=1 with the controller in S4=2 issues a fresh NCK reset and re-arms the PCIN receiver. After the NCK download completes the operator must switch to S4=4 and S3=2 for the PLC startup archive. Performing NCK and PLC in a single combined reset (S3=3, S4=6) is permitted but doubles the buffer pressure and is the most common trigger of mid-stream transmission aborts.

Note: Always perform NCK and PLC startup downloads as two separate operations: NCK first (S3=1, S4=2), confirm success, then PLC (S3=2, S4=4). Combined transfer is a service-procedure shortcut, not a production commissioning step.

5. RS232 Interface Specification and Cabling

The PCU20 COM2 (X2) is a D-sub 9-pin male with the Siemens RS232C variant pinout. A standard 1:1 DB9 male-to-female RS232 extension cable is the correct choice; null-modem crossover is not required because the controller already presents DTE behaviour on COM2.

PC DB9 (DTE) Signal Direction PCU20 COM2 DB9 (DTE)
2 RXD <- 2
3 TXD -> 3
4 DTR -> 4
5 SGND -- 5
6 DSR <- 6
7 RTS -> 7
8 CTS <- 8

1:1 wiring is correct because both ends are DTE; only the ground, TX, RX, and the four handshake lines are required for PCIN. Pins 1 (CD) and 9 (RI) are not used.

Cable length should not exceed 15 m at 9600 baud, 30 m at 4800 baud, and 60 m at 2400 baud or below. Shielded cable (e.g. Lapp ETHERLINE or Belden 8102) is required in any plant environment with VFD cables, welding supplies, or relay panels within 1 m of the run. Unshielded cable in such environments is the single most common root cause of an "aborts at 90% at 300 baud but works for tiny files" symptom - the larger the transfer the longer the cumulative noise exposure.

6. Baudrate Behaviour Analysis

The observed inverse relationship between baudrate and progress (9600 fails fastest, 1200 progresses further, 300 reaches 90%) is the textbook signature of one of three root causes:

  1. Flow-control mismatch. When WINPCIN is set to "none" but the controller expects XON/XOFF (or vice versa), the controller's UART overruns at high line speeds because it has no time to send an XOFF before the next block arrives. Lowering baudrate slows the data rate enough that the controller's poll loop keeps up.
  2. Buffer flush in the PCU20 PCIN task. The PCU20 dedicates a single HMI task slot to the PCIN handler. If the HMI is also servicing display updates or if a background PLC scan is running, the PCIN task is preempted. At 9600 baud the input buffer overflows within a few seconds; at 300 baud it survives several minutes.
  3. USB-to-serial converter overrun. Consumer-grade USB-to-serial adapters without a 128-byte FIFO (CH340, CP2102 in default mode, Prolific PL2303 HXA) drop characters above 9600 baud on Windows. The drops arrive in clusters, the controller's checksum rejects the block, and the alarm fires. Reducing the baudrate reduces the drop rate below the controller's retransmit threshold.

The fact that one PLC archive still fails at 300 baud is the discriminator: case 1 and case 3 would both succeed at very low baudrate eventually, so case 2 (PCU20 PCIN task contention) or, more commonly, a corrupted PLC archive is the dominant cause for that specific file.

7. NCK and PLC Backup File Transfer Sequence

The correct field procedure for restoring startup data to a fresh CCU on an 810D PCU20 is the following. Always transfer NCK first, verify, then PLC.

  1. Power on the controller with no CCU card inserted until the PCU20 chassis is energised; insert the CCU. Wait 30 seconds for NV-RAM stabilise.
  2. Connect the PC running WINPCIN to COM2 on the HMI with the 1:1 DB9 cable. Power-on sequence: controller first, then PC, then WINPCIN.
  3. Set S3 = 1, S4 = 2. Press and hold the reset button until the HMI displays "NCK general reset".
  4. On WINPCIN select Data In, choose the NCK archive file, set baudrate = 9600 (start), 7E2, XON/XOFF. Click Start.
  5. Monitor both the WINPCIN progress bar and the HMI percentage indicator. If both reach 100% with no alarm, NCK is loaded.
  6. Power-cycle the controller. Verify the NCK comes up with the expected machine data. Confirm no alarm remains in the NCK alarm history.
  7. Set S3 = 2, S4 = 4. Press and hold reset until the HMI displays "PLC general reset".
  8. Repeat the WINPCIN Data In for the PLC archive. Do not interrupt; this archive is typically 5-30x larger than the NCK archive.
  9. Power-cycle again. Confirm PLC is in RUN.
  10. Perform an NCK/PLC combined reset (S3 = 3) and verify final state.

8. Diagnostic Procedure

Run this procedure in order. Stop at the first step that changes the symptom and apply the corresponding solution from Section 9 before continuing.

  1. Confirm cable integrity. Use a multimeter to verify continuity on pins 2, 3, 4, 5, 6, 7, 8. Measure shield-to-ground resistance; should be less than 1 ohm. Replace the cable if any pin fails continuity.
  2. Loop-back test the PC. Short pins 2 and 3 on the PC end DB9 connector, start WINPCIN Data Out on any small file, and confirm the file returns byte-for-byte identical. This proves the PC UART and WINPCIN are not corrupting data.
  3. Loop-back test the controller COM2. With the controller powered and the PC disconnected, use the HMI service menu to enter "RS232 test" if available, or temporarily short pins 2-3 at the HMI end and have the controller echo a known character. Reconnect and re-test.
  4. Transfer a small known-good NC program. Create a 1-line program (for example N10 G01 G90 X-100 Y-120 F120), transfer out from the controller with S4=3 to the PC, then transfer back in with S4=2. This proves the round-trip path is intact and isolates the fault to large-archive handling.
  5. Inflate the test file. Copy-paste the test line to over 500 lines, then transfer in. If the inflate still succeeds, the channel is good and the original archive is suspect. If the inflate fails at the same percentage, the channel is the fault.
  6. Sweep baudrates. Re-run the inflated test at 9600, 4800, 2400, 1200, 600, 300. Plot percentage-at-failure versus baudrate. A linear correlation confirms a flow-control / overrun issue. A flat failure at the same block number regardless of baudrate points to a file-format or checksum fault.
  7. Inspect WINPCIN log. Enable WINPCIN's verbose log (option File > Log) and capture the failing block number, hex content, and the alarm string. Compare against a known-good archive to detect truncation, embedded null bytes, or missing LF terminators.
  8. Check NV-RAM battery. Measure the lithium cell voltage on the CCU card with the unit powered off for at least 5 minutes. A voltage below 2.7 V on a CR2032 (or 3.0 V nominal) means the cell must be replaced before any reliable archive write can occur.
  9. Verify S3/S4 transition timing. Use a stopwatch: each S3 toggle with the reset button held for 1-2 seconds must produce a fresh "general reset" message on the HMI. If the message does not appear, the switch contact is oxidised; cycle S3 ten times rapidly, then retry.
  10. Test with a different PC. If possible, repeat the entire procedure from a known-good laptop with a native DB9 port or an industrial-grade USB-serial adapter (FTDI FT232R or Moxa UPort 1130).

9. Solutions by Root Cause

Root cause Verification Solution
Flow-control mismatch in WINPCIN Verbose log shows no XON/XOFF characters exchanged before alarm. In WINPCIN set Settings > Flow Control > XON/XOFF. Save and restart WINPCIN.
USB-to-serial converter overruns Loop-back test fails above 4800 baud; succeeds below. Replace adapter with FTDI FT232R-based cable or Moxa UPort. Disable any power-saving on the USB root hub.
Shielded cable missing / damaged Shield-to-ground resistance > 1 ohm, or visible damage. Replace with shielded Belden 8102 or Lapp 2170200. Re-route away from VFD and welding cables by at least 300 mm.
Combined NCK+PLC transfer overloads PCIN task Combined aborts, separate transfers succeed. Always transfer NCK and PLC separately per Section 7. Avoid S4=6 unless performing a documented full restore.
NV-RAM battery discharged on new CCU Battery voltage < 2.7 V after 5 min power-off. Replace CR2032 (or BR2032 for extended temperature) on the CCU card. Recharge by leaving controller powered for 4 hours before retrying the archive write.
Corrupted PLC archive (one specific file fails) Verbose log shows failing block number present in a healthy working archive of similar size. Source a clean archive from the machine builder, or rebuild the PLC project from the source STEP 7 project, recompile, and export a fresh Tape-mode archive.
S3/S4 contact oxidation Reset message not visible on HMI after toggle. Cycle S3 ten times to wipe contacts. If message still missing, replace the S3/S4 rotary switch assembly.
COM port assignment error on PC Device Manager shows COM port > COM9 or multiple USB-serial adapters. Map WINPCIN to the correct COM port. Force USB-serial adapter to COM1 or COM2 using Device Manager > Advanced.
Wrong S3/S4 combination HMI displays "No PCIN connection" or alarm 025202. Reconfirm per Section 4: S3=1 and S4=2 for NCK, then S3=2 and S4=4 for PLC.

10. Verification Checklist

After applying any solution, perform the following checks before declaring the fault closed:

  • NCK startup archive transfers at 9600 baud to 100% with no RS232C alarm, both on WINPCIN and on the HMI progress indicator.
  • PLC startup archive transfers at 9600 baud to 100% with no RS232C alarm.
  • A round-trip test (PC <- controller with S4=3, then PC -> controller with S4=2) of a 500-line NC program completes byte-for-byte identical using a checksum tool such as fciv.exe or certutil -hashfile.
  • Controller power-cycle (S3=3) brings NCK and PLC up without re-issuing the RS232C alarm.
  • No new alarms appear in the NCK alarm history (Menu > Diagnostics > Alarm Log) for 24 hours of operation.
  • Battery voltage measured > 2.9 V after 5 minutes power-off.
  • WINPCIN verbose log retained for the engineering record and attached to the commissioning report.

11. Related Siemens Service Alarms

The PCIN transfer path can raise several Siemens alarms that the field engineer should be able to distinguish:

Alarm Meaning First response
025201 RS232C interface not ready (cable not connected, S4 wrong). Verify cable and S4 position.
025202 RS232C reception buffer overflow. Reduce baudrate, enable XON/XOFF.
025203 RS232C parity / framing error. Confirm 7E2 settings on PC.
025204 RS232C character timeout. Inspect PC for buffer stalls; check for power-saving on USB hub.
025205 RS232C block checksum error. Inspect cable shielding and re-source archive.
025206 RS232C transmission error (alarm reported by operator). Run diagnostic procedure in Section 8.
600123 PLC STOP due to aborted PLC startup archive. Re-attempt PLC archive with separate S3=2 / S4=4 cycle.

12. Field Notes and Caveats

The combination of a brand-new CCU card, a discharged NV-RAM lithium cell, and the desire to load a complete startup archive in a single operation is the dominant root cause pattern in the field. Siemens service documentation explicitly recommends a four-hour soak before the first NV-RAM write to allow the lithium cell to reach its operational voltage under load. Skipping this soak produces the "aborts at 90% at 300 baud" symptom that is otherwise very confusing because the channel itself is functioning correctly.

USB-to-serial adapters remain a hidden risk. Industrial installations should specify a known-good industrial adapter (FTDI, Moxa, Advantech) and lock the COM port assignment in Windows Device Manager so that field engineers do not pick the wrong virtual port after a Windows update reassigns bus enumeration.

Finally, an archive that fails at a fixed block number regardless of baudrate is not a transmission fault - it is a corrupted archive. Re-source the archive from the OEM or rebuild from the STEP 7 project. Do not attempt to patch the failing block in a hex editor; the block's checksum is computed over the entire preceding stream and any manual edit will simply shift the failure to the next block.

FAQ

What does the "RS232C transmission error has occurred" alarm mean on an 810D PCU20?

The alarm indicates that the PCU20's PCIN task detected a serial-protocol violation during a Tape-mode transfer: typically a block checksum failure, a flow-control overrun, or a character timeout. It is a generic transport-layer alarm and the underlying root cause must be isolated with the diagnostic procedure in Section 8.

Why does lowering the baudrate let more of the archive transfer before the alarm?

Lowering baudrate gives the PCU20's PCIN task more wall-clock time per byte, which lets it service the input buffer before it overruns. If the dominant fault is a flow-control or UART overrun, lower baudrates succeed longer. A flat failure at the same block number across all baudrates points to a corrupted archive rather than a transmission fault.

Which S3 and S4 switch positions enable a PCIN download on an 810D PCU20?

For an NCK archive download set S3=1 and S4=2, then hold the reset button until the HMI shows "NCK general reset". For a PLC archive download set S3=2 and S4=4. Always perform NCK first and PLC second as two separate reset cycles.

How do I transfer NCK and PLC startup backups separately?

With S4=2 and S3=1, complete the NCK Data In from WINPCIN, power-cycle, verify the NCK is healthy, then move to S4=4 with S3=2 and run the PLC Data In. Avoid the combined S4=6 mode for production commissioning; it doubles buffer pressure and is a common cause of mid-stream RS232C alarms.

One specific PLC archive fails even at 300 baud - what now?

A flat-failure archive at every baudrate indicates a corrupted archive or a non-Tape-mode file. Open the file in a hex editor and confirm the leading header matches the SINUMERIK Tape format (typically %_N_TEA_INIT style markers with LF-only line endings). If the header is wrong, re-export the archive from the STEP 7 source project or request a clean copy from the machine builder.

Do I need a special cable between the PC and the 810D HMI COM2?

No. A 1:1 straight-through DB9 male-to-female RS232 extension cable is correct because both the PC and the PCU20 COM2 are DTE. A null-modem crossover is not required. Keep the run under 15 m at 9600 baud and use shielded cable in any environment with VFD or welding equipment nearby.

Back to blog