IM151-8 PN/DP to S7-300: Configuring PUT/GET PROFINET

David Krause17 min read
Industrial NetworkingSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

IM151-8 CPU PN/DP to S7-300 PN/DP: Resolving AG_SEND Status 8093 with PUT/GET over PROFINET

This technical reference documents the field-validated procedure for establishing PROFINET I/O data exchange between a SIMATIC ET 200S IM151-8 CPU PN/DP (order number 6ES7151-8AB01-0AB0, firmware V3.x) and a SIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0). The original failure mode is well documented: the IM151-8 enters SF (System Fault), the diagnostic buffer logs an I/O access error, reading event, and FC5 AG_SEND returns status 0x8093 with DONE=0, ERROR=1. The root cause is a connection-type mismatch: AG_SEND/AG_RECV cannot be bound to an S7 connection. The remedy is to substitute the S7-300 / ET 200S compatible PUT/GET SFBs, or alternatively the T-blocks (USEND/URCV, BSEND/BRCV) over an S7 connection, or alternatively the Open TCP/IP blocks from the SIMATIC NET CP 300 library when no S7 connection is configured in NetPro.

Critical constraint: The IM151-8 PN/DP is an S7-300-class CPU. The SIMATIC_NET_CP → CP 300 library contains both SFBs (S7-400 only) and FBs (S7-300 / IM151-8). You must use the FB variants — for example FB15 PUT and FB14 GET — never the SFB versions. The CP 300 library is installed with STEP 7 V5.5 / STEP 7 Professional and lives at SIMATIC_NET_CP\CP 300\Library\Standard Library.

1. Problem Statement

The reported failure on an IM151-8 PN/DP master station appears as follows after FC5 AG_SEND is called from OB1:

  • SF LED on the IM151-8 illuminates solid red.
  • Diagnostic buffer of the IM151-8 lists "I/O access error, reading" (event ID 0x3924 / 0x39xx family), pointing at the LADDR of the AG_SEND L-area.
  • Removing the call of the AG_SEND wrapper (e.g., a user FC90) from OB1 clears the SF immediately.
  • FC5 returns STATUS = W#16#8093 with DONE = FALSE, ERROR = TRUE.

The temptation is to assume the LADDR is wrong and to retest the PROFINET port base address (typically 2036*–2047* for an integrated PROFINET IO controller on an IM151-8). The actual root cause sits one layer above: the connection type bound to FC5/FC6 in NetPro.

2. Root Cause: Connection-Type vs. Comm Block Compatibility

SIMATIC S7 communication blocks are not interchangeable across connection types. The STEP 7 help text on "Common Parameters of the SFBs/FBs and SFC/FC for the S7 communication" defines a hard matrix:

Block-to-Connection-Type Compatibility Matrix (S7-300 / IM151-8 class)
Block family Block names S7 conn. FDL ISO Transport ISO-on-TCP TCP UDP
AG_L FC5 AG_SEND, FC6 AG_RECV
T-blocks FB8 USEND, FB9 URCV, FB12 BSEND, FB13 BRCV
GET/PUT FB14 GET, FB15 PUT
CPU-CPU control FB19 START, FB20 STOP, FB21 RESUME, FB22 STATUS, FB23 USTATUS
Open TCP/IP (CP 300 FB lib) FB63 TSEND, FB64 TRCV, FB65 TCON, FB66 TDISCON, FB67 TUSEND, FB68 TURCV No NetPro connection required; configured via TCON parameters

The original NetPro configuration in the failure case used an S7 connection. The AG_SEND wrapper is therefore referencing a logical connection that has no AG_SEND/AG_RECV endpoint. The PROFINET IO controller (port 3, base address 2044*) is unrelated to the S7 connection target; it is an I/O area, not a communications socket. The CPU's online diagnostics display the S7 connection establishment attempt against the wrong subsystem and the call is rejected, which surfaces as the I/O access error, reading on the diagnostic buffer because the input area the call tries to read (the LADDR) belongs to the PROFINET IO image, not to the user data area.

3. Decoding Status 0x8093

Status word 0x8093 for FC5/FC6 (and equivalents) is documented in the STEP 7 help index under STATUS parameter of AG_SEND / AG_RECV. The high byte 0x80 indicates an AG_SEND-class status; the low byte 0x93 is the error subtype:

FC5 AG_SEND status 0x8093 — field meaning
Status DONE ERROR Meaning
0x8093 0 1 The configured connection does not exist, the connection is not an FDL/ISO/ISO-on-TCP/TCP/UDP type that AG_SEND supports, or the LADDR / IO area is inconsistent with the partner assigned in NetPro. Check connection type in NetPro first; do not change the LADDR before re-validating connection type.

Related AG_SEND statuses the field engineer should also recognise on the IM151-8:

AG_SEND / AG_RECV status quick reference (excerpt)
Status (hex) Class Interpretation
0x0000 OK Job complete without error.
0x7000 Info No job active; call is idle.
0x7001 Info Job active, first call with REQ=1.
0x7002 Info Job active, follow-up call.
0x8080 Error Internal error in AG_SEND (firmware bug or memory); cycle power and re-download.
0x8081 Error Connection ID unknown to AG_SEND (NetPro mismatch).
0x8090 Error Specified LADDR / IO area does not exist in the S7-300 IO image.
0x8093 Error Connection type not suitable for AG_SEND — this is the reported failure mode.
0x80A0 Error Negative acknowledgement from partner CPU; partner received data but rejected it (e.g. wrong length, access protection).
0x80B0 Error Physical link down — check PROFINET cable, port LED on IM151-8, switch port.
0x80C0 Error Temporary resource shortage; reduce call rate or remove concurrent AG_SEND calls.
0x80C1 Error Total length of the send data exceeds the configured AG_SEND buffer (LEN parameter > configured max).
0x80D0 Error Send job aborted because the connection was terminated.
0x80D1 Error Send job aborted because the partner initiated a stop / reset.

The diagnostic buffer entry "I/O access error, reading" observed on the IM151-8 is a synchronous TZ-1 fault generated by the IM151-8 firmware when the AG_SEND block tries to read the LADDR's process image and detects that the LADDR is part of the PROFINET IO image rather than the user I area. The OB121 (programming error) or OB122 (I/O access error) handler is invoked; if neither OB is loaded, the CPU goes to STOP. Loading OB122 (and OB121) is a standard hardening step for any IO-controller on PROFINET.

4. LADDR Selection — Why the PROFINET Port Base Address Is Wrong

On the IM151-8 PN/DP, the three PROFINET ports of the integrated IO controller (X1, X2, X3) are managed as one logical PROFINET device with a single IO base address range. In a typical STEP 7 / HW Config view the user sees:

Typical IM151-8 PN/DP I/O address map (example slotting)
Slot Module Input address Output address Diagnostic address
0 IM151-8 PN/DP head 2036* 2036* 2040*
1 PN-IO-1 (port subgroup) 0..15 2044*
2 PN-IO-2 2045*
3 PN-IO-3 2046*
X1 (combined) PN-IO combined 2047*

Addresses suffixed with * indicate a diagnostic address slot, not a process-data slot. Passing 2044 or 2047 (0x7FC / 0x7FF) as LADDR to FC5 is structurally invalid: the LADDR parameter of AG_SEND expects the start address of the user I/O area in the process image, not a diagnostic address. This compounds the connection-type error and is why both 2044* and 2047* "do not work". When the user later moves to PUT/GET, no LADDR is required at all — PUT/GET reference a remote DB / bit on the partner CPU, not a local I/O area.

5. Recommended Remedy: S7 Connection with PUT/GET (FB14 / FB15)

For an IM151-8 CPU talking to an S7-300 CPU over the integrated PROFINET port, the lowest-friction, best-supported configuration is:

  1. An S7 connection defined in NetPro from the IM151-8 (client) to the S7-300 CPU 315-2 PN/DP (server).
  2. Use of the FB15 PUT and FB14 GET instances from the SIMATIC_NET_CP → CP 300 → Standard Library.
  3. Each block instance requires a unique connection ID matching the NetPro connection entry.
  4. No LADDR is needed; PUT/GET carry the data directly to / from a remote DB on the partner CPU.

5.1 NetPro connection entry (IM151-8 side)

Open the IM151-8 station in NetPro, right-click the CPU and select Insert New Connection. Choose the partner CPU 315-2 PN/DP and connection type S7 connection. The resulting connection record carries:

  • Local ID: e.g. 1 (decimal), 1-based; this becomes the ID input of PUT/GET.
  • Partner IP: 192.168.0.x as set on the S7-300 CPU's PROFINET interface (X2).
  • Local end point: IM151-8 PROFINET interface (X1 / X2 / X3; the connection is bound to the CPU, not the port — any port can carry the S7 connection as long as the IP route is correct).
  • Block parameters: Active connection establishment = yes on the IM151-8 side.

5.2 Calling FB15 PUT in OB1 (IM151-8)

// FB15 PUT — IM151-8 sends a 20-byte block to S7-300 DB100
// Instance DB: DB115 ("iPUT")
// Connection ID: 1 (must match NetPro)

CALL  "PUT" , DB115
  REQ     := M10.0          // Edge-triggered start bit
  ID      := W#16#1         // NetPro connection ID (decimal 1)
  DONE    := M20.0
  ERROR   := M20.1
  STATUS  := MW22
  ADDR_1  := P#DB100.DBX 0.0 BYTE 20   // Remote: S7-300 DB100, bytes 0..19
  SD_1    := P#DB200.DBX 0.0 BYTE 20   // Local : IM151-8 DB200, bytes 0..19
  LEN     := 20

5.3 Calling FB14 GET in OB1 (IM151-8)

// FB14 GET — IM151-8 reads 32 bytes from S7-300 DB110 into local DB210
// Instance DB: DB114 ("iGET")
// Connection ID: 1 (must match NetPro)

CALL  "GET" , DB114
  REQ     := M11.0          // Edge-triggered start bit
  ID      := W#16#1
  DONE    := M21.0
  ERROR   := M21.1
  STATUS  := MW24
  ADDR_1  := P#DB110.DBX 0.0 BYTE 32   // Remote: S7-300 DB110, bytes 0..31
  RD_1    := P#DB210.DBX 0.0 BYTE 32   // Local : IM151-8 DB210, bytes 0..31

For a 1-to-N layout (one IM151-8, multiple S7-300 stations) define one NetPro S7 connection per partner and instantiate one FB14/FB15 DB per connection, each with its own ID. The connection ID is the integer shown in the NetPro connection properties, not a hash of the partner IP.

6. Alternative 1: T-Blocks (USEND/URCV, BSEND/BRCV) on the S7 Connection

If the application requires handshake-driven, segmented data transfer (e.g. recipes or large process records), the T-blocks from the same CP 300 library are valid on an S7 connection:

T-block selection on S7 connection (S7-300 / IM151-8)
Block Direction Max user data / call Use case
FB8 USEND Send, unacknowledged ≤ 440 bytes Broadcast-like, low overhead, no partner ACK.
FB9 URCV Receive, unacknowledged ≤ 440 bytes Partner of USEND.
FB12 BSEND Send, segmented, acknowledged ≤ 65534 bytes Large data with flow control.
FB13 BRCV Receive, segmented, acknowledged ≤ 65534 bytes Partner of BSEND.

The call signature uses the same ID parameter as PUT/GET (NetPro S7 connection ID) and uses an R_ID (DWORD) to demultiplex multiple T-block pairs on the same connection. BSEND/URCV call pattern:

CALL  "BSEND" , DB112   // IM151-8 sends 800 bytes to S7-300 DB300
  REQ    := M30.0
  ID     := W#16#1
  R_ID   := DW#16#1A2B3C4D   // Must match partner BRCV's R_ID
  DONE   := M31.0
  ERROR  := M31.1
  STATUS := MW32
  SD_1   := P#DB200.DBX 0.0 BYTE 800
  LEN    := 800

The S7-300 partner BRCV must use the same ID and the same R_ID; the S7-300 instance DB is created by the wizard or by right-clicking FB13 and choosing Instance DB in STEP 7.

7. Alternative 2: Open TCP/IP Communication Without NetPro

When no S7 connection is desired — for example, when the IM151-8 is exchanging data with a non-Siemens controller — use the Open TCP/IP blocks from the same library. The relevant FBs are FB63 TSEND, FB64 TRCV, FB65 TCON, FB66 TDISCON, FB67 TUSEND, FB68 TURCV. Configuration is purely parameter-driven via the TCON block; no NetPro entry is required. The connection parameters (partner IP, partner port, local port) are stored in the instance DB of TCON.

8. SF LED and I/O Access Error — Cleanup Procedure

After replacing AG_SEND with PUT/GET, clear the residual diagnostic state:

  1. In STEP 7, go online with the IM151-8.
  2. Open CPU → Operating Mode; the IM151-8 should already be RUN if OB122 was loaded — if not, perform a STOP → RUN transition.
  3. Open PLC → Clear/Reset and execute Clear Reset (MRES) only if the diagnostic buffer cannot be cleared online. For an I/O access error, MRES is normally not needed; deleting the offending call from OB1 is sufficient.
  4. Open the Diagnostic Buffer and confirm no new entries appear once the corrected PUT/GET calls are running.
  5. Observe the IM151-8 LEDs: SF should be off, BF (bus fault) off, RUN solid green.
Hardening tip: Load OB121 and OB122 on every IM151-8 used as a PROFINET IO controller. This converts any single I/O access error into a logged event instead of a CPU STOP. OB122 only requires a single line BE at the top; a more sophisticated OB122 can be used to set a status flag for HMIs.

9. Verification Procedure

After commissioning, validate the corrected PROFINET communication in five steps:

  1. Connection state — In NetPro, right-click the S7 connection, select Connection Status. State should read established within 1–2 s of RUN.
  2. DONE / ERROR flags — In a watch table, force REQ = TRUE on a PUT instance and confirm DONE pulses, ERROR stays FALSE, STATUS = 0.
  3. Round-trip data — Increment a counter in IM151-8 DB200.DBX0 (BYTE), write via PUT to S7-300 DB100.DBX0, then read back into IM151-8 DB210.DBX0 via GET. The GET-read value should follow the PUT-write value within 100–300 ms on a 100 Mbit/s PROFINET link.
  4. Cable and link integrity — On the IM151-8 PROFINET port LED, link/activity should flash at the S7-300 PROFINET port rate (green/amber per Siemens PROFINET LED convention).
  5. Diagnostic buffer cleanliness — After 1 h of cycling, the diagnostic buffer on the IM151-8 should contain no entries related to the S7 connection or the PUT/GET instance DBs.

10. Troubleshooting Matrix

Field-tested fault matrix for IM151-8 ↔ S7-300 PROFINET communication
Symptom Likely cause Verification Fix
SF LED on, diagnostic buffer shows "I/O access error, reading" LADDR passed to AG_SEND points at a PROFINET diagnostic address (e.g. 2044*) instead of a user I/O area Open HW Config, inspect slot 0–3 diagnostic addresses Switch to PUT/GET (no LADDR) or to T-blocks; remove LADDR from AG_SEND call
FC5 status 0x8093, DONE=0, ERROR=1 AG_SEND bound to an S7 connection (AG_SEND does not support S7 connection type) Open NetPro, inspect connection type Re-create the connection as FDL/ISO/ISO-on-TCP/TCP/UDP if AG_SEND is required; or replace AG_SEND with PUT/GET (recommended on IM151-8)
BF LED flashing, no S7 connection established Partner IP / subnet mismatch between IM151-8 and S7-300 From IM151-8 in online mode, run Accessible Nodes in STEP 7 Assign compatible subnet mask and gateway; ensure both CPUs are on the same PROFINET subnet
PUT/GET DONE=0, ERROR=1, STATUS=0x0001 Connection not yet established at the time of first REQ Check NetPro connection status, run Connection Status Gate REQ on a connection-established flag (status word of GET/PUT itself) or delay first call 2 s after RUN
PUT/GET DONE=0, ERROR=1, STATUS=0x000E Remote DB not loaded on partner, or remote DB has wrong optimised/non-optimised attribute (optimised blocks are not accessible via PUT/GET on classic S7-300 / IM151-8) Open S7-300 DB100 properties, check Optimised block access = OFF Disable optimised access on S7-300 DBs that are targets of PUT/GET; recompile and re-download
PUT/GET STATUS=0x80B0 (legacy AG) or 0x000A (PUT/GET) PROFINET cable fault, port physically down Check port LED, swap cable, use a different switch port Replace cable; verify no EMC damage; check PoE / 24 V supply if using a PoE switch
SF LED returns after first call cycle, OB122 not loaded Transient I/O access error due to startup race Open IM151-8 diagnostic buffer for OB122 trigger events Load OB122; ensure all I/O areas referenced by user code are present in the process image

11. Common Field Pitfalls

  • Optimised DBs on the S7-300 partner. PUT/GET require non-optimised (absolute-addressable) DBs on the target. S7-300/400-class CPUs do not support optimised blocks, but if the S7-300 station is later replaced with an S7-1500, the blocks must be re-engineered — PUT/GET cannot address optimised DBs on S7-1500 by symbolic name alone; use absolute offsets in the S7-1500 DBs.
  • Connection ID confusion. The connection ID in the NetPro connection table is a 16-bit integer. The ID input of PUT/GET is a WORD; do not pass the partner IP, the connection name, or the slot number.
  • SFB vs FB selection. The S7-400 SFB14/SFB15 (PUT/GET as system function blocks) are not supported on S7-300 or IM151-8. Always use the FB14/FB15 instances from the CP 300 library.
  • One REQ per call cycle, not level-triggered. PUT/GET require an edge on REQ. Holding REQ high causes only one job to start; the block does not retrigger.
  • LEN on PUT must match the byte count of the largest ADDR_1 segment. If you set LEN to 0 with ADDR_1 specified, PUT evaluates ADDR_1's byte count automatically; for a multi-segment PUT, LEN must equal the total of all ADDR_1 segments.
  • PROFINET port base address in HW Config is not a comms LADDR. Treat slot 0–X diagnostic addresses as diagnostic, not as data pointers for PUT/GET or AG_SEND.

12. Engineering Reference Summary

IM151-8 PN/DP ↔ S7-300 PN/DP — recommended engineering reference
Item Value / source
IM151-8 PN/DP order number 6ES7151-8AB01-0AB0 (firmware V3.x)
Recommended STEP 7 version STEP 7 V5.5 SP4 or STEP 7 Professional 2010 SRx with HSP for ET 200S IM151-8
Recommended connection type in NetPro S7 connection (one per partner CPU)
Recommended send/receive blocks FB15 PUT, FB14 GET (CP 300 library); FB12/FB13 BSEND/BRCV for > 440 bytes; FB8/FB9 USEND/URCV for unacknowledged data
Avoid FC5/FC6 AG_SEND/AG_RECV on S7 connection (returns 0x8093, causes SF)
LADDR (PUT/GET) Not used
Target DB requirement Non-optimised, absolute addressable, downloaded on partner
Maximum data per PUT job (single segment) 160 bytes (S7-300 / IM151-8 limit); up to 462 bytes per segment via multi-segment PUT on newer firmware
Maximum data per BSEND job 65534 bytes (segmented)
Hardening OBs OB82, OB83, OB86, OB121, OB122
PROFINET cable Cat 5e or higher, shielded, max 100 m segment

With the connection type corrected to S7 and the AG_SEND wrapper replaced by FB14/FB15 (or the T-block family), the IM151-8 establishes a clean, deterministic PROFINET data path to the S7-300 CPU 315-2 PN/DP. The SF LED clears on the next STOP→RUN transition, the diagnostic buffer stays empty, and the 0x8093 status no longer occurs because AG_SEND is no longer called.

Why does AG_SEND return status 0x8093 on the IM151-8 PN/DP?

Status 0x8093 means the connection bound to FC5 AG_SEND is not of a type AG_SEND supports. AG_SEND works only with FDL, ISO Transport, ISO-on-TCP, TCP, or UDP connections. If the NetPro connection is of type S7 connection (the default for S7-300 / IM151-8 PROFINET CPU-to-CPU), the call is rejected with 0x8093 and the diagnostic buffer logs an I/O access error because the LADDR points to a PROFINET diagnostic address rather than a user I/O area.

Which blocks should I use instead of AG_SEND between an IM151-8 and a CPU 315-2 PN/DP?

Use FB15 PUT and FB14 GET from the SIMATIC_NET_CP → CP 300 → Standard Library on an S7 connection. For large or handshake-driven data, use the T-blocks FB12 BSEND / FB13 BRCV (up to 65534 bytes) or FB8 USEND / FB9 URCV (up to 440 bytes, unacknowledged). Always use the FB variants, never SFB14/SFB15 — the SFB versions are S7-400 only.

Is the PROFINET port base address (e.g. 2044*) the correct LADDR for AG_SEND?

No. The 2036*–2047* range visible in HW Config on the IM151-8 are diagnostic addresses for the integrated PROFINET IO controller slots, not data LADDRs. AG_SEND's LADDR must point to a user I/O area (input or output image of a real module). The cleanest fix is to switch to PUT/GET, which does not use LADDR at all and instead references a remote DB on the partner CPU by offset.

Do I need OB121 / OB122 on the IM151-8 to prevent CPU STOP on I/O access errors?

Yes, for production hardening. Without OB122 loaded, a single I/O access error on a PROFINET slot takes the IM151-8 to STOP. Loading OB122 (with at minimum a BE instruction, ideally a flag set) converts the access error to a logged diagnostic event. Load OB82, OB83, OB86, OB121 and OB122 on any IM151-8 used as a PROFINET IO controller.

What is the connection ID that PUT/GET expects?

The connection ID is the 16-bit integer shown in the NetPro connection properties (right-click the S7 connection → Object Properties → General → Local ID). Pass it to the ID input of FB14/FB15 as a WORD constant (for example W#16#1 for ID = 1). It is not the partner IP, not the connection name, and not a hash of either.

Can PUT/GET access optimised DBs on a partner S7-1500?

On an S7-1500 partner, PUT/GET can read/write optimised DBs only by absolute offset (P#DBxx.DBXy.z BYTE n) and only if the partner CPU's access protection is configured to allow PUT/GET (CPU Properties → Protection & Security → Connection mechanisms → Permit access with PUT/GET communication from remote partner = enabled). Symbolic access to optimised blocks is reserved for the S7-1500's own program execution.

Back to blog