Problem Overview
A migrated TIA Portal project targeting a SIMATIC TP1500 Comfort panel compiles cleanly in TIA Portal V11 with Runtime (OS) version 11. After the runtime is updated to OS version 13.0.1, the same project — with no changes to the IP configuration — refuses to compile and throws the following error in the compile log:
The IP address is in the same subnet as the interface X1
The original project had two PROFINET ports configured with the option "not networked" (no IP stack). The error appears immediately after the upgrade, before the panel is even downloaded. No edits were made to the port properties between V11 and V13.
This article documents the root cause, the supported solution confirmed by Siemens technical support, and the verification procedure.
Affected Products and Versions
| Component | Version / Identifier | Notes |
|---|---|---|
| HMI Hardware | SIMATIC TP1500 Comfort | 15" widescreen, 1280 × 800 native resolution |
| Original Engineering | TIA Portal V11 | Project built and tested |
| Original Runtime | OS V11 (WinCC Comfort) | Running on TP1500 Comfort |
| Target Engineering | TIA Portal V13 / V13 SP1 | Project migrated forward |
| Target Runtime | OS V13.0.1 | Updated firmware image on panel |
| Interfaces | X1, X2 (and optionally X3) | Independent PROFINET controllers |
The TP1500 Comfort is a member of the SIMATIC HMI Comfort Panel family. Its base unit always includes PROFINET port X1; additional ports (X2, X3) are exposed depending on the order code suffix (e.g. integrated second PROFINET interface, PN/PN coupler).
Root Cause Analysis
TIA Portal V13 introduced stricter validation rules for PROFINET interface configuration on Comfort Panels than V11 enforced. The rule that bites this specific project is:
Each physical PROFINET interface on a multi-port HMI must resolve to a unique IP subnet. Two interfaces whose address + mask combination lands in the same network prefix will fail compilation.
In V11 the "not networked" checkbox effectively disabled the IP routing path for that port, which meant the compiler did not perform subnet-overlap validation against it. The V13 compiler, however, treats a "not networked" port as an interface on a default address space and will flag a subnet conflict the moment a second interface is configured with any IP address.
The panel in question had both PROFINET ports configured with:
-
Subnet mask:
255.255.255.248(CIDR /29, 6 usable hosts per subnet) - IP addresses: two distinct host addresses inside the same /29 network
- Networking: "not networked" enabled on both
Even though the two IP addresses differed, they both resolved to the same /29 network prefix under V13 validation, and the compiler rejected the project before the runtime image could be generated. V11 never performed this check, which is why the same configuration shipped for years without incident.
Solution
Siemens technical support confirmed the fix in writing. The procedure is:
- Open the device configuration of the TP1500 Comfort in TIA Portal V13 (Project Tree → Devices → [TP1500 Comfort] → Device Configuration).
- Select the X1 port symbol in the device view.
- In the Properties inspector, expand PROFINET Interface [X1] → General → IP Protocol.
- Record the IP address and subnet mask currently assigned.
- Repeat steps 2–4 for the X2 (and X3, if present) port.
- Change at least one interface's subnet mask so that its
(IP AND mask)result differs from the other interface's network address.
Siemens support's specific recommendation in the original case was to change the subnet mask octet from 248 to 255 on the affected interface, so the mask moved from 255.255.255.248 (/29) to 255.255.255.255 (/32). A /32 mask gives the interface its own single-host network, which guarantees no overlap regardless of the partner IP. In practice, an equally clean and more conventional choice is 255.255.255.0 (/24), which produces a 254-host cell subnet and clearly separates the two PROFINET networks.
Once the masks are no longer overlapping, recompile. The error disappears and the project builds to completion.
The original Siemens support reply cited changing "248 to 255". This refers to the final octet of the dotted-decimal mask: 255.255.255.248 → 255.255.255.255. Both 255.255.255.255 (/32) and 255.255.255.0 (/24) are valid resolutions; pick whichever matches the physical topology you intend to deploy. Do not use 255.255.255.255 in production unless the port is genuinely point-to-point with a single peer, because no other device on that subnet can be reached.
Step-by-Step Procedure
1. Open the device configuration
- In the TIA Portal project tree, expand Devices.
- Double-click [TP1500 Comfort] to open the device view.
- The graphical representation of the panel shows the X1, X2, and (where populated) X3 ports along the bottom of the device silhouette.
2. Audit current IP settings
Click each port symbol and record:
| Port | IP Address | Subnet Mask | Network (IP AND mask) |
|---|---|---|---|
| X1 | 192.168.0.1 | 255.255.255.248 | 192.168.0.0/29 |
| X2 | 192.168.0.2 | 255.255.255.248 | 192.168.0.0/29 |
Both interfaces resolve to 192.168.0.0/29 — this is the conflict.
3. Re-mask one interface
For X2, change the subnet mask to 255.255.255.0. The result:
| Port | IP Address | Subnet Mask | Network (IP AND mask) |
|---|---|---|---|
| X1 | 192.168.0.1 | 255.255.255.248 | 192.168.0.0/29 |
| X2 | 192.168.0.2 | 255.255.255.0 | 192.168.0.0/24 |
Wait — that still overlaps at the network boundary because /29 is fully contained in /24. The clean fix is to either:
- Move X2 to a different physical subnet (e.g.
192.168.1.2with mask255.255.255.0), or - Apply distinct /29 networks (X1 =
192.168.0.0/29, X2 =192.168.0.8/29), or - Apply the Siemens-recommended /32 mask (
255.255.255.255) on the interface that does not need to be in a larger cell.
4. Recompile
From the menu: Compile → Software (rebuild all). Confirm the compile log no longer lists any IP/subnet errors.
Verification
After recompiling, run the following checks before downloading to the panel:
-
Compile log clean — no occurrences of
IP address is in the same subnet as the interface. - Device view inspection — both port symbols in the device view show their IP and subnet mask without warning triangles.
-
Network scan with PRONETA (free Siemens network diagnostics tool):
- Connect a service laptop to the engineering port.
- Run PRONETA → Network analysis → scan the segment.
- Confirm the TP1500 Comfort appears once per active port, with the configured IP.
-
Download and ping — download the project to the panel and use
ping <panel-IP>from a service PC to confirm L3 reachability on each port. - PROFINET diagnostics — from TIA Portal, right-click the panel → Online & Diagnostics → PROFINET diagnostics. The device should report no configuration errors.
Following the recompile under OS V13, you may see numerous warnings of the form "wrong size of graphics". These warnings did not appear under OS V11 and manifest at runtime as slightly distorted or blurry images. Root cause: V13 enforces stricter bitmap-vs-screen-resolution matching. Resolutions of typical TP1500 Comfort bitmaps that were authored against the V11 graphic engine may now be flagged. Fix by re-exporting bitmaps at the panel's native 1280 × 800 pixel grid, or by adjusting the screen / image object's "Adapt picture" property to
Fit or Stretch.
Subnet Mask Reference
| Dotted Mask | CIDR | Usable Hosts | Typical Use |
|---|---|---|---|
| 255.255.255.255 | /32 | 1 | Single-host (Siemens support recommendation in this case) |
| 255.255.255.248 | /29 | 6 | Compact point-to-point links |
| 255.255.255.240 | /28 | 14 | Small isolated subnets |
| 255.255.255.224 | /27 | 30 | Mid-size subnets |
| 255.255.255.192 | /26 | 62 | Department subnets |
| 255.255.255.0 | /24 | 254 | Standard cell subnet (recommended for HMI dual-port split) |
| 255.255.254.0 | /23 | 510 | Two adjacent /24s merged |
Why the V13 Stricter Rule Exists
At the industrial-networking layer, two IP interfaces on the same physical device resolving to the same subnet creates an ambiguous L2 routing situation. When an ARP request is broadcast, both ports will answer (or one will, unpredictably), and the kernel's routing table will not have a deterministic winner. PROFINET's real-time channel (RT/IRT) is particularly sensitive to this, because deterministic forwarding depends on knowing exactly which physical port owns a given MAC.
V11 was permissive because the original "not networked" UI state was conceived as a benign configuration placeholder — the panel's IP stack effectively skipped validation for that port. As Comfort Panels grew in capability and customers started routinely using both X1 and X2 for live networks (e.g., one to the PLC, one to a SCADA gateway), Siemens tightened the validation in V13 so that misconfigurations were caught at compile time rather than at commissioning.
Best Practices to Prevent Recurrence
- Document port roles at project creation. Decide up front: which port talks to the controller, which talks to the engineering / MES layer, which is unused.
- Always assign a real subnet mask to every port. Avoid "not networked" as a permanent placeholder; treat it as a temporary state during initial commissioning only.
- Run a dry compile before upgrading TIA Portal. Copy the project to a sandbox, upgrade, and recompile. Surface every V13 enforcement change before touching the live project.
- Use PRONETA for pre-commissioning verification — it scans PROFINET segments and reports duplicate IPs and overlapping subnets regardless of TIA Portal version.
- Track firmware/runtime versions explicitly. Store the OS image version in the project documentation. V11 → V13 is a non-trivial jump; expect behavior changes in graphic handling, scripting, and network validation.
- Engage Siemens support early when a migration breaks an unchanged configuration. The original case was resolved with a single Siemens support contact in one session.
Related Configuration Checks
| Check | Where (TIA V13) | Expected Result |
|---|---|---|
| No duplicate IP across the project | Project tree → right-click → Properties → Address overview | Each IP appears once |
| Each interface has a unique subnet | Device view → each port symbol | No warning triangles on port symbol |
| Router address set if cross-subnet traffic | PROFINET Interface → IP Protocol → Router | Default router IP matches target segment |
| PROFINET device name unique | Online & Diagnostics → Assign PROFINET device name | Unique on plant network |
| Panel time synchronized | Device configuration → Time settings | NTP or PLC-master, no drift > 1 s |
Diagnostics Quick Reference
| Symptom | Likely Cause | First Action |
|---|---|---|
| Compile error: IP in same subnet as X1 | Overlapping masks on X1 and X2 | Re-mask one interface to /24 or /32 |
| Download fails with timeout | PC on wrong subnet | Add static route to panel IP |
| Runtime shows distorted graphics | Bitmap resolution mismatch under V13 | Re-export bitmaps to 1280 × 800 |
| PROFINET name conflict at runtime | Duplicate device name in plant | Use PRONETA to assign unique name |
| Panel boots but X2 stays link-down | X2 not provisioned in order code | Verify hardware variant, not a software fault |
| Error persists after mask change | Address cache in compiled project | Compile → Software (rebuild all), not incremental |
Frequently Asked Questions
Why did the same project compile in TIA Portal V11 but fail in V13?
V13 tightened PROFINET interface validation. Configurations V11 treated as inert (e.g., both ports set to "not networked") now produce an explicit subnet overlap error during compile. Each interface must resolve to a unique (IP AND mask) network.
Is the "not networked" option still available in TIA Portal V13?
Yes, the checkbox remains on the PROFINET interface properties dialog. However, V13 still validates the implied subnet and will flag overlap when another interface is configured. Do not rely on "not networked" to bypass the rule.
Do I need to change IP addresses, or only subnet masks?
Often only the mask must change so the (IP AND mask) result differs per interface. In tightly packed topologies you may also need to renumber one interface. Validate with PRONETA before downloading.
Will changing the subnet mask break communication with the PLC?
Only if the PLC and the affected HMI port are expected to live on different physical segments without a router. If the PLC is at 192.168.0.10/29 and you move HMI X2 to 192.168.0.2/24, the routes are technically compatible because /29 is a subset of /24 — but only if the PLC accepts traffic from the wider /24 broadcast domain. Configure the router field if cross-segment traffic is intended.
What is the difference between X1, X2, and X3 on the TP1500 Comfort?
X1 is the primary PROFINET port and is always populated. X2 is present when the order code includes the integrated second PROFINET interface. X3 appears on certain variants with the PN/PN coupler option. Each is an independent Ethernet controller and must be assigned a unique subnet under V13.
Why do "wrong size of graphics" warnings appear after the V13 recompile?
V13 enforces stricter bitmap-vs-screen-resolution matching than V11. Bitmaps authored against the V11 graphic engine may not match the 1280 × 800 native pixel grid of the TP1500 Comfort. Re-export the bitmaps at the panel's native resolution, or set the picture object's Adapt Picture property to Fit or Stretch to remove the warnings.