Fixing LOGO! 8.3 Connection Errors with LOGO!Soft Comfort 8.3.1
This technical reference documents the diagnostic workflow and corrective actions for Ethernet communication failures between a Siemens LOGO! 8.3 basic module (firmware 1.83.02) and LOGO!Soft Comfort V8.3.1. The failure pattern addressed here is the most common field complaint: every LOGO! device on the LAN is visible to the LSC network browser, the LSC "Go Online" status returns devices, yet the program download fails, the connection drops during transfer, or LSC refuses to commit the new configuration to the LOGO! 8.3 BM. The same procedure applies whether the previous LSC install was V7.0/V7.1 or an earlier V8.x build.
1. LOGO! 8.3 Communication Architecture
Understanding the network stack used by LOGO! 8.3 prevents misdiagnosis. The BM (basic module) integrates a 10/100 Mbit/s Ethernet interface on the left-hand RJ45 port. Communication occurs over four distinct channels, each with its own TCP/UDP port:
| Service | Port | Protocol | Function |
|---|---|---|---|
| S7 PUT/GET (programming) | TCP 102 | ISO-on-TCP (RFC 1006) | Program upload/download, online monitoring via TIA / LSC |
| LOGO!Soft Comfort link | TCP 10005 | LOGO! proprietary | LSC configuration transfer, firmware update |
| Web server (HTTPS) | TCP 8443 | HTTPS | Web-based configuration, status visualization, e-mail setup |
| SNMP | UDP 161 | SNMPv1/v3 | Diagnostics via NMS (disabled by default on 8.3) |
| NTP | UDP 123 | NTP | Time synchronization (optional) |
LOGO!Soft Comfort V8.3.1 uses port 10005 for the bulk of its transfer operations and port 102 for the S7 read/write used during online mode. A failed transfer with the dialog "Cannot connect to LOGO!" or "Connection interrupted during write" indicates either port 10005 or port 102 is being filtered, blocked, or held by another process.
2. Symptom Matrix
Before applying any fix, classify the failure mode. Each row in the matrix below corresponds to a distinct root-cause family.
| Observed behavior | Likely root cause | First action |
|---|---|---|
| LSC shows all LOGO! devices, "Go Online" succeeds, but transfer fails immediately | Duplicate IP or DHCP lease collision | arp -a and router DHCP table inspection |
| Network scan returns the new LOGO! but list flickers or shows old entry | BM still configured from prior subnet / 169.254.x.x link-local | Reset BM via front-panel menu or 6ED1052-xCC08 web UI |
| LSC reports "Demo mode" watermark after upgrade | LSC license not transferred from V7.x | Verify License Key in Help > About; re-authorize |
| Connection succeeds, then drops mid-transfer with timeout >30 s | Firewall or antivirus pattern-match on LSC.exe | Disable Windows Defender Controlled Folder Access; add LSC inbound/outbound rules |
| Direct crossover/point-to-point works, LAN fails | Managed switch blocking multicast, port security, or VLAN mismatch | Move BM to access port, disable 802.1X for LOGO! MAC |
| W10 works, W11 fails (or vice versa) | Network profile = Public; SMB/Device Discovery disabled | Set network to Private, enable Network Discovery |
3. Prerequisites for Diagnosis
- Local administrator rights on the engineering PC (required for firewall, NIC driver, and ARP cache operations).
- LOGO!Soft Comfort V8.3.1 (build 8.3.1.0 or later; verify via Help > About).
- LOGO! 8.3 BM firmware 1.83.02 (verify on the BM display:
Menu > Diagnostics > Firmware, or via the web UI athttps://<IP>:8443). - Known-good patch or crossover cable (Cat 5e or better).
- A spare unmanaged 100 Mbit/s switch for isolation tests.
- Static IP plan for the LOGO! network (out-of-DHCP-pool).
4. Step-by-Step Diagnostic Procedure
Step 4.1 — Validate LOGO! 8.3 IP Address
Open the BM display and navigate Menu > Network > IP Address. Note the four octets and the subnet mask (default: 255.255.255.0). Confirm:
- The address is outside the router's DHCP pool (typically a router issues 192.168.0.100–192.168.0.254; place LOGO! in 192.168.0.2–192.168.0.99).
- No other LOGO! shares the same address. Run on the PC:
If the MAC returned is not the Siemens MAC (prefix 00-0E-8C or similar), a duplicate exists.arp -a | findstr "<IP-of-LOGO>"
Step 4.2 — Disable DHCP on the BM
On the BM display: Menu > Network > DHCP > No. Repeat for each LOGO! 8.3 BM on the segment. The DHCP state is volatile across BM power-cycles only if the firmware was upgraded mid-session; perform a power-cycle after toggling to ensure the new state is committed to flash.
Step 4.3 — Verify Subnet Consistency
Every device that must communicate must share the same subnet mask. A common field error is a LOGO! at 192.168.0.10/24 and a PC at 192.168.1.20/24 — both fall in 192.168.x.x and pass naive visual inspection but are on different Layer 3 networks.
On the PC, run:
ipconfig /all
Compare the PC's IPv4 address, subnet mask, and default gateway against the LOGO! settings. All three must be consistent across the engineering PC and every LOGO! BM that must be reached.
Step 4.4 — Test Point-to-Point Connectivity
- Disconnect the LOGO! 8.3 BM from the plant LAN.
- Connect the BM directly to the PC using a patch cable (modern PCs auto-negotiate MDI/MDIX; no crossover required).
- Assign the PC a static address in the same subnet, e.g. 192.168.0.50/24.
- Ping the LOGO!:
A successful round trip with TTL ~64 confirms Layer 2/3 reachability independent of switches, routers, and DHCP.ping 192.168.0.10
If the ping fails point-to-point, the issue is at the BM or PC NIC — proceed to Step 4.5. If the ping succeeds point-to-point but fails on the LAN, the issue is at the switch or router — proceed to Step 4.6.
Step 4.5 — Reset LOGO! 8.3 to Factory Defaults
Hold the ESC and OK buttons on the BM during power-up. The display will prompt Reset to factory defaults?. Press OK to confirm. This clears IP, subnet, DHCP, web-server passwords, and program storage. Reapply the IP configuration after the reset. The BM will reboot in ~30 s.
https://<IP>:8443 > Tools > Backup.
Step 4.6 — Inspect Managed Switch / Router
If point-to-point is healthy but LAN is broken, the managed switch or router is the suspect. Verify:
- Port security: Disable 802.1X authentication or pre-register the BM MAC in the allowed-MAC table.
- VLAN membership: The BM port and PC port must be in the same VLAN (or VLAN trunking must pass the BM's VLAN tag).
- Multicast / IGMP snooping: LSC discovery uses a limited broadcast. Excessive IGMP snooping on some HP/Aruba switches has been observed to drop the LSC probe packet.
- ACL / Firewall rules: Block on TCP 10005 is rare but exists on locked-down industrial firewalls.
Step 4.7 — Validate Windows Network Profile
Windows 10 and Windows 11 default to the Public network profile on first connection to a new SSID or wired segment. The Public profile blocks inbound discovery and disables file/printer sharing. Open Settings > Network & Internet > Ethernet and confirm the profile reads Private. Also verify:
Get-NetFirewallProfile -Name Public | Select Enabled, DefaultInboundAction
Get-NetFirewallProfile -Name Private | Select Enabled, DefaultInboundAction
The Private profile inbound action should be NotConfigured or Allow; the Public profile should remain Block.
Step 4.8 — Configure Windows Firewall Rules for LSC
Even with firewall fully disabled, third-party security products (Symantec, McAfee, Trend Micro, Kaspersky) re-enable protection at the NDIS level. Open wf.msc and create two explicit rules:
- Inbound rule: Allow TCP 10005 — program path
%ProgramFiles%\Siemens\LOGOComfort_V8\LOGOComfort.exe. - Inbound rule: Allow TCP 102 — same program path.
If using a third-party endpoint protection suite, add LSC and its dependent s7otbxdx.dll process to the application allow-list. A common field symptom is the firewall disabled in Windows Defender but active in the third-party product, producing the same transfer failure.
5. LOGO!Soft Comfort V8.3.1 License Validation
The most overlooked cause of "connection seems to work but won't commit" is a license downgrade. LOGO!Soft Comfort V7.x full licenses do not auto-migrate to V8.x; they must be re-activated via the Siemens License Server or the License Key USB stick that shipped with the V7.x purchase.
Verify license state
- Open LSC V8.3.1.
- Click
Help > About LOGO!Soft Comfort. - Inspect the line "License:" — it must read Full Version, not "Trial" or "Demo".
- Click "Activate License" if the field shows "Not Activated". Provide the license key from the original V7.x Certificate of License (CoL) or the License Key USB stick.
If the V7.x install was a demo, the upgrade to V8.x is also a demo. Demo builds of LSC can browse the network and enter online mode but cannot download programs to a BM with firmware > 1.82.00. The BM display will show STOP after the transfer attempt because the program was rejected at the BM level (BMs reject non-licensed program images).
6. Program Transfer Procedure (Verified)
- Open the program in LSC V8.3.1.
- Click
Tools > Transfer > PC → LOGO!(or press Ctrl+D). - Select the target BM from the dialog. The IP, BM type, and firmware are displayed. If the firmware shows 1.83.02 and the program is older, LSC will offer to recompile — accept.
- Choose the transfer mode: Stop LOGO! (RUN → STOP → RUN). This is the safe path. The other option, RUN → RUN, requires the program signatures to be byte-identical except for variable values.
- Click "Transfer". A progress bar appears; the BM display reads
PC<->LOGO!. Transfer of a typical 200-block program completes in 5–15 s. - Confirm with
OKon the BM display when prompted, then click "Start LOGO!" in LSC.
7. Web Server Verification (Alternate Path)
If LSC continues to refuse connection despite the fixes above, validate end-to-end IP reachability via the LOGO! web UI:
- Open a browser and navigate to
https://192.168.0.10:8443(replace IP with the BM's actual address). - Accept the self-signed certificate warning.
- Default credentials: user
LOGO, passwordLOGO(factory default; change on first login via the Web UI). - Inspect the Diagnostics page — note any active error codes. Common 8.3 firmware 1.83.02 codes:
| Web UI diagnostic | Meaning | Action |
|---|---|---|
| "Ethernet link: Down" | Physical cable/port fault | Replace cable, try another switch port |
| "IP conflict detected" | Duplicate IP on segment | Reassign static IP outside DHCP pool |
| "Firmware mismatch" | BM firmware incompatible with LSC build | Update BM firmware via SD card |
| "Web server disabled" | Web UI disabled via LSC configuration | Re-enable: Menu > Webserver > On
|
If the web UI loads but LSC still fails, the S7/LSC protocol path (port 102/10005) is broken while the HTTPS path (port 8443) is healthy — strongly indicating a firewall or third-party security product block.
8. Firmware Compatibility Matrix
| LOGO! 8.3 BM | Firmware | Minimum LSC | Recommended LSC |
|---|---|---|---|
| 6ED1052-1BA08-0BA1 (BM 230RCE) | 1.83.02 | V8.3.0 | V8.3.1 |
| 6ED1052-1MD08-0BA1 (BM 24CE) | 1.83.02 | V8.3.0 | V8.3.1 |
| 6ED1052-2BA08-0BA1 (BM 230RCEo) | 1.83.02 | V8.3.0 | V8.3.1 |
| 6ED1052-2CC08-0BA1 (BM 24RCEo) | 1.83.02 | V8.3.0 | V8.3.1 |
| 6ED1055-4MH08-0BA1 (TDE) | 1.83.02 | V8.3.0 | V8.3.1 |
| 6ED1052-1BA08-0BA2 (newer BM revision) | 1.84.x | V8.4.x | V8.4.x |
9. SD Card Firmware Update Procedure
- Obtain the firmware file
LOGO8_3_BM_V18402.zipfrom the Siemens Industry Online Support portal. - Extract the
.updfile to a microSD card (FAT32, <32 GB recommended). - Power off the BM, insert the SD card.
- Hold the OK button during power-on. The display shows the firmware file from the SD card.
- Press OK to confirm. The update runs in ~90 s. Do not interrupt power.
- After the BM reboots, verify firmware on the display or via the web UI.
10. Verification Checklist
| Check | Expected | Command / location |
|---|---|---|
| Ping BM | Reply <1 ms | ping <IP> |
| ARP entry | Siemens MAC OUI | arp -a |
| Web UI | Status page loads | https://<IP>:8443 |
| LSC network scan | BM listed with firmware 1.83.02 | LSC > Tools > Network Scan |
| Online monitoring | Inputs/outputs update live | LSC > Tools > Go Online |
| Program transfer | 5–15 s, BM returns to RUN | Ctrl+D |
| BM display | RUN (green) or STOP (red) as configured | Physical BM |
| Retention | Counters/timers persist across transfer | Check via Web UI status |
11. Edge Cases and Field-Proven Caveats
- Multiple NICs: PCs with both Ethernet and Wi-Fi active can route LSC traffic out the wrong NIC. Disable Wi-Fi during transfer or set the NIC metric so the wired interface is preferred.
- VPN client: Cisco AnyConnect, FortiClient, and Zscaler insert virtual NICs that can intercept TCP 10005. Disconnect the VPN before transferring.
- Docker / WSL: Hyper-V virtual switches and WSL2 vNICs can claim the 192.168.0.0/24 range, blocking LSC. Disable Hyper-V WSL integration or set the LSC to use a specific NIC.
-
Dual-stack IPv6/IPv4: Some LSC builds attempt IPv6 first; if IPv6 routing is broken, transfer hangs. Force IPv4 with the LSC option
Use IPv4 onlyinTools > Options > Connection. - Time skew: LSC rejects connections from PCs whose clock is >5 minutes off the BM clock. Synchronize both to NTP before commissioning.
12. Frequently Asked Questions
Why does LOGO!Soft Comfort see my LOGO! 8.3 in the network list but fail to download the program?
LSC uses a lightweight broadcast/UDP discovery that the BM answers even when the S7/LOGO protocol path is blocked. The download fails because TCP ports 102 and 10005 are filtered, the BM has a duplicate IP, or LSC is running in demo mode. Validate with the matrix in Section 2 and the firewall rules in Section 4.8.
Do I need a new license to upgrade from LOGO!Soft Comfort V7 to V8.3.1?
If V7 was a full (paid) version, the V7 license key re-activates V8.3.1 via the Siemens License Server. If V7 was a demo, V8.3.1 will also run as demo and refuse to write a usable program image to firmware 1.83.02. Demo mode is the single most common cause of "transfers but BM rejects" symptoms.
How do I confirm a duplicate IP is causing the connection failure?
On the PC, run arp -a and compare the MAC address returned for the LOGO! IP against the MAC printed on the BM housing (format 00-0E-8C-xx-xx-xx for most Siemens Ethernet LOGO! BMs). A mismatch means another device holds the same IP. Reassign the BM to a free address outside the router DHCP pool, then disable DHCP on the BM via the front-panel menu.
Can I mix LOGO! 7 and LOGO! 8.3 in the same LSC V8.3.1 project?
No. A project targets a single BM family. LOGO! 7 and LOGO! 8.3 use different instruction sets and memory maps. Open separate projects for each family. LSC V8.3.1 can scan both on the network but only one BM type per opened project.
What is the correct firewall configuration for LOGO!Soft Comfort on Windows 10/11?
Allow inbound TCP 102 and inbound TCP 10005 for the LSC executable (default path %ProgramFiles%\Siemens\LOGOComfort_V8\LOGOComfort.exe). Verify both Private and Domain profile rules are enabled. Public profile should remain blocked. Many third-party endpoint products re-enable filtering even when Windows Defender is disabled — explicitly allow LSC in those products as well.
Why does the BM display "PC<->LOGO!" and freeze during transfer?
The BM is waiting for LSC to acknowledge a firmware/program version check. This usually indicates a baud-rate or timeout mismatch on the S7 path. Reduce the LSC transfer timeout to 60 s (Tools > Options > Transfer), disable any third-party security product, and confirm the PC clock is within 5 minutes of the BM clock. Persistent freeze after firmware mismatch requires a firmware downgrade via SD card.