Migrating SIMATIC MP 377 to TP1500/TP1900 Comfort: Field Guide

David Krause14 min read
SiemensTechnical ReferenceTIA Portal
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Migrating SIMATIC MP 377 to TP1500/TP1900 Comfort Panels

The SIMATIC MP 377 15" Touch (article number 6AV6644-0AB01-2AX0) has been phased out of the Siemens HMI catalog. Field replacements with spare-part stock are no longer sustainable, and most plants now face a forced migration to the Comfort Panel family. The two practical successors that preserve the 15" to 19" footprint of the original installation are the TP1500 Comfort (6AV2124-0QC02-0AX1) and the TP1900 Comfort (6AV2124-0UC02-0AX1). This reference covers the engineering workflow, software prerequisites, project-recovery options, and verification checks required to complete the swap with minimum downtime.

Important: A USB backup (ProSave) from the MP 377 contains runtime files only. It cannot be restored on a Comfort panel and cannot be reverse-engineered into an editable WinCC flexible or TIA Portal project. If the engineering source is unavailable, the original project file (*.fwx for WinCC flexible 2007) must be reconstructed before migration can proceed.

1. Overview: Why Migrate to a Comfort Panel

The MP 377 was configured with WinCC flexible 2007 and belongs to the second-generation x77/x70 platform that uses a 4:3 XGA LCD with CCFL backlight. The Comfort family replaces this with:

  • 16:9 widescreen TFT with LED backlight (no inverter to fail)
  • Higher pixel density (1366 x 768 vs 1024 x 768)
  • Configuration under TIA Portal with the WinCC Comfort / Advanced / Professional engineering toolchain
  • Modernized OPC UA, SNMP, and Sm@rtServer capabilities
  • Significantly higher internal flash and RAM budgets

For most machine builders the migration is mandatory: spare-part availability on MP 377 drops off sharply five years after product phase-out, and Siemens support escalations on WinCC flexible are limited.

2. Hardware Comparison: MP 377 vs TP1500 vs TP1900 Comfort

The table below summarises the key parameters that influence cut-out, project sizing, and commissioning. Always cross-check the exact variant on the device label before ordering.

Parameter MP 377 15" Touch TP1500 Comfort TP1900 Comfort
Article number 6AV6644-0AB01-2AX0 6AV2124-0QC02-0AX1 6AV2124-0UC02-0AX1
Display diagonal 15" (38.1 cm) 15.4" (39.1 cm) 18.5" (47 cm)
Resolution 1024 x 768 (XGA, 4:3) 1366 x 768 (WXGA, 16:9) 1366 x 768 (WXGA, 16:9)
Color depth 16.2 M colors 16.2 M colors 16.2 M colors
Touch Analog resistive Analog resistive Analog resistive
Backlight CCFL (service part) LED, dimmable LED, dimmable
PROFINET 1 x onboard (PN/IE) 2 x onboard (PN/IE) 2 x onboard (PN/IE)
PROFIBUS DP 1 x onboard MPI/PB 1 x onboard MPI/PB (variant-dependent) 1 x onboard MPI/PB (variant-dependent)
USB 2 x USB 2.0 host 2 x USB host (2.0/3.0 mixed by variant) 2 x USB host (2.0/3.0 mixed by variant)
Configuration tool WinCC flexible 2007 TIA Portal + WinCC Comfort TIA Portal + WinCC Comfort
Operating voltage 24 V DC 24 V DC 24 V DC
Footprint warning: Both Comfort panels have a wider cut-out than the MP 377 15". The TP1500 Comfort in particular requires approximately 396 x 262 mm of cut-out; the MP 377 15" needs approximately 367 x 287 mm. Verify the bezel dimensions against the cabinet before specifying the TP1500 Comfort. If the existing cut-out cannot be enlarged, the TP1900 Comfort (which typically fits new cabinets at 465 x 319 mm) is the easier drop-in only if the cabinet depth is sufficient.

3. Software Migration Path: WinCC flexible 2007 to TIA Portal

The migration is not a single-step file copy. The path has three phases:

  1. Open the original project in WinCC flexible — WinCC flexible 2008 SP2 or SP3 is recommended because it can read .fwx files generated by WinCC flexible 2007.
  2. Run the TIA Portal migration wizard — from Project → Migrate project, which converts the WinCC flexible database into the TIA Portal equivalent.
  3. Re-target the device and recompile — change the HMI device from MP 377 15" Touch to TP1500 Comfort or TP1900 Comfort, then address layout, screen, and connection differences.

Siemens maintains a dedicated migration FAQ at support entry 109765132 which collects the most common field issues during this path. Read it before committing to the migration window.

4. Hardware Support Packages (HSP) and Required TIA Portal Versions

Comfort panels are supported from TIA Portal V13 SP1 upward, but for current firmware (V14.0.x and above) Siemens recommends TIA Portal V14 SP1 with the matching HSP. The HSP is installed separately via Options → Support Packages in the TIA Portal and adds:

  • Device description (GSD/GSDML-aware PROFINET and PROFIBUS profiles)
  • Firmware update images that can be pushed to the panel during commissioning
  • Functional scope additions such as OPC UA server certificates

Without the correct HSP installed, the target Comfort panel will not appear in the device catalog and the project cannot be compiled to it. A typical prerequisite stack:

TIA Portal V14 SP1 Update 7 (or later)
+ WinCC Comfort/Advanced V14 SP1 Update 7
+ HSP for Comfort Panels V14.0.x
+ HSP for legacy PLC connection (e.g. S7-300/ET 200S if applicable)
License note: Configuring a Comfort panel requires a valid WinCC Comfort, WinCC Advanced, or WinCC Professional license. WinCC flexible licenses do not transfer; a new license key (USB or Software Entitlement) must be present on the engineering station. A floating license on a license server is also acceptable.

5. Project Source Recovery: Backup File vs Source Project

This is the most common failure point of the entire migration. A field technician arriving at the cabinet typically finds one of the following:

Available artefact Recoverable? Notes
WinCC flexible source project (.fwx) Yes, full migration Preferred path. Contains all screens, tags, alarms, scripts, recipes.
Backup file (*.psb, ProSave) on USB No, runtime only Can only be restored to the same MP 377 panel. Cannot be loaded to a Comfort panel.
Upload from running MP 377 Conditional Possible only if the original programmer enabled the Upload to programming device option during download. Results in a partially recovered project (no scripts, partial recipes).
Reverse document (PDF printout of screens) No, manual reconstruction Last resort. Re-create the project in WinCC flexible first, then migrate.

To check whether the running MP 377 supports a recovery upload:

  1. Connect a PG/PC running WinCC flexible 2008 SP2/SP3 to the MP 377 over PROFINET or MPI/PROFIBUS.
  2. Open Project → Transfer → Backup — if the panel allows an upload, a project tree appears.
  3. Save the recovered project as a new .fwx file.
  4. Run the TIA Portal migration wizard on that file.

6. Pre-Migration Engineering Checklist

Complete the following checklist before scheduling the cabinet outage. Each item reduces the risk of an extended commissioning window.

  • Original WinCC flexible .fwx file located and verified to open in WinCC flexible 2008 SP2/SP3.
  • TIA Portal V14 SP1 (or target version) installed on the engineering station with matching WinCC Comfort license.
  • Correct HSP package(s) installed. Verify under Options → Support Packages.
  • PLC program and symbol table exported from STEP 7 / TIA Portal and available for re-import on the HMI side.
  • Cabinet cut-out dimension verified against the selected Comfort panel datasheet.
  • 24 V DC supply capacity checked: TP1500 Comfort typically draws ~1.5 A at 24 V, TP1900 Comfort ~2.0 A. Compare against existing PSU sizing.
  • Network topology — IP address plan, PROFINET device name, PROFIBUS station address documented.
  • Backup of all PLC programs, drive parameters, and SCADA configuration before the swap.
  • Operator screens printed or screenshotted as a reference for layout adaptation.
  • Spare USB stick with ProSave-compatible format (FAT32) prepared for firmware and image download.

7. Step-by-Step Migration Procedure

The procedure below assumes a successful migration from a WinCC flexible 2007 project to a Comfort panel on TIA Portal V14 SP1. Plan a 4 to 8 hour window for a typical mid-size project (50 screens, 800 tags, 200 alarms).

7.1 Open the source project

  1. Launch WinCC flexible 2008 SP2 (or SP3) on the engineering station.
  2. Open the original .fwx project. Resolve any compile warnings before continuing.
  3. Save a clean copy under a new name (e.g. Project_migrate.fwx) so the original remains untouched.

7.2 Migrate to TIA Portal

  1. Launch TIA Portal V14 SP1.
  2. Select Project → Migrate project and choose the cleaned WinCC flexible project.
  3. Select the target HMI device: TP1500 Comfort (15.4") or TP1900 Comfort (18.5").
  4. Accept the proposed migration. The migration log is stored in the project directory as MigrationLog.txt — review every warning before continuing.

7.3 Re-target the device

  1. In the TIA Portal project tree, right-click the HMI device and select Change device if you need to switch from a trial TP1500 to TP1900.
  2. Verify the connection list. PROFINET connections to S7-300/400/1200/1500 controllers are typically carried over unchanged, but confirm the slot assignment and IP address.
  3. Re-bind any HMI tags that were using external tag sources from STEP 7. The HMI tag database is rebuilt under HMI tags → Show all tags.

7.4 Compile and download

  1. Right-click the HMI device and select Compile → Software (rebuild all).
  2. Resolve any errors flagged in the Info editor. Common issues include deprecated function calls, unsupported fonts, and missing graphics.
  3. Transfer the project to the Comfort panel over PROFINET using the panel's IP address, or via USB using a ProSave-compatible stick.

8. Layout Adaptation: 4:3 to Widescreen Conversion

The aspect-ratio change from 4:3 (1024 x 768) to 16:9 (1366 x 768) means horizontal width grows by approximately 33% while vertical height stays the same. Screens designed for the MP 377 will appear stretched if simply retargeted. The recommended approach is:

  1. Use the TIA Portal Adapt screen tool (Runtime settings → Screen → Adapt to new device) as a starting point.
  2. Manually re-flow objects left-to-right and rebalance vertical spacing.
  3. Resize fixed-size elements (buttons, I/O fields) using the Arrange → Resize tools. Keep touch-target sizes at least 12 mm x 12 mm for operator gloves.
  4. Re-export any custom graphics at 1366 x 768 native resolution to avoid interpolation artefacts.

A quick ratio check for objects moved between screens:

Scale factor X = new_width / old_width = 1366 / 1024 = 1.334
Scale factor Y = new_height / old_height = 768 / 768 = 1.000

Use 1.334 as the horizontal scaling factor and 1.000 vertically. Operators should always re-validate alarm acknowledgment and emergency stop button placement after the layout pass.

9. Tags, Alarms, and Scripts Conversion

The migration wizard carries most tags and alarms over, but several categories need explicit review:

WinCC flexible element Comfort equivalent Action required
Tags (internal, external) HMI tags, PLC tags Re-bind external tags to the correct PLC connection.
Discrete alarms Alarm classes (errors, warnings) Confirm acknowledgement groups match operator workflow.
Analog alarms Alarm classes with limits Convert limit tables; check dead-band values.
VB scripts VBScripts (mostly compatible) Replace deprecated HMIRuntime functions with the Comfort API equivalents.
C scripts Not directly migrated Re-author as VBScript or as PLC-side logic.
Schedulers Scheduler (events) Re-confirm trigger times, especially for daylight-saving plants.
User administration User administration (UMC) Re-import user groups; review password-hash compatibility.
Script warning: Several legacy WinCC flexible scripting APIs were removed or renamed in TIA Portal V14. After migration, run a project-wide search for any HMIRuntime. call that the compiler flags, and replace with the Comfort equivalents. Common substitutions include SetValue becoming HMIRuntime.Tags.Item(...).Write, and screen navigation going through ActivateScreenByNumber only.

10. Communication, Recipes, and Historical Data

10.1 Communication

PROFINET and PROFIBUS connections migrate with the project. Verify the following in TIA Portal after migration:

  • PLC station number / IP address is unchanged.
  • PROFINET device name matches the plant standard (commonly the same as the old MP 377).
  • Update rate and watchdog times are still appropriate for the Comfort panel's faster CPU.
  • If the original project used an S7-200 or older S7-300 MPI connection, verify the Comfort panel still supports that protocol via the appropriate HSP.

10.2 Recipes

Recipes migrate to the Comfort format but the on-disk path changes. After commissioning, copy any saved recipe files from the old MP 377 backup (under /Recipes) to the Comfort panel using ProSave or an FTP transfer. Verify the data record import paths under Recipes → Properties → Storage.

10.3 Historical data

WinCC flexible archives on the MP 377 cannot be opened in WinCC Comfort directly. Plan to export the historical data while the old panel is still running, or accept that historical archives will restart on the new Comfort panel.

11. Verification and Acceptance Testing

Run the following verification suite on the Comfort panel before handing it back to operations:

  1. Tag polling verification — force a known PLC tag, confirm the HMI display updates within one update cycle.
  2. Alarm acknowledgement — trigger an alarm from the PLC, acknowledge from the Comfort panel, confirm the alarm clears and the audit log records the operator.
  3. Recipe round-trip — save a recipe, modify a data record on the Comfort panel, restore, confirm the PLC values match.
  4. Touch calibration — touch each of the four screen corners and the centre; the cursor must track within 1 mm.
  5. Backlight and screen-saver — set the screen-saver timeout to match the original MP 377 setting; confirm the backlight dims to the planned value.
  6. User administration — log in as each role; confirm visibility restrictions and button-level authorisations.
  7. Network connectivity — confirm Sm@rtServer (if used) is reachable and OPC UA server certificate exchange completes.
  8. Emergency stop and safety-critical buttons — verify physical touch target is at least 12 mm x 12 mm and the button is reachable while wearing gloves.
  9. Audit log — confirm the audit log is being written to the configured location (SD card, USB, or network share).
  10. Power-cycle test — remove 24 V for 30 seconds, restore, confirm the panel auto-starts into runtime and re-establishes the PROFINET connection.

12. Troubleshooting Migration Matrix

Symptom Likely cause Remediation
Comfort panel not in device catalog Missing HSP Install the correct HSP under Options → Support Packages and restart TIA Portal.
Compile error: deprecated function VB script using legacy API Replace with the Comfort equivalent per TIA Portal help.
Compile error: tag not found External tag source not re-bound Re-link to PLC tag under HMI tags → Connection.
Stretched or clipped screen Auto-adaptation not run, or layout scaled incorrectly Use Adapt screen, then manually re-flow.
Runtime does not start after download Firmware mismatch Update panel firmware to the version matched to TIA Portal V14 SP1 HSP.
Touch response offset Touch not recalibrated after mechanical mounting Run Start Center → Control Panel → Touch and recalibrate.
PROFINET connection lost at runtime Device name reset after firmware update Re-assign PROFINET device name from TIA Portal.
Recipes not loading Storage path mismatch Check Recipe properties → Storage location; confirm SD/USB is mounted.
Historical data empty Format change between WinCC flexible and Comfort Export historical data before migration; restart archives on the new panel.
Alarm colour scheme wrong Alarm class defaults overridden Restore class colours under HMI alarms → Alarm classes.
User login fails Password hash algorithm changed Re-import user list from PLC or CSV; do not copy from MP 377 backup.

13. Frequently Asked Questions

Can the SIMATIC TP1500 Comfort directly replace an MP 377 15" Touch?

Physically no. The TP1500 Comfort (6AV2124-0QC02-0AX1) has a wider cut-out (~396 x 262 mm) than the MP 377 15" (~367 x 287 mm). The TP1500 Comfort is the closest 15" widescreen successor electrically and logically, but the cabinet cut-out must be enlarged or a different panel selected. The TP1900 Comfort is the recommended successor if the cabinet has space for a 19" widescreen bezel.

Can I restore a USB backup from the MP 377 onto a Comfort panel?

No. The ProSave backup file (*.psb) contains runtime binaries for the MP 377 platform only. Comfort panels use a different firmware and image format. A backup can only be restored to the same model of panel. To migrate, you need the original WinCC flexible source project (.fwx) or the project must be reconstructed.

Which TIA Portal version is required to configure a TP1500 or TP1900 Comfort panel?

TIA Portal V14 SP1 (or later) is the typical baseline for current Comfort firmware. The matching WinCC Comfort / Advanced / Professional license and the latest available HSP for Comfort Panels must be installed on the engineering station. Older V13 SP1 configurations are technically possible but Siemens recommends V14 SP1 or above for active support.

Is the WinCC flexible project file enough, or do I need the STEP 7 project too?

The WinCC flexible .fwx file contains screens, tags, alarms, recipes, and scripts. However, external tag references point to a STEP 7 project on the PLC side. Without the STEP 7 project (or at minimum the symbol table export), the HMI tags cannot resolve and the project will fail to compile after migration. Always export both sides of the boundary.

What if the original WinCC flexible project file is lost?

Attempt an upload from the running MP 377 over PROFINET or MPI using WinCC flexible 2008 SP2/SP3. This works only if the original programmer enabled the Upload to programming device option at download time. The recovered project will be missing scripts and some recipe data, but it is usually enough to rebuild the rest. If upload is not possible, the project must be manually reconstructed from screenshots and PLC documentation.