How Do You Meter and Log Two 4-Inch Water Lines Correctly?

Karen Mitchell6 min read
Data AcquisitionOther ManufacturerTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

The operator sees two separate water streams, each around 500–700 GPM, but has no combined plant total or time-based consumption report. Treat the display as the end of a signal chain: meter element, output signal, logger input, scaling, total calculation, and report interval. Check that chain in order.

What must the operator see?

Define the required screen values before selecting hardware. A report of total water used during a shift needs accumulated volume. A live display needs flow rate. These are different measurements even when one instrument supplies both.

Required value Reading or setting Effect
Line 1 live flow Rate signal from meter 1 Shows instantaneous or sampled GPM
Line 2 live flow Rate signal from meter 2 Shows instantaneous or sampled GPM
Combined live flow Line_1_Rate + Line_2_Rate Shows plant inlet rate
Individual volume Pulse count or integrated rate for each line Preserves line-by-line usage
Combined volume Line_1_Total + Line_2_Total Provides the reportable plant total

If the operator needs only consumption totals, pulse outputs provide the simplest data path. If the screen must also show current GPM, collect the rate signal as well. Continue by checking whether the meter can measure the actual operating range.

Does the meter cover both the pipe and flow range?

The stated operating point is a nominal 4-inch line carrying approximately 500–700 GPM at 20 PSI. Select from the meter manufacturer’s sizing table using the pipe’s actual inside diameter and material, not nominal size alone. Inside diameter determines velocity, and the transducer must operate within its specified velocity range.

Calculate velocity only after reading the inside diameter from the pipe specification:

Velocity = volumetric flow / internal flow area

Use consistent units. Check both 500 GPM and 700 GPM so the entire expected range lies between the meter’s minimum and maximum velocity limits. If either endpoint falls outside the range, change the meter size, technology, or installation arrangement before selecting the logger.

The 20 PSI value describes process pressure at the stated location; it does not define allowable meter pressure, available pressure loss, or differential pressure across a meter. Read the meter’s pressure rating and pressure-loss data separately. Also inspect the proposed relationship to the city meter. “Piggyback” can describe several physical arrangements, but it is not enough to specify an instrument. Record whether the new device will be inline, inserted through the pipe wall, or mounted externally, then check straight-run, orientation, accessibility, and upstream disturbance requirements in its installation data.

Data Industrial 220B flow transducers and the 1500 rate/totalizer were identified as candidate devices. Confirm their current pipe, velocity, output, pressure, and mounting specifications before treating either model as a fit.

Is the meter output pulse, 4–20 mA, or both?

Read the output terminals and configuration sheet for each selected meter. Totalized volume is commonly represented by dry-contact pulses, with a configured quantity such as gallons or cubic feet per pulse. Flow rate is commonly represented by 4–20 mA.

Output found Logger input required Next decision
Dry-contact pulse Counter input compatible with the contact Read the volume-per-pulse factor
4–20 mA Analog current input Read the engineering range assigned to 4 and 20 mA
Both outputs Counter plus analog input per line Use pulses for billing-style totals and analog values for live rate

A tag can have the correct name while its binding points to the wrong input channel or applies the wrong scale. For a pulse input, configure Volume = Pulse_Count × Volume_Per_Pulse. For a rate input, map the measured current to the meter’s configured flow range. Do not infer that range from the expected 500–700 GPM process flow; read it from the meter configuration.

Check pulse characteristics against the logger input specification, including contact type, maximum pulse frequency, and minimum detectable pulse duration. Those exact values must come from the selected meter and logger documentation. A mismatch can undercount volume even while the live rate appears reasonable.

Can the logger combine and report both meters?

The logger needs two independent input channels of every required type. For totals alone, it must count and retain two pulse streams. For rate and totals, it must also acquire two analog values or obtain rate from another supported interface.

Setting Location Effect
Pulse factor Meter or logger channel Converts counts to volume
Analog range Meter and logger channel Converts current to GPM
Combined rate expression Logger software Adds simultaneous line rates
Combined total expression Logger software Adds individual accumulated volumes
Logging interval Logger configuration Sets time resolution of stored rate data
Report boundaries Reporting software Defines shift, day, or other requested period

HOBO was identified as a possible data-logger source, but select the logger by input compatibility, counter retention, storage capacity, timestamp handling, and reporting functions. Confirm that counters survive a power interruption or that the software can reconstruct totals without losing pulses.

Which totalizing method should you use?

Two configurations can produce valid combined consumption. Counting calibrated volume pulses is preferred when the meters provide them because every accepted pulse represents a defined volume. Integrating sampled 4–20 mA rate data also works, but accuracy then depends on the sample interval, scaling, timestamp quality, and treatment of missing samples.

Keep individual totals and calculate the combined result afterward:

Combined_Total = Line_1_Total + Line_2_Total

Do not combine the electrical pulse wires into one counter input. Separate channels preserve diagnostics and prevent simultaneous pulses from being lost. Likewise, store both individual rates before calculating Combined_Rate. This makes a failed meter, broken wire, frozen input, or scaling error visible instead of hiding it inside one plant value.

When reports cover set time periods, calculate usage from the difference between boundary totals: Period_Usage = End_Total − Start_Total. Define how the software handles counter resets, rollover, missing records, and clock changes before relying on automated reports.

How do you configure and verify the complete chain?

  1. Record pipe material, actual inside diameter, installation arrangement, normal flow range, process pressure, and available mounting length for each line.
  2. Check 500 GPM and 700 GPM against the selected transducer’s published velocity range. Check pressure rating and installation requirements independently.
  3. Choose a pulse output for accumulated volume. Add 4–20 mA when the operator also needs live rate or rate trending.
  4. Wire each meter to its own logger channel. Match the counter input to the pulse output and the analog input to the current loop requirements shown in the device documentation.
  5. Enter each meter’s actual volume-per-pulse factor and analog range. Bind the display tags to the corresponding physical channels.
  6. Create separate tags for line rates and totals, then calculate combined values by addition. Configure storage and the required report boundaries.
  7. Run one line at a time. Confirm that only its associated rate and total tags change. Repeat on the other line.
  8. Run both lines and compare the displayed combined rate with the sum of the two displayed line rates. Compare combined period usage with the sum of the two individual period usages.

FAQ

What happens if I use only the 4–20 mA outputs?

You can display and trend GPM, then calculate volume by integrating the sampled rate. The result depends on correct scaling, sample timing, and handling of missing data; use calibrated pulses when dependable accumulated volume is the priority.

What happens if both meter pulse wires share one counter input?

Simultaneous or overlapping pulses can be missed, and the combined signal hides which line produced each count. Connect each dry-contact pulse output to a separate counter and add the two calculated totals in software.

What happens if the combined total does not match the two line totals?

Check channel binding, volume-per-pulse factors, counter resets, report start and end timestamps, and lost-pulse indicators. Finish by verifying that Combined_Total = Line_1_Total + Line_2_Total at the same timestamp.

Back to blog