After the correct reference circuit is wired and each drive is configured for the intended command source, every motor can follow its own local potentiometer or a common remote speed command without overloading an analog input. The number that matters is the drive output current relative to motor current; commanded frequency sets speed, but current produces heat.
Wrong fixes and their failure modes
| Attempt | Why it fails | Correct check |
|---|---|---|
| Copy another inverter's terminal diagram | Analog-input terminals, reference supplies, commons, and digital inputs are not standardized across drives. | Use the terminal diagram and parameter list for the installed inverter. |
| Connect one potentiometer directly to several drives | Paralleled reference supplies can oppose each other, and the combined input load can distort the command. | Use one designated supply with verified loading, an isolated signal splitter, or a communications command. |
| Change wiring without selecting the analog reference | The drive may still take its speed command from its keypad, preset speeds, or communications interface. | Read the active command-source and frequency-reference selections. |
| Use one inverter for several independently controlled motors | A single inverter produces one output frequency, so connected motors cannot receive independent speed commands. | Use one inverter per motor when independent speed control is required. |
| Raise frequency to cure low-speed torque | More commanded speed does not correct undersized equipment, excessive load, poor motor data, or inadequate low-speed cooling. | Measure output current and compare it with the motor and drive ratings. |
Frequency, current, and thermal load
An inverter varies motor speed primarily by changing output frequency while controlling voltage and current according to its control method. The potentiometer does not carry motor power. It creates a low-power reference that the analog input converts into a frequency command.
Motor load determines current. Excessive current heats motor windings and inverter power devices even when the speed reference appears correct. At low speed, a shaft-mounted motor fan also moves less cooling air. This is heat, not logic: a stable frequency command cannot compensate for inadequate cooling or sustained overload.
| Quantity | Limit or decision | Where to read it |
|---|---|---|
| Motor rated current | Use the motor nameplate value when entering motor data and selecting protection. | Motor nameplate |
| Drive output-current rating | Match it to the motor and duty; motor power alone is not the final sizing quantity. | Drive nameplate or datasheet |
| Actual output current | Investigate sustained operation near or above the permitted duty rating. | Drive monitor or measured output data |
| Commanded frequency | Constrain minimum and maximum values to the machine's safe operating range. | Drive frequency monitor and limit parameters |
| Analog reference | Confirm that minimum, maximum, polarity, and signal type match the selected input. | Analog-input monitor and inverter manual |
| Motor temperature | Rising temperature at low speed indicates a load or cooling problem, not necessarily a reference fault. | Installed temperature protection or approved measurement method |
Single-motor reference circuit
The drive manual defines the actual terminals. A typical potentiometer circuit uses the inverter's reference source, analog input, and analog common:
Drive reference source ─── potentiometer high side
Drive analog common ─── potentiometer low side
Drive analog input ─── potentiometer wiper
This diagram describes signal function only. Read the manual for the required potentiometer resistance, permitted input type, reference-source loading, shielding, and terminal designations. Never apply external control voltage to a drive-provided reference output; equipment damage can result.
Route analog wiring away from motor leads, braking conductors, contactor coils, and other switching circuits. Use the cable and grounding practice specified by the drive manufacturer. Noise on the reference usually appears as an unstable commanded frequency rather than as a mechanical load change.
Local and common remote control
Independent local adjustment requires one speed reference per motor and normally one inverter per motor. Each inverter receives its own potentiometer signal and produces its own output frequency:
Local potentiometer 1 ── analog reference ── Inverter 1 ── Motor 1
Local potentiometer 2 ── analog reference ── Inverter 2 ── Motor 2
Local potentiometer 3 ── analog reference ── Inverter 3 ── Motor 3
A common remote command must distribute the same setpoint without electrically tying incompatible reference sources together. Standard architectures include an isolated multi-output signal splitter, separate controller analog outputs, or a supported communications network. Check the source's output capability against the combined input impedance when a manufacturer permits one analog source to feed multiple inputs.
Local/remote selection needs two separate decisions: the run-command source and the speed-reference source. A selector can change both, but its contacts or controller logic must drive the designated control inputs; it must not switch inverter output conductors between running motors.
LOCAL: local run command + local potentiometer
REMOTE: supervisory run command + distributed master reference
Define the behavior for a lost remote signal before commissioning. Use the drive's documented response choices and machine risk assessment rather than assuming that a missing reference always means zero speed.
Configuration and commissioning procedure
- Record each motor's nameplate data, rated current, intended speed range, load type, and required acceleration and stopping behavior.
- Identify the inverter's reference source, analog input, analog common, run inputs, and any local/remote selection inputs from its own manual.
- Confirm the permitted potentiometer resistance and analog signal mode. Set any hardware selector and software parameter to the same input type.
- Wire one local potentiometer to each independently controlled inverter. Keep control wiring separated from power wiring as directed by the manufacturer.
- Select the external analog input as the frequency-reference source. Select the required local or remote run-command source separately.
- Configure minimum frequency, maximum frequency, acceleration, deceleration, and signal-loss behavior for the machine.
- Enter the motor data requested by the inverter and configure motor overload protection for each motor.
- Test initially with the mechanical process in a safe unloaded or lightly loaded condition. Verify rotation before applying normal production load.
- For common remote control, connect the approved distribution device or communications link and confirm that each inverter maps the master command to the intended frequency range.
Verification and recurring pitfalls
Turn each local potentiometer slowly from minimum to maximum while watching the drive's analog-input and commanded-frequency monitors. Both values should change smoothly and in the correct direction. A full command that produces only part of the intended frequency range indicates scaling, input-mode, supply-loading, or wiring trouble.
Run every motor through its operating range under realistic load. Record commanded frequency, actual output frequency, output current, and motor temperature trend. If current rises excessively, inspect the mechanical load, acceleration demand, motor data, drive sizing, and low-speed cooling before changing the speed-reference circuit.
Switch between local and remote modes at a controlled speed and confirm the run source, reference source, and transfer behavior. An unexpected speed step means the two references differ or the transfer logic lacks the required handoff behavior. Verify each inverter separately because identical commands do not guarantee identical scaling.
Frequently asked questions
Can I connect a potentiometer directly to an inverter?
Yes, when the inverter manual identifies a compatible reference source, analog input, common, and potentiometer resistance. Configure that analog input as the active frequency reference.
Can I use one potentiometer for several inverters?
Only when the source can drive the combined input load and the manufacturer permits the connection. An isolated signal splitter, separate controller outputs, or communications usually provides clearer electrical separation.
Does one inverter control several motors at different speeds?
No. Motors connected to one inverter receive the same output frequency; independent speed commands normally require one inverter per motor.
Can I keep troubleshooting if the terminal functions are unclear?
Stop if the manual does not clearly identify the reference source, analog common, input type, loading limits, or local/remote parameters. Record the inverter identification, wiring, parameter settings, and monitor readings, then escalate to the manufacturer's official technical support channel before applying control power.