A LinuxCNC retrofit using a Mesa 6i25 with 7i77 and 7i76 daughtercards can show digital I/O in PNCconf while omitting the 7i77 analog-output and encoder configuration panes. The evidence identifies two separate checks: confirm the FPGA firmware matches the daughtercard combination, then test PNCconf under an English Debian locale. In the reported Debian 10 Buster, PREEMPT-RT, LinuxCNC 2.8.2 installation, changing the interface from French to English restored the missing panes.
Identify the Failure Mode
| Observation | Interpretation | Next check |
|---|---|---|
| 7i77 and 7i76 digital I/O appear, but the 7i77 analog-output and encoder panes do not | The interface is incomplete; this does not by itself prove that the hardware is absent | Verify the loaded FPGA firmware, then test the English locale |
| The expected pin map does not appear during the firmware readback | The installed firmware may not match the 7i77/7i76 combination | Use the matching bitstream and repeat readback |
| The panes appear in English but disappear in French | The reported fault is associated with PNCconf localization rather than encoder wiring | Create the initial configuration in English |
Separate Firmware Mapping from the Locale Defect
Do not treat the missing panes as a single-cause failure. The 6i25 must first expose the correct I/O mapping for both daughtercards. The recorded firmware package contains 5i25_7i77_7i76.bit for programming and 5i25_7i77_7i76.pin for reviewing the expected I/O assignment. Although the installed board is identified as a 6i25, the supplied filenames use the 5i25 prefix; preserve the package filename instead of silently renaming it.
If firmware readback matches the pin file but PNCconf still omits the analog-output and encoder pages, switch the Debian interface to English. Reinstalling Debian did not correct the reported behavior, while changing the locale did.
Verify and Load the FPGA Firmware
Install, power, and configure the Mesa card before running the firmware utility. The evidence records the following Mesaflash sequence. Confirm the command syntax supported by the installed Mesaflash package before use because no official command reference was supplied with the case.
- Place
5i25_7i77_7i76.bitin the command's accessible working path. A file-not-found error occurred until the bitstream was placed where Mesaflash could locate it. - Read the current mapping and compare the output with
5i25_7i77_7i76.pin.sudo mesaflash device --5i25 --readmid - If the mapping is wrong, perform the recorded fallback write, reload, and readback.
sudo mesaflash device --5i25 --fallback --write 5i25_7i77_7i76.bit sudo mesaflash device --5i25 --fallback --reload sudo mesaflash device --5i25 --readmid - Only after the fallback image produces the expected mapping, perform the recorded permanent write and verify it again.
sudo mesaflash device --5i25 --write 5i25_7i77_7i76.bit sudo mesaflash device --5i25 --reload sudo mesaflash device --5i25 --readmid
Restore the Missing PNCconf Pages
- Start PNCconf and select the
7i77_7i76configuration. - If only digital I/O appears, change Debian from French to English and restart PNCconf.
- Confirm that the 7i77 pane labeled PWM and the encoder configuration pane are now present.
- Create the initial machine configuration in English. After generation, return Debian to French if required; the reported system retained operation even though the localized configuration-window problem remained.
- For later customization, edit the generated INI and HAL files directly instead of depending exclusively on the configuration utility.
Verify Hardware and Configuration
Use three independent acceptance checks. First, Mesaflash readback must correspond to the I/O assignments documented in 5i25_7i77_7i76.pin. Second, PNCconf in English must display both the 7i77 analog-output/PWM pane and the encoder pane. Third, connect an encoder and verify that LinuxCNC reports its motion; the reported installation passed this encoder test after the panes became available.
Do not proceed from a visible digital-I/O list alone. It confirms only that some configuration data is available, not that the required analog and encoder functions have been exposed and configured.
FAQ
Why are the 7i77 analog outputs missing in PNCconf?
First verify that the FPGA mapping matches 5i25_7i77_7i76.pin. If it does, run PNCconf with Debian set to English; the reported French interface omitted the 7i77 PWM and encoder panes.
Which firmware file matches the 6i25, 7i77, and 7i76 setup?
The recorded package used 5i25_7i77_7i76.bit, with 5i25_7i77_7i76.pin documenting the I/O mapping. The filename retains a 5i25 prefix even though the installed host card was identified as a 6i25.
How do I verify the PNCconf fix?
Confirm that the English interface displays the 7i77 PWM and encoder pages, then connect an encoder and verify that LinuxCNC reads its movement. Reinstalling Debian is not supported as a fix because it did not change the reported locale-dependent behavior.