KTP1200 Basic HMI: Detecting PLC Communication Loss Without VBS
Second-generation SIMATIC KTP1200 Basic panels (6AV2 123-2MB03-0AX0 and the wider KTP Basic 2nd family) intentionally exclude the VBScript runtime and the Comfort-class scheduler that normally drive PLC life-bit monitoring. The panel still ships the full PROFINET connection stack, the area-pointer engine, and the system-event dispatcher — so the connection can absolutely be evaluated, but the diagnostic path runs through different features than on a TP/Comfort panel. This reference shows the three working methods (System Event 140001, Coordination area pointer, and PLC-driven watchdog tag) and the constraints of each on Basic firmware.
1. Why Basic Panels Constrain the Standard Diagnostic Path
Comfort panels execute a VBScript environment that runs in the background. Typical Comfort code used to monitor the PLC connection looks like this:
' Comfort-panel VBS — NOT supported on Basic panels
If SmartTags("HMI_LifeBit_Heartbeat") = SmartTags("HMI_LifeBit_LastValue") Then
SmartTags("CommState") = 1 ' connection lost
SmartTags("LostTime") = SmartTags("LostTime") + 1
End If
SmartTags("HMI_LifeBit_LastValue") = SmartTags("HMI_LifeBit_Heartbeat")
The Basic runtime (WinCC RT for KTP Basic 2nd Generation) omits the scripting host. Per the official SIMATIC HMI HMI devices Basic Panels 2nd Generation operating instructions, the only programmable responses available in the Events tab of a screen object are limited to system functions (SetBit, ResetBit, SetValue, ActivateScreen, UpdateTag, Logoff, StopRuntime, etc.). The job scheduler and global scripts — features relied on by Comfort programmers — are absent on the Basic runtime image.
This forces the engineer to detect a lost connection using only:
- System events raised by the runtime itself (notably
140001and140000). - Area pointer Coordination (the life bit, generated by the HMI for the PLC, but the inverse read is also possible via tag polling).
- PLC-driven watchdog tags that are refreshed by the controller and visibly decay on the screen when the link drops.
2. System Event 140001 — Connection Aborted
The Basic runtime logs a discrete system event the moment a configured connection to a PLC is torn down or fails to be established. The relevant event IDs (decimal) are:
| Event ID | Category | Trigger | Basic Panel Support |
|---|---|---|---|
| 140000 | Connection | Connection established / re-established | Yes |
| 140001 | Connection | Connection aborted (HMI lost the PLC) | Yes |
| 140002 | Connection | Connection fault (authentication / partner unreachable during startup) | Yes |
| 140004 | Connection | Connection terminated (partner rejected / wrong slot) | Yes |
On a Comfort panel, 140001 can be wired in the HMI Alarms > System Events editor to fire a function list that, for example, sets a tag and activates an error screen. On a Basic panel, the supported response in the same editor is restricted to the system function palette. Per the KTP Basic Manual the following functions are available on 140001:
-
SetBit/ResetBiton an internal HMI tag -
SetValueon an internal HMI tag -
ActivateScreen(jump to a dedicated "No PLC Communication" screen) -
StopRuntime(use only on safety-relevant panels)
2.1 Wiring the Function on Event 140001
- In the TIA Portal project tree open HMI Alarms &emdash System Events.
- Locate event 140001 ("Connection to PLC aborted").
- Right-click the row and choose Properties > Events > OnAppear.
- Add the system function
SetBiton the HMI-internal tagHMI_Comm_OK= 0 (false). - Add a second function
ActivateScreenpointing to screenscreen_ComLoss. - Repeat on event 140000 (OnAppear) and call
ResetBitonHMI_Comm_OKandActivateScreentoscreen_Overview.
This is the cleanest method because it is driven by the runtime itself — no PLC cooperation is required. The trade-off is that HMI_Comm_OK only updates when the runtime actually re-evaluates the connection. If the panel is on a switch port that has been administratively shut, the event can take one polling cycle (default 1 s) to arrive.
3. Area Pointer Coordination and the Life Bit
The Coordination area pointer is a fixed bit-mapped word at a configurable address that the HMI updates on every acquisition cycle. The most commonly used bit (bit 0) is the HMI life bit. The PLC reads that bit to detect a dead panel, but the same word can be polled in the opposite direction using an additional tag to detect whether the HMI is still receiving new values from the PLC.
3.1 Configuration in TIA Portal
- Open the HMI device configuration, select Connections > <PLC> > Area Pointers.
- Activate Coordination. Assign the PLC tag
DB_HMI_Coord.DBW0 (or a flag word such asMW100). - Confirm that the acquisition mode is set to Cyclic continuous (the default).
- Build and download the project.
3.2 Bit Layout of the Coordination Word
| Bit | Meaning | Direction |
|---|---|---|
| 0 | HMI Life Bit (toggles every acquisition cycle, default 1 s) | HMI → PLC |
| 1 | Project ID 1 (active when project A is loaded) | HMI → PLC |
| 2 | Project ID 2 (active when project B is loaded) | HMI → PLC |
| 3 | Project ID 3 (active when project C is loaded) | HMI → PLC |
| 4 | Project ID 4 (active when project D is loaded) | HMI → PLC |
| 5 | Operating mode: 0 = Online, 1 = Offline | HMI → PLC |
| 6–7 | Reserved | — |
| 8 | PLC Life Bit placeholder (read from a tag the PLC writes) | PLC → HMI |
| 9–15 | User-defined (often used as a second heartbeat direction) | PLC → HMI |
Bits 0–7 are written by the panel. The Basic runtime does not itself monitor bits 8–15, so the symmetric watchdog must be implemented as a regular HMI tag polled from the PLC. That tag is the foundation of the next method.
4. Configuring a PLC-Driven Watchdog Tag
The workhorse for Basic panels is a single bit (or a free-running counter) in the PLC that toggles faster than the HMI acquisition cycle. When the HMI stops seeing that value change, the panel's copy of the tag simply freezes, which can be used as a visible dead-link indicator.
4.1 S7-1200 / S7-1500 Ladder Snippet
// OB1 - Cyclic heartbeat from the PLC to the HMI
// Symbol: "HMI_Heartbeat" BOOL, located at %DB20.DBX0.0
// Acquisition cycle on the HMI = 500 ms, so toggle every 250 ms
A "SysClock_1Hz" // System clock, 1 Hz, 50 % duty
= "HMI_Heartbeat" // BOOL visible to the HMI
For a free-running counter instead of a bit, use the standard IEC timer pattern:
// Counter toggling 0..255, cycle 2.55 s at 100 ms tick
// Symbol: "HMI_Heartbeat_Cnt" BYTE @ %DB20.DBB1
CALL "TON_TIME" , DB_Ton_100ms
IN := TRUE
PT := T#100ms
Q := #pulse
A #pulse
FP #edge
JC incr
incr: L "HMI_Heartbeat_Cnt"
+ 1
T "HMI_Heartbeat_Cnt"
NOP 0
4.2 HMI-Side Tag Setup
- Open the HMI tag table and add
HMI_Heartbeat(BOOL) orHMI_Heartbeat_Cnt(BYTE). Point it to the matching PLC address (e.g.%DB20.DBX0.0or%DB20.DBB1). - Set Acquisition mode = Cyclic continuous and Acquisition cycle = 500 ms.
- Create an internal HMI tag
HMI_Heartbeat_Last(BOOL or BYTE) of the same type. - On a screen, place an animation that compares the two tags.
5. Detecting Loss on the HMI Without Scripts
Because Basic panels do not run a script, the comparison has to be expressed as a single-tag animation that is driven by a small PLC-side dead-band computation. The PLC detects the freeze and writes a dedicated comm_OK bit. The HMI then animates a graphics object (icon, lamp, screen background) off that bit.
5.1 PLC-Side Dead-Band Logic
// DB20 - Heartbeat watchdog
// HMI_Heartbeat_Cnt : BYTE (live, counter from HMI_Heartbeat_Cnt above)
// HMI_Comm_OK : BOOL (true = OK, false = dead)
// t_Watchdog : TIME (10 s timeout)
A "HMI_Heartbeat_Cnt" // trigger on each new value
<> "HMI_LastCount" // did the value change?
= "edge_new"
// Block: Edge detection + TON (SCL, FB "HMI_LinkWatchdog")
IF "HMI_Heartbeat_Cnt" <> "HMI_LastCount" THEN
"HMI_Comm_OK" := TRUE; // link is alive
"HMI_LastCount" := "HMI_Heartbeat_Cnt";
"HMI_LinkTimer".TON(IN := FALSE);
ELSE
"HMI_LinkTimer".TON(IN := TRUE, PT := T#10s);
IF "HMI_LinkTimer".Q THEN
"HMI_Comm_OK" := FALSE; // link declared dead
END_IF;
END_IF;
Pick the timer preset so that PT > 2 × HMI acquisition cycle — for a 500 ms cycle that means at least T#1.5s, but T#10s is recommended to ride out normal PROFINET reconfiguration after a controller restart.
5.2 HMI Animation Recipe
- Insert a circle object on the start screen.
- Open Properties > Appearance > Visibility and bind the expression to
{HMI_Comm_OK} = 0(Basic panels use WinCC flexible-style expression syntax). - Bind the Background color of a second lamp to
{HMI_Comm_OK}: green for 1, red for 0. - Add a text field bound to the same tag, with two text lists ("Connection OK" / "No PLC Communication").
This delivers a clearly visible warning the moment the heartbeat stops moving, without any VBScript.
6. HMI Tag Polling and the Acquisition Cycle
Several of the methods above rely on the HMI acquisition cycle. The KTP Basic 2nd Generation supports cycles between 100 ms and 5 s. Sub-100 ms cycles are not supported; the system silently rounds down. Recommended values:
| Use Case | Acquisition Cycle | Watchdog Timer Preset (PLC) |
|---|---|---|
| Operator panel (machine-level) | 500 ms | T#3s |
| Process panel (line-level) | 1 s | T#5s |
| Slow link, lossy wireless bridge | 2 s | T#10s |
7. PROFINET Network Prerequisites
For the diagnostics to mean anything the underlying PROFINET connection must be physically and logically healthy. Before commissioning the watchdog logic, verify the following points (per the TIA Portal HMI-to-PLC communication documentation):
- The HMI and PLC IP addresses are on the same subnet. Default for a KTP1200 Basic is 192.168.0.1, but a static address out of the project range is required for production use.
- The PROFINET device name is assigned and matches the configured name in the HMI connection editor.
- The PLC and HMI are online in the same TIA Portal project — TIA will refuse to download a connection to a device whose device name does not match.
- The S7-1200/S7-1500 Protection settings allow PUT/GET communication from the HMI (CPU properties > Protection > Permit access with PUT/GET). Without this flag the KTP1200 cannot read or write the data blocks that drive the watchdog.
- Any managed switch between the panel and the CPU forwards LLDP frames — the KTP1200 Basic 2nd Generation uses LLDP for neighbour detection.
8. Verification Procedure After Download
- Download the PLC project first, then the HMI project. Order matters because the HMI checks partner reachability at startup.
- Power-cycle the HMI and confirm that the start screen shows
HMI_Comm_OK = 1(green lamp). - Disconnect the PROFINET cable at the CPU side. Within two acquisition cycles the green lamp must turn red and the comm-loss screen must appear.
- Reconnect the cable. Confirm that the lamp returns to green within three acquisition cycles (PROFINET re-establishment + HMI re-sync).
- Stop the CPU (toggle the S7-1200 mode switch to STOP). The lamp must turn red. Switch back to RUN — the lamp must return to green within 5 s.
- Open HMI Alarms > System Events in the HMI runtime buffer (Control Panel > System > Event Log) and confirm that event 140001 was raised exactly once during the cable disconnect, and 140000 exactly once on reconnect.
9. Troubleshooting Matrix
| Symptom | Likely Root Cause | Fix |
|---|---|---|
| Lamp stays red on start-up even though PROFINET is up | PLC protection blocks PUT/GET; tag reads return quality "bad" | Enable "Permit access with PUT/GET from remote partner" in CPU properties |
| Lamp flickers every 5–10 s | Acquisition cycle shorter than PLC scan; heartbeat toggle aligned with scan boundaries | Use a TON-based free-running counter; increase PLC watchdog PT to 3× acquisition cycle |
| System event 140001 fires but screen does not change | Event configured on alarm text row instead of the line above the text | Edit Properties > Events of the 140001 alarm line, not its text row |
| Coordination word reads 0 in PLC | Area pointer not enabled or DB address overlaps with code | Re-add Coordination area pointer; rebuild project; re-download |
| Lamp stays green even with cable unplugged | Tag configured "Cyclic on use" and the visible object is hidden, so the tag is not polled | Switch acquisition mode to "Cyclic continuous" for the heartbeat tag |
| 140002 raised instead of 140001 at start-up | HMI project references a connection that is not present on the CPU | Verify the connection name and partner IP/TSAP in the HMI connection editor |
| Life bit toggles correctly in the PLC, but HMI still shows old value after reconnect | Area pointer length or DB number mismatch after a partial download | Re-download the entire HMI project, not just the changes |
10. Field-Proven Caveats
- Firmware V14 vs V15/V16: On V14 the Events tab for system events is hidden by default; you must enable Show all alarms in the toolbar of the HMI Alarms editor. V15 onward shows the Events tab on every line.
- Multiple connections: If the HMI has two PLCs configured, the Coordination area pointer is per connection, but 140001 is a global system event. Check the connection name in the alarm text to disambiguate.
- StopRuntime on 140001: Calling StopRuntime from 140001 will shut the panel down, which is rarely what is wanted on a Basic panel that is the only operator interface for the cell. Prefer ActivateScreen + a sticky comm-loss bit.
- S7-200 / LOGO! compatibility: KTP Basic panels can also connect to S7-200 and LOGO! 8 controllers. The Coordination area pointer is supported, but the watchdog SCL snippet above assumes S7-1200/1500 syntax. Translate the counter block to ladder for the older families.
11. Quick Reference — Recommended Implementation
| Layer | Mechanism | Latency | Effort |
|---|---|---|---|
| Runtime | System Event 140001 → SetBit / ActivateScreen | 1 acquisition cycle | Lowest |
| PLC | Heartbeat counter with PLC-side watchdog timer | PT = 3× cycle | Medium |
| Area pointer | Coordination life bit read in PLC | 1 cycle | Lowest |
| Combined | 140001 + PLC watchdog bit + visible lamp | 1–3 cycles | Recommended |
For a production cell, combine the System Event 140001 path with the PLC-driven watchdog. They cover complementary failure modes: 140001 catches network-level drops (cable, switch, name mismatch) while the watchdog catches a frozen or scan-overrun CPU where PROFINET stays nominally up but the data is stale.
FAQ
Can I run a VBScript on a KTP1200 Basic to detect a lost connection?
No. The Basic 2nd Generation runtime does not include the VBScript host. Detection must be implemented with system events, area pointers, and PLC-driven watchdog tags. See the SIMATIC HMI Basic Panels 2nd Generation manual for the supported function set.
What is the difference between System Event 140001 and the Coordination life bit?
140001 is a runtime event raised when the HMI detects that the connection to the PLC is physically or logically down. The Coordination area pointer is a data area (default 1 word) that the HMI writes every acquisition cycle so the PLC can monitor the HMI. They are independent signals and are normally combined for full coverage.
What acquisition cycle should I use for the heartbeat tag?
500 ms is the practical minimum for operator panels; 1 s for process-level HMI. The PLC watchdog timer should be at least three times the acquisition cycle, e.g. T#3s for 500 ms, T#5s for 1 s. Below 100 ms the Basic runtime rounds up the cycle, defeating the purpose.
Do I need to enable PUT/GET access on the S7-1200 for the watchdog to work?
Yes. The KTP1200 reads its tags from the CPU using S7 communication, which requires "Permit access with PUT/GET from remote partner" under CPU Properties > Protection. Without it, the tag quality is "bad" and the heartbeat will not be read at all, so the watchdog would declare a healthy link as failed. The TIA Portal HMI-to-PLC communication page lists this prerequisite explicitly.
Why does the lamp stay red even though I can ping the CPU from the panel?
A successful ping only confirms Layer 3 reachability; the HMI connection also requires the configured PROFINET device name, an S7 connection entry on the HMI side, and PUT/GET permission on the CPU. A common cause is a stale device name after a controller replacement — re-assign the PROFINET name in the CPU's Online > Accessible Nodes view and reload the HMI project.